FläktGroup CentriFlow 3D GMPM_GMEB Built-on drive Operating instructions

Type
Operating instructions

FläktGroup CentriFlow 3D GMPM_GMEB Built-on drive is a device that can be used to control the speed of a permanent magnet synchronous motor or an asynchronous motor. It can be controlled with a 0-10 V DC signal, potentiometer, Modbus RTU or hand terminal. The hand terminal is not automatically included in the delivery but can be ordered as an accessory.

The built-on drive has an EMC filter and is equipped with an indication relays for alarm and running.

FläktGroup CentriFlow 3D GMPM_GMEB Built-on drive is a device that can be used to control the speed of a permanent magnet synchronous motor or an asynchronous motor. It can be controlled with a 0-10 V DC signal, potentiometer, Modbus RTU or hand terminal. The hand terminal is not automatically included in the delivery but can be ordered as an accessory.

The built-on drive has an EMC filter and is equipped with an indication relays for alarm and running.

FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
BUILT-ON FREQUENCY CONVERTER FW02 FOR
CENTRIFLOW 3D PLUG FAN WITH PERMANENT
MAGNET AND ASYNCHRONOUS MOTOR
CONTENT PAGE
1. Introduction ............................................................................................. 2
2. Features ................................................................................................... 2
3. Installation .............................................................................................. 2
4. Functions ................................................................................................. 8
5. Built-in protection ................................................................................. 9
6. Alarms ...................................................................................................... 9
7. Modbus ..................................................................................................... 9
8. Maintenance ......................................................................................... 13
9. Troubleshooting ...................................................................................14
10. Disposal ................................................................................................. 15
11. Technical specification..................................................................... 16
PLUG FAN GMPM, GMEB
BUILT-ON SPEED CONTROLLER
INSTALLATION AND OPERATION
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
2
1. INTRODUCTION
This frequency controller is used with permanent magnet syn-
chronous motors (PM) or asynchronous motors (AC). Speed can
be controlled with a 0-10 V DC signal, potentiometer, Modbus RTU
or hand terminal. The hand terminal (PAN-08-0) is not automati-
cally included in the delivery but can be ordered as an accessory.
Main voltage requirement is 3-phase 400 VAC. Frequency control-
ler is equipped with an EMC filter.
Built-on means that the frequency controller is mounted at the
side of the fan. If the fan service side is on the other side, the
drive can easily be moved there by opening four screws. Cabling
between motor and drive is already done.
Built-on version is ready to be used and needs only power from
mains and control signals. They can be easily connected to the
terminals under the drive’s plastic cover.
2. FEATURES
As standard, frequency controller has the following built-in
features
Modbus RTU
0-10 V analogue input for controlling speed
Control via external hand terminal
Indication relays for alarm and running
Flying start
Alarms for overload, over-voltage and under-voltage
Motor and cable protector with built-in current limiter
Short-circuit protection against phase to phase short circuiting
on motor output terminals
Digital input for “Start/stop”
Digital input for “Alarm reset” or “Fire mode”
Built-in EMC filter
Automatic speed reduction in the event of over temperature in-
side the drive or lacking phase on the supply input.
Frequency controller cooling ribs are in the air flow. Surplus heat is removed
by active ventilation.
3. INSTALLATION
3.1. MECHANICAL INSTALLATION
The built-on frequency converter is factory mounted to left side of
the fan (when looking from behind of the fan). If needed, the fre-
quency converter can be removed to the right hand side of the fan
according to the following instructions. Otherwise please use the
cable tie (delivered with the fan) to attach the motor cable to the
motor bracket/mounting plate, see point 3.1.5.
3.1.2 Loosen the upper bolts and remove lower fixing bolts (M6)
of the frequency converter mounting plate. You might need a
10 mm wrench with the upper front bolt.
Upper bolt
Lower bolt
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
3
3.1.3 Slide off the mounting plate.
3.1.4 Put the upper bolts (removed from the left hand side) on
their places on the right hand side of the motor bracket.
Bolts shall be loose enough to get the mounting plate slided
to its place. After that, attach lower bolts (also removed from
the left hand side) and tighten all bolts.
3.1.5 Attach the cable tie to motor bracket / mounting plate.
3.2. ELECTRICAL INSTALLATION
• Frequency converter must only be installed
and commissioned by trained and qualified
personnel.
• Incorrect electrical installation may cause risk
of severe or fatal personal injury.
If natural draught through the duct system causes the fan to
rotate even when it has not received an operating signal, there
is a risk that the motor will induce voltage on the frequency
converter motor terminals, making them dangerous to touch.
3.2.1. SHORT CIRCUIT PROTECTION
Correct short-circuit protection must always be used with the
frequency converter in accordance with local and international
regulations.
Short-circuit protection is supplied by the installer
3.2.2. SUPPLEMENTARY PROTECTION
Direct earthing or TN or TT system earthing can be used for
supplementary protection
Frequency converter must always be supplementary protected
with an earthing wire connected to the protective earth terminal
(PE).
If an RCD/HPFI (TT system) is used, it must be specifically in-
tended for use with motor controllers.
3.2.3. POTENTIAL EQUALISATION
There is a risk of electrical interference if the ground potential
between the frequency converter and the air handling unit or
duct differ from each other. In the event of potential differences
between system components, an equalisation conductor must
always be fitted.
Recommended cable cross section is 10 mm
2
.
Lugs should be used, and the equalisation conductor should be
attached to the frequency converter enclosure via one of the
screws used to mechanically install the unit.
3.2.4. EARTH CONNECTION (PE)
Frequency converter must be earthed in accordance with appli-
cable local and international standards and directives.
In power cable, please use an earthing lead which is suitable
for the purpose.
Frequency converter must be earthed singly and must therefore
never be earthed in series.
Keep earth connection wires as short as possible.
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
4
3.2.5. CABLE REQUIREMENTS
All cables and leads used in connection with the frequency
converter must comply with local and national rules and
regulations.
Shielded cable is not necessary for I/O and Modbus communi-
cation.
Generally, cable types with copper wires are recommended.
For recommended cable dimensions, see table 3.1 below
Power Cable gland Cable diameter Cable size, min. Cable size, max. Core sleeve/stripped min.
Power supply cable
1,5-3,0 kW M20 7-13 mm 4x1,5 mm² 4x2,5 mm² 10 mm
4,0-7,5 kW M20 7-13 mm 4x1,5 mm² 4x4 mm² 15-10 mm
11, 15 kW M25 10-17 mm 4x2,5 mm² 4x10 mm² 18-10 mm
A/D control cable
1,5-15 kW M20 7-13 mm 2x2x0,7 mm² 10x2x0,7 mm² 10 mm
Modbus round cable
1,5-15 kW M16 4-10 mm 3x2x0,7 mm² 10x2x0,7 mm² 10 mm
Modbus round cable
1,5-15 kW Telecommunication cable/ribbon cable, 6-core, unshielded, 30 AWG/0,066 mm²
Table 3.1
3.2.6. OPENING THE FREQUENCY CONVERTER
Check that the voltage supply to the frequency converter has
been disconnected before opening the cover.
Wait approx. 3 minutes after disconnecting mains voltage be-
fore removing the cover.
Frequency converter is opened by loosening the six Torx20
screws holding the plastic cover in place.
Carefully remove the loosened cover.
3.2.7. TERMINAL AND CONNECTOR OVERVIEW
Motor
3 400V
50/60 Hz
Alarm
Relay 1
Running
Relay 2
Modbus
Supply
Hand
terminal
Reset
Start/Stop
U V W
PE
L1 L2 L3 PE
BR
BR +
A
B
C
11 NC
12 C
13 N0
14 NC
01 Bus A
02 Bus B
03 GND
04 + 10 VDC
05 0 - 10Vln
06 GND
07 Din2
08 Din1
09 Dout1
10 GND
15 C
16 N0
M
3
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
5
3.2.8. MAINS VOLTAGE CONNECTION 3~400V, 50HZ
Connect power cable to terminals L1, L2, L3 and PE
It is recommended that the PE wire is 20 mm longer than the
other wires in the cable
Remember to re-tighten the cable glands to ensure ingress
protection and strain relief.
3.2.9. MODBUS CONNECTION
Frequency converter is equipped with four connectors for Mod-
bus connection.
It also features 3 x RJ12 connectors and one strip of spring ter-
minals.
On the terminal strip with spring terminals for control signals
(A/D I/O), the terminals for connecting Modbus are marked
”Bus A”, ”Bus B” and ”GND”.
If wanted, a round cable can be used for Modbus communica-
tion, connected to terminals marked ”Bus A” and ”Bus B” on the
frequency converter terminal strip. The Modbus terminals are
internally connected in parallel to the Modbus pins in the RJ12
connectors marked ”A” and ”B”.
The three 3 RJ12 connectors are marked ”A”, ”B” and ”C”.
”A”: Modbus connection, slave, +24V voltage supply in connector.
”B”: Modbus connection, slave, no voltage supply in connector.
”C”: Modbus connection, master, external equipment, e.g. PTH/
VOC.
A 6-core, unshielded, 30 AWG/0.066 mm² telecommunications
cable or similar type of ribbon cable can also be used for Mod-
bus communication.
Attach RJ12 connectors to both ends by using a special-pur-
pose tool.
L1
L2
L3
PE
MAINS
8-15 mm
Bus A
Bus B
GND
+10V DC
Same colour sequence
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
6
3.2.10. A/D CONTROL SIGNAL CONNECTIONS
Connect A/D control signals to the terminal strips
The function/programming of A/D inputs and outputs can be
changed via Modbus.
POTENTIOMETER CONTROL
+10VDC = Constant + 10VDC
0-10V In = Analogue 0-10V control input for speed
o Potentiometer, electrical connection. (Potentiometer: min. 500
Ω, recommended 4.7 kΩ)
GND = Ground (-)
EXTERNAL CONTROLLER, ELECTRICAL CONNECTION
0-10V In = Analogue 0-10V
GND = Ground (-)
DIGITAL INPUTS
Din2 = Alarm reset (factory setting)
Din1 = Start/Stop (factory setting)
DIGITAL OUTPUT
Dout1 = Alarm Out; Open Collector (factory setting)
Max. pull-up voltage 24 V, max. current 20 mA
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
7
RELAY OUTPUTS
Relay output 1: Alarm
Relay 1 (terminals 11, 12, 13) can be used to send an alarm
signal to an external device.
The signal output is a changeover relay which is closed
between terminals 11 and 12 in idle position and otherwise
closes between terminals 12 and 13.
If the frequency converter has stopped due to a critical alarm,
the relay will switch position and close between terminals 12
and 13. The relay is simultaneously opened between terminals
11 and 12.
When the alarm is reset / acknowledged, the relay returns to
its original position, closing between terminals 11 and 12.
Relay output 2: Running indication
Relay 2 (terminals 14, 15, 16) can be used to send an operating
signal to an external device.
The signal output is a changeover relay which is closed
between terminals 14 and 15 in idle position and otherwise
closes between terminals 15 and 16.
When the frequency converter receives a start signal, the relay
changes position, closing between terminals 15 and 16. The
relay is simultaneously opened between terminals 14 and 15.
When the start signal to frequency convert is removed, the
relay returns to its starting position, closing between terminals
14 and 15.
Max. 30VAC/24VDC/1A
Alarm
Relay 1
NC CNCNO NOC
1611 1312 1514
Running
Relay 2
3.2.11. HAND TERMINAL (PAN-08) CONNECTION AND FUNCTIONS
The FWD-02 frequency converter can be connected to a PAN-08
hand terminal via Modbus RJ12 connector ”A”.
If a PAN-08 is connected, the hand terminal will act as master
and the frequency converter as slave.
Only one master at a time can be connected to the RJ12 connec-
tors marked ”A” and ”B”.
It is thus not possible to connect both a hand terminal to connec-
tor ”A” and an active Modbus communication cable to connector
”B” at the same time.
PAN-08 has the following menu options:
Status: Control and operating parameters for connected fre-
quency converter
Setup: Setting application parameters
Alarm: Read-out of alarm log for connected frequency converter
Modbus: Changing Modbus settings for frequency converter
About: Read-out of software version no. and type for connected
frequency converter
Config: Changing frequency converter / motor settings.
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
8
4. FUNCTIONS
Frequency controller can be controlled via:
Analogue/digital (A/D) inputs
Modbus RTU
Local hand terminal PAN-08-0
• Potentiometer
The factory setting is Analogue/digital (A/D) control
4.1. ANALOGUE/DIGITAL CONTROL
Frequency/revolutions
Max. Hz/Rpm
Min. Hz/Rpm
0%
0V
100%
9.5V
Setpoint
Speed out
Setpoint
Max. Speed
Min. Speed
100%
0%
Time
Time
Up
ramp
Down
ramp
Frequency controller can be controlled by external input signals.
Before the frequency controller can be started, it must be given a
start/stop signal. It is given by short-circuiting terminals GND and
Din1.
Speed is controlled by connecting the control signal (0-10V DC) to
terminals 0-10V In and GND.
Relation between control signal (0-10 V In) and speed – see fig.
4.2. MODBUS CONTROL
Frequency converter can be controlled via Modbus commands
according to the Modbus protocol.
Control of motor speed via Modbus communication is factory
disabled.
If the fFrequency converter is to be controlled via Modbus, Coil
Stat Bit register 8 must be set to ”0” = ”Modbus control”.
Other functions, such as alarm read-out and acknowledgement,
are still possible via Modbus even though “Modbus control” is
not activated.
See more detailed description of Modbus in chapter 7. Modbus.
4.3. SWITCHING FREQUENCY
Switching frequency is crucial in determining the amount of audi-
ble acoustic noise emitted by the frequency converter.
The higher the switching frequency, the less audible noise will be
emitted by the frequency converter. At the same time, however,
internal losses will be increased, reducing efficiency.
The frequency converter can be set to operate constantly with a
switching frequency of either 4 kHz or 8 kHz, or it can be set to
change switching frequency automatically depending on motor
speed (AUTO setting).
Switching frequency (switching mode) is set via Modbus:
Setting ”4kHz” = Constant 4kHz switching frequency
Setting ”8kHz” = Constant 8kHz switching frequency
Setting ”AUTO” = Switching frequency is changed automatically:
At motor speeds higher than 70% of rated speed, switching
frequency is changed to 4 kHz
At motor speeds lower than 60% of rated speed, switching
frequency is changed to 8 kHz
4.4. FIRE MODE
Fire mode designates a function in which the frequency con-
verter is kept operating by an emergency program which disa-
bles the alarm monitor.
Among other things, the function can be used in connection
with smoke extraction from a burning property. When fire mode
is activated, an extraction fan will continue to remove smoke
from the property for as long as possible.
In fire mode, the frequency converter is able to maintain opera-
tion for at least an hour even when the frequency converter and
the fan motor are overheated (max. 70°C).
In fire mode, the overheating protection built into the frequency
converter is disabled and the motor is not stopped if communi-
cation is lost.
In fire mode, the fan is not stopped in case of faults or other
alarms from either the fan or the frequency converter.
Speed is controlled to the actual setting, determined by an ex-
ternal 0-10V signal, a potentiometer or via Modbus from a Mod-
bus master controller.
Fire mode can be activated via Modbus.
The control signal regulates motor speed between the set mini-
mum and maximum speeds (AC motor = Hz; PM motor = rpm)
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
9
5. BUILT-IN PROTECTION
If the temperature inside frequency converter exceeds +95°C,
the frequency converter will attempt to reduce its internal heat
generation by reducing motor speed (rpm).
Frequency converter has built-in current limitation for the pro-
tection of motor and cables and cannot therefore supply more
current than it is set to.
In the event of lacking phase on the supply input, the frequency
converter will reduce speed and activate a non-critical alarm.
The frequency converter motor output terminals are short cir-
cuit protected against phase-to-phase short circuiting.
6. ALARMS
Frequency converter has a built-in alarm monitor, which moni-
tors optimal fault-free operation and triggers an alarm if operat-
ing or performance problems are observed.
Alarms are either ”Critical” alarms or ”Non-critical” alarms.
”Critical” alarms stop the motor.
”Non-critical” alarms reduce motor performance.
The built-in alarm monitor stops the frequency converter.
If the alarm situation passes, the alarm is automatically reset
and frequency converter restarted.
If the maximum number of restarts (5 times/60 min) is exceed-
ed, the alarm must be reset manually.
The alarm can be reset by means of a Modbus command.
The alarm is automatically reset if the power is disconnected
for longer than 60 seconds.
Alarms can be read via Modbus, see Modbus protocol.
Alarm overview, see table 6.0 below
Alarm overview Alarm
priority
Motor operation/
response
Insufficient supply voltage NC RP
Excessive supply voltage CSA5
Excessive power consumption by
motor CSA5
Excessive temperature inside
FWD-02 (> 95°C) NC RP
Phase fault; one or more phases
disconnected (L1, L2, L3) CSA5
Blocked motor CSA5
Motor current has reached its limit NC RP
Internal hardware fault CSA5
Wrong direction of rotation CSA5
Fault in internal EEPROM circuit NC RP
Stopped after 5 attempted restarts
within 60 min C S
Fault in braking chopper NC RP
Phase fault on motor power supply
(U, V, W) CSA5
Internal communication error CSA5
Excessive ripple voltage NC RP
External 24VDC power supply
overloaded NC RP
Table 6.0
Abbreviations:
C = Critical alarm
NC = Non-critical alarm
RP = Reduced performance
SA5 = Motor stops after 5 restarts caused by same fault within 60
min
S = Motor stops immediately
LED INDICATIONS
Frequency converter is equipped with a two-colour LED which
indicates operating status.
The LED is located on the underside of the frequency converter
beside the entry for the mains cable.
LED lights constantly green when mains voltage is connected.
LED flashes green when Modbus communication is active.
LED lights constantly red when at least one critical alarm is
active-
LED flashes red when at least one non-critical alarm is active.
7. MODBUS
7.1. INTRODUCTION
This protocol contains the Modbus addresses and registers which
are available in the frequency converter.
Modbus can access single addresses or several addresses
simultaneously, either by reading or writing 1-bit or 16-bit values.
A Modbus address contains either a 1-bit value or a 16-bit integer.
Values in this protocol are to be changed at your own risk.
It is your own responsibility that changing of values and settings
does not cause any overload or damage to the product, motor or fan.
7.2. MODBUS REGISTER TYPES:
Modbus Type Description Reference
Coil Status (R/W) Discrete Output 0x
Input Status (R) Discrete Input 1x
Input Register (R) 16-bit Input Register 3x
Holding Register (R/W) 16-bit Output Register 4x
R=Read only, R/W = Read/Write
LED
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
10
7.3. SUPPORTED MODBUS COMMANDS
Function code Description
1Read Coil Status
2Read Input Status
3Read Holding Registers
4Read Input Registers
5Force Single Coil
6Preset Single Registers
8Diagnostics. Sub-function 00 Only - Return Query
Data (loop back).
15 Force Multiple Coils
16 Preset Multiple Registers
7.4. MODBUS ADDRESSING
Modbus addressing of frequency converter can be accomplished
in three different ways.
Via PC Tool by writing to Modbus Holding Register 4x0017
Via Hand Terminal, where frequency converter can be set to
other Modbus addresses.
Via the addressing pins of the ”A” or ”B” connectors – see fig-
ure in chapter 3.2.9. The addressing pins can be used to as-
sign the frequency converter controls the address range: 0x36
(dec.54), 0x37 (dec.55), 0x38 (dec.56) and 0x39 (dec.57), see
table below.
7.5. COMMUNICATION PARAMETERS
Communication parameters can be set using the Hand Terminal
or via a PC Tool.
You can always connect frequency converter with these fixed
values:
Parameter Range Unit Factory setting
Address 1-247 n/a 54 dec
Baud rate 9.600, 19.200,
38.400, 115.200 bps 38.400
Parity None, even, odd n/a None
Stop bit(s) 0, 1, 2 n/a 1
Communication
timeout 0-240 Sec. 0
Table 7.5.1
n/a = not applicable
You can set alternate communication parameters to Holding
registers 4x0017...4x0025. See table 7.5.5.
COIL STAT BITS - Available Coil Stat Bits are shown in the table
below.
Standard Modbus (RTU)
Coil Stat Bits: 11 (R/W)
0x01: Read
0x05: Write Single Coil (NOTE: ON => output value = 0xFF00)
0x0F: Write Multiple Coils
Register Address Function Range Active state
0x0001 0Motor ON/OFF 0 - 1 1 = ON
0x0002 1Reset Alarms 0 - 1 1 = Reset
0x0004 3Fire Mode 0 - 1 1 = Active
0x0006 5Rotation 0 - 1 1 = Clockwise
0x0007 6Disable V_Rip-
ple protection
0 - 1 1 = Disable
0x0008 7Control 0 - 1 0 = Modbus
1 = 0-10 V
0x0010 9Autodetect
communica-
tion
0 - 1 1 = Enable
0x0011 10 Analog start
signal
0 - 1 1 = Enable
0x0012 11 Inverter analog
speed input
0 - 1 1 = Invert
0x0013 12 Allow using
field weaken-
ing
0 - 1 1 = Allow FW
0x0014 13 Allow using
brake chopper
0 - 1 1 = Allow BC
0x0015 14 Allow using
cooling fan
0 - 1 1 = Allow fan
0x0016 15 Undervoltage
config.
0 - 1 0 = UV value from
CCF
1 = Fixed value
for 3x230V
Table 7.5.2
Add.
Oin no.
0X36
(54 dec)
0X37
(55 dec)
0X38
(56 dec)
0X39
(57 dec)
Add. Pin1
Add. Pin2
= No connection between “GND” and add. Pin1/Add. Pin 2
= Connection between “GND” and add. Pin1/Add. Pin 2
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
11
INPUT STAT BITS - Available input Stat Bits are shown in the table below:
Input Stat Bits 24 (R), 0x02: Read
Register Address Function Range Active state
1x0001 0V LO Alarm 0 – 1 1 = Alarm
1x0002 1V HI Alarm 0 – 1 1 = Alarm
1x0003 2I HI Alarm (Motor out short) 0 – 1 1 = Alarm
1x0004 3Temperature high 0 – 1 1 = Warning
1x0005 4Input phase error 0 – 1 1 = Error
1x0006 5Rotor Blocked 0 – 1 1 = Error
1x0007 6Limit 0 – 1 1 = Warning
1x0008 7Internal HW Fault 0 – 1 1 = Alarm
1x0009 8Rotor direction 0 – 1 1 = Alarm
1x0010 9EEPROM Error 0 – 1 1 = Warning
1x0011 10 Internal Stop 0 – 1 1 = Alarm (Stop)
1x0013 12 Brake Chopper Fault 0 – 1 1 = Warning
1x0014 13 Motor Phase Error 0 – 1 1 = Alarm
1x0015 14 Communication error MOC 0 – 1 1 = Alarm
1x0016 15 V Ripple 0 – 1 1 = Warning
1x0017 16 Digital input 1 0 – 1 1 = Hi
1x0018 17 Digital Input 2 0 – 1 1 = Hi
1x0019 18 Ext. 24 V supply overload 0 – 1 1 = Overload
1x0020 19 MOC in bootloader 0 – 1 1 = Alarm
1x0021 20 Digital input 3 (IOM) 0 – 1 1 = Hi
1x0022 21 Digital input 4 (IOM) 0 – 1 1 = Hi
1x0023 22 Communication error (IOM) 0 – 1 1 = Warning
1x0024 23 Motor Overheat (IOM) 0 – 1 1 = Alarm
1x0025 24 Windmilling 0 – 1 1 = Warning
1x0026 25 Rotation OK 0 - 1 1 = Rotation OK
Table 7.5.3
INPUT REGISTERS - Available Input Registers are shown in the table below.
Input Registers: 28 (R), 0x04: Read
Register Address Function Range PM-motor AC-motor
Resolution Unit Resolution Unit
3x0001 0Drive type 1000-? 1n/a 1n/a
3x0002 1AOC SW version 0 - ? 0,01 n/a 0,01 n/a
3x0003 2MOC SW version 0 - ? 0,01 n/a 0,01 n/a
3x0004 3PrcOut 0 - 10000 0,01 %0,01 %
3x0005 4RPMOut 0 - 3000 1RPM 0,01 Hz
3x0006 5Intern Temp -5000 - 15000 0,01 °C 0,01 °C
3x0007 6V In 0 - 500 1 V 1 V
3x0008 7I Out 0 - 30000 1mA 1mA
3x0009 8Power In 0 - 6000 1 W 1 W
3x0010 9I Ripple 0 - 32000 1mA 1mA
3x0011 10 Operation minutes 0 - 1439 1min 1min
3x0012 11 Operation days 0 - 9999 1Days 1Days
3x0013 12 V Ripple 0 - 500 1 V 1 V
3x0014 13 Config. File Variant AA-ZZ 2 ASCII characters 2 ASCII characters
3x0015 14 Config. File Version 100 - 32000 0,01 n/a 0,01 n/a
3x0016 15 ExtermSet 0 - 100000 1mV 1mV
3x0019 18 AOC SW Variant n/a n/a n/a n/a n/a
3x0020 19 AOC Boot SW 0 - ? 0,01 n/a 0,01 n/a
3x0021 20 MOC Boot SW 0 - ? 0,01 n/a 0,01 n/a
3x0022 21 Motor config. Variant 0 - 65535 1n/a 1n/a
3x0023 22 Motor config. Version 0 - 65535 0,01 n/a 0,01 n/a
3x0024 23 Fan config. Variant 0 - 65535 1n/a 1n/a
3x0025 24 Fan config. Version 0 - 65535 0,01 n/a 0,01 n/a
3x0026 25 User Data Varioant 0 - 65535 1n/a 1n/a
3x0027 26 User Data Version 0 - 65535 0,01 n/a 0,01 n/a
3x0028 27 IOM SW version 0 - ? 0,01 n/a 0,01 n/a
3x0029 28 V DC Bus (Peak) 0 - 800 1 V 1 V
3x0030 29 V Motor (Peak) 0-500 1 V 1 V
Table 7.5.4
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
12
HOLDING REGISTERS – Available Holding Registers are shown in the table below
Holding Registers: 32 (R/W)
0x03: Read
0x06: Write Single
0x10: Write Multiple
Register Address Function PM-motor AC-motor
Range Resolution Unit Range Resolution Unit
4x0001 0Setpoint/PrcSet 0-10000 0,01 %0-10000 0,01 %
4x0002 1Min. RPM 0 - ? 1RPM 0 - ? 0,01 Hz
4x0003 2Max. RPM 0 - ? 1RPM 0 - ? 0,01 Hz
4x0004 3UpRampTime 15 - 300 1Sec. 15 - 300 1Sec.
4x0005 4DownRampTime 15 - 300 1Sec. 15 - 300 1Sec.
4x0008 7Max I Out 0 - ? 1mA 1000-65000 1mA
4x0009 8I Out Alarm Limit n/a n/a n/a 1000-30000 1mA
4x0011 10 Switch Mode
0Auto 0Auto
1 4 kHz 1 4 kHz
2 8 kHz 2 8 kHz
4x0012 11 U minHz n/a n/a n/a 0 - ? 1 V
4x0013 12 Freq Umax n/a n/a n/a 0 - ? 0,01 Hz
4x0014 13 Auto SF Change 0 - 10000 0,01 %0 - 10000 0,01 %
4x0015 14 ExpSet n/a n/a n/a 0 -100 1n/a
4x0016 15 Drive Type 1000 - ? 1n/a 1 - 99 1n/a
4x0017 16 Modbus ID 1 - 247 1n/a 1 - 247 1n/a
4x0020 19 Number of retries -1 - 100 1n/a -1 - 100 1n/a
4x0022 21 CommTimeout 0 - 240 1Sec. 0 - 240 1Sec.
4x0023 22 CommRate
09600 bps 09600 bps
119200 bps 119200 bps
238400 bps 238400 bps
3115200 bps 3115200 bps
4x0024 23 Parity
0None n/a 0None n/a
1Odd n/a 1n/a n/a
2Even n/a 2n/a n/a
4x0025 24 Stop Bits
n/a INVALID n/a n/a INVALID n/a
1 1 n/a 1 1 n/a
2 2 n/a 2 2 n/a
4x0026 25 DigIn1 config
n/a Disabled n/a n/a Disabled n/a
1Start/Stop n/a 1n/a n/a
2AlarmReset n/a 2n/a n/a
3MB_IDs2 n/a 3n/a n/a
4Invert 10V n/a 4n/a n/a
5Rotation n/a 5n/a n/a
6Firemode n/a 6n/a n/a
7Motor Overheat n/a 7n/a n/a
4x0027 26 DigIn2 config
n/a Disabled n/a n/a Disabled n/a
1Start/Stop n/a 1n/a n/a
2AlarmReset n/a 2n/a n/a
3MB_IDs2 n/a 3n/a n/a
4Invert 10V n/a 4n/a n/a
5Rotation n/a 5n/a n/a
6Firemode n/a 6n/a n/a
7Motor Overheat n/a 7n/a n/a
4x0028 27 DigOut config
0Disabled n/a n/a Disabled n/a
1TachoOut n/a 1n/a n/a
2Running n/a 2n/a n/a
3AlarmOut n/a 3n/a n/a
4x0029 28 MotorConfigVar 0 - 65535 1n/a 0-65535 1n/a
4x0030 29 FanConfigVar 0 - 65535 1n/a 0-65535 1n/a
Table 7.5.5
“?” = Value depends on hardware variant
“n/a” = not applicable
Continued on next page.
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
13
Register Address Function PM-motor AC-motor
Range Resolution Unit Range Resolution Unit
4x0031 30 DigIn3 config (IOM)
0Disabled n/a 0Disabled n/a
1Start/Stop n/a 1Start/Stop n/a
2AlarmReset n/a 2AlarmReset n/a
3Disabled n/a 3Disabled n/a
4Invert 10V n/a 4Invert 10V n/a
5Rotation n/a 5Rotation n/a
6Firemode n/a 6Firemode n/a
4x0032 31 DigIn4 config (IOM)
0Disabled n/a 0Disabled n/a
1Start/Stop n/a 1Start/Stop n/a
2AlarmReset n/a 2AlarmReset n/a
3Disabled n/a 3Disabled n/a
4Invert 10V n/a 4Invert 10V n/a
5Rotation n/a 5Rotation n/a
6Firemode n/a 6Firemode n/a
4x0033 32 Relay 1 config (IOM)
0Disabled n/a 0Disabled n/a
1n/a n/a 1n/a n/a
2Running start n/a 2Running start n/a
3Alarm out n/a 3Alarm out n/a
4Running spin n/a 4Running spin n/a
4x0034 33 Relay 2 config (IOM)
0Disabled n/a 0Disabled n/a
1n/a n/a 1n/a n/a
2Running start n/a 2Running start n/a
3Alarm out n/a 3Alarm out n/a
4Running spin n/a 4Running spin n/a
4x0035 34 AnalogOut1 config (IOM)
0Disabled n/a 0Disabled n/a
1ActSpeed n/a 1ActSpeed n/a
2TBD n/a 2TBD n/a
4x0036 35 Thermistor config (IOM)
0Disabled n/a 0Disabled n/a
1Motor Overheat PTC n/a 1Motor Overheat PTC n/a
2TBD n/a 2TBD n/a
4x0037 36 AnalogIn2 config (IOM)
0Disabled n/a 0Disabled n/a
1TBD n/a 1TBD n/a
2TBD n/a 2TBD n/a
4x0038 37 Thermistor treshold 1-65000 1ohm 1-65000 1ohm
4x0039 38 Max Windmilling Time 0-65000 1Sec 0-65000 1Sec
Table 7.5.5
“?” = Value depends on hardware variant
“n/a” = not applicable
8. MAINTENANCE
Frequency converter is maintenance free under normal operat-
ing conditions and load profiles.
The cooling fins must be kept free of dust, dirt and other foreign
matter so that air can pass freely over them. Deposits of dust,
dirt or other foreign matter on and between the cooling fins will
prevent cooling of the frequency converter and thus impair per-
formance.
The cooling fins may become very hot. (Max. +95°C under nor-
mal operating conditions)
Frequency converter cannot be repaired on site. Never attempt
to repair a defective unit. Contact your supplier to obtain a re-
placement.
Additional technical data are available on request from Fläkt-
Group.
HOLDING REGISTERS, CONT.
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
14
9. TROUBLESHOOTING
Before opening the frequency converter, the mains voltage
must be disconnected for at least 3 minutes to ensure there is
no risk of dangerous residual currents in electronic circuits or
capacitors.
If natural draught through the duct system cause the fan to
rotate even though it has received no operating signal, there is
a risk that the motor will induce voltage on the frequency con-
verter motor terminals, making them dangerous to touch.
TROUBLESHOOTING WHEN FREQUENCY CONVERTER IS CONTROLLED VIA A/D SIGNALS:
Symptom Cause Action
Motor inoperative
Lacking supply voltage
Check voltage 400V in frequency controller terminals L1,
L2 and L3
Check whether short-circuit protection has been activated.
Check that the voltage supply to frequency converter has
not been cut off by other components.
Poor electrical connections Check electrical connections
Wrong motor for frequency converter setup Check that the correct motor settings have been read into
and stored in the frequency converter setup.
Lacking operating signal A/D control: Short-circuit frequency controller terminals
Din 1 (START) and GND
No 0-10 V DC control signal
Check that 0-10 VDC signal is connected correctly to fre-
quency controller terminals 0-10Vin and GND
With potentiometer control : Check that the potentiometer
is connected correctly to frequency controller terminals
+10V dc, 0-10V In and GND.
Active alarm Read out active alarms and remedy their cause.
The motor has been stopped by the built-in
motor protector 5 times because of overload
or other alarm.
Reset the alarm by short-circuiting frequency controller
terminals DIn 2 and GND.
The alarm can also be reset by disconnecting the power
supply to the frequency controller and reconnecting it after
approx. 60 seconds
Defective frequency controller
Replace frequency controller. Never attempt to repair a
defective frequency controller. Contact your supplier for
replacement/repair.
Defective motor Replace motor
Motor running in wrong direction Wrong phase sequence in motor cable Interchange two phase wires on the motor or the frequen-
cy converter terminal strip.
Motor is noisier than acceptable Switching frequency too low
Increase switching frequency
0 = Auto (factory setting), 1 = Low = 4 kHz, 2 = High = 8 kHz
Raising the switching frequency increases energy losses
in frequency controller. Switching frequency can be
changed using the Hand Terminal.
Frequency controller cuts out due
to an alarm.
At least one alarm active
Use Hand Terminal to view the alarm and determine which
alarm has stopped the controller/motor.
Reset the alarm by short-circuiting frequency controller
terminals DIn 2 and GND.
The alarm can also be reset by disconnecting the power
supply to the frequency controller and reconnecting it after
approx. 60 seconds.
The alarm is re-activated after reset
Use Hand Terminal or PC Tool to view the alarm and de-
termine which alarm has stopped the controller/motor.
Remedy the cause of repeated alarm activation.
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
15
Symptom Cause Action
Motor inoperative
Lacking supply voltage
Check voltage 400V in frequency controller terminals L1,
L2 and L3
Check whether short-circuit protection has been activated.
Check that the voltage supply to frequency converter has
not been cut off by other components.
Poor electrical connections Check electrical connections
Wrong motor for frequency converter setup Check that the correct motor settings have been read into
and stored in the frequency converter setup.
Lacking operating signal
Check that the frequency converter can receive
an operating signal.
Coil Stat Bits Register 0X0001: Motor start/stop (1=On).
Lacking % control signal from Modbus con-
troller
Check the Modbus control signal at Modbus address:
Holding registers; Register 3X0001: PrcSet 0-10000 (0-
100%).
The motor has been stopped by the built-in
motor protector 5 times because of over-
loading
Reset alarm: Coil Stat Bits Register 0X0002: Reset (1 pulse
= Reset). The alarm can also be reset by disconnecting the
power supply to the frequency converter and reconnecting
it after approx. 60 seconds.
Defective frequency controller
Replace frequency controller. Never attempt to repair a
defective frequency controller. Contact your supplier for
replacement/repair.
Defective motor Replace motor
Motor running in wrong direction Wrong phase sequence in motor cable Interchange two phase wires on the motor or the frequen-
cy converter terminal strip.
Motor is noisier than acceptable Switching frequency too low
Increase switching frequency.
0 = Auto
1 = Low = 4 kHz
2 = High = 8 kHz
Increasing switching frequency increases losses within
frequency converter, thus reducing efficiency.
Frequency converter switching frequency can be changed
via Hand Terminal or via Modbus.
Frequency controller cuts out due
to an alarm
At least one alarm active
Use Hand Terminal to view the alarm and determine which
alarm has stopped the controller/motor.
Reset the alarm by short-circuiting frequency controller
terminals DIn 2 and GND.
The alarm can also be reset by disconnecting the power
supply to the frequency controller and reconnecting it after
approx. 60 seconds.
The alarm is re-activated after reset
Read out the alarm via Modbus registers and determine
which alarm has stopped the controller/motor.
Remedy the cause of repeated alarm activation.
TROUBLESHOOTING WHEN SPEED IS CONTROLLED BY MODBUS
10. DISPOSAL
Frequency converter contains electronic com-
ponents and must not be disposed of together
with household waste.
Frequency converter must be disposed of in
accordance with applicable local rules and
regulations.
Frequency converter meets the requirements
on marking of electronic waste contained in the European
WEEE Directive 2012/19/EU.
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
16
11. TECHNICAL SPECIFICATION
SPEED CONTROLLER
Power size kW 1.5 2.4 3.0 4.0 5.5 6.5 7.5
Efficiency %> 96.5
POWER SUPPLY
Voltage VAC 3 x 400 VAC 50/60 Hz +/-10%
Supply current at max. load A3.1 5.0 6.3 8.4 11.5 13.6 15.7
Power factor at max. load cos-phi φ> 0.9
MOTOR OUTPUT
Max output voltage Vrms 3 x 0 - 360 VAC
Max output current Arms 4.5 6.4 8.0 11.7 16 19 19
PROTECTION
Max. fuse A16
Motor output Short-circuit protected between phases
Motor Protected by current limit
Impulse protection Protected against transient voltages by VDR
Over-voltage protection Yes. 565 V
Overload protection Current and temperature overload protection
ENVIROMENT
Operating temperature °C -40°C to +50°C
Starting temperature °C -40°C to +50°C
Storage temperature °C -40°C to +70°C
Dimensions mm 185 x 250 x 100 mm 220 x 295 x 110 mm
Protection rating IP 65 54
Enclosure material Aluminium
Front cover Plastic
Weight kG 3.0 3.9
Humidity % rh 10-95% rh. non-condensing
Vibration Stationary: IEC 60721-3-3 Class 3M6 2.0 Kg
Non-stationary: IEC 60721-3-3 Class 3M6 25.0 Kg
Air flow / cooling > 3 m/s | full power | mounted inside air stream | no need for on-board fan
< 3 m/s | derated output power| typically mounted outside direct air stream | on-board fan can be added
INTERFACES
Digital communication MODBUS RTU RS485 (baud rate: 9.6. 19.2. 38.4. 115.2 Kbaud)
Digital communication Slave 2 x RJ12 & 2 x spring terminals
Digital communication Master 1 x RJ12 connection
Analogue In1 0-10 VDC, 100% @ 9.5 V DC +/-2%
Analogue Out1 +10 VDC
Digital In1 Start/stop with internal pull-up
Digital In2 Alarm res
Digital Out1 Alarm signal
Relay 1 Alarm signal
Relay 2 Running indication
Green LED Lit: Power connected | Flashing: Active communication
Red LED Flashing: Alarm but still running | Constantly lit: Critical alarm - stop motor
Built-on Speed controller - Installation and Operation
FläktGroup DC-9757GB_180424_R0 Specifications are subject to alteration without notice
17
FEATURES
Technology Sinusoidal back-EMF signal controlled via FOC (Field Oriented Control)
Flying start Yes. typically below 30% of max. speed depending on load and fan weight
Ramp-up time sec. 15-300
Ramp-down time sec. 15-300
Alarm Yes
Alarm reset Via digital input. Modbus or powering down for more than 60 seconds
Fan stop sec. The braking system stops the fan as quickly as possible.
Braking time will depend on the inertia of the fan.
Service data log Operating hours, alarms, loads, software version, max. temp.,
max. motor voltage, max. motor current, max. ripple voltage, max. ripple current
Software updating Yes, via serial interface
Motor parameters Preprogrammed by FläktGroup or on-site configuration
Fire mode Nominal power for 1 hour at 70°C ambient temperature
Field weakening Yes
Short-circuit protection Yes
EMC filter Integrated
APPROVALS
EMC EMC EN 61800-3 (C1 and C2)
Safety EN 61800-5-1
Product standard EN 61800 Part 2
RoHS Directive Yes
Product approvals CE
Data are valid at nominal supply votage, temperature +25° C and sufficient air flow.
FG_DC_9757GB_Built-on Speed controller_IN-OM_20180424_R0 © Copyright 2018 FläktGroup
WWW.FLAKTGROUP.FI GMPM/GMEB 9757
» Learn more on www.flaktgroup.com
or contact one of our offices
A HISTORY OF INNOVATION
AND RELIABILITY
With more than a century of accumulated industry experience, FläktGroup is in a
unique position to deliver energy efficient components and solutions for integrated
performance, reliability and quality. With modern manufacturing technologies, pre-
cise deliveries and technical support, FläktGroup is your partner – fulfilling and
surpassing industry standards and certifications.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

FläktGroup CentriFlow 3D GMPM_GMEB Built-on drive Operating instructions

Type
Operating instructions

FläktGroup CentriFlow 3D GMPM_GMEB Built-on drive is a device that can be used to control the speed of a permanent magnet synchronous motor or an asynchronous motor. It can be controlled with a 0-10 V DC signal, potentiometer, Modbus RTU or hand terminal. The hand terminal is not automatically included in the delivery but can be ordered as an accessory.

The built-on drive has an EMC filter and is equipped with an indication relays for alarm and running.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI