FläktGroup Row-DENCO controller Owner's manual

Category
Split-system air conditioners
Type
Owner's manual
Controller for Row-DENCO®
OPERATION MANUAL
Table of Contents Controller for Row-DENCO
2FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
1 Safety and User Information....................................................... 4
1.1 Availability of the operation manual .......................................................... 4
1.2 Used symbols ........................................................................................... 4
1.3 Labelling of safety information ................................................................. 5
1.4 Used safety symbols................................................................................. 6
1.5 Safety-conscious work procedures ........................................................... 6
1.6 Proper use ................................................................................................ 7
1.7 Modifications and changes ....................................................................... 7
1.8 Spare parts ............................................................................................... 7
1.9 Disposal .................................................................................................... 8
1.10 Personnel selection and qualification........................................................ 8
2 General Characteristics............................................................... 9
2.1 User interface............................................................................................ 9
3 Main Screen................................................................................ 11
4 Status Screen............................................................................. 15
5 Parameter Setting Screens ....................................................... 17
5.1 Password management ......................................................................... 18
5.2 Menu items ............................................................................................. 18
5.3 Group A screens ..................................................................................... 19
5.4 Group B screens ..................................................................................... 21
5.5 Group C screens..................................................................................... 22
5.6 Group D screens..................................................................................... 23
5.7 Group E screens ..................................................................................... 24
5.8 Group F screens ..................................................................................... 25
6 Diagrams..................................................................................... 32
6.1 Control diagrams..................................................................................... 32
6.2 Alarm threshold diagram......................................................................... 33
6.3 Ambient humidity control diagram........................................................... 33
7 Operating in Cooling Mode....................................................... 34
7.1 Cooling on chilled water units ................................................................. 34
7.2 Cooling on chilled water units with two interlaced coils .......................... 34
7.3 Cooling on direct expansion units ........................................................... 35
8 Additional Functions ................................................................. 38
8.1 Minimum outlet temperature limit function .............................................. 38
8.2 Dehumidification function........................................................................ 38
8.3 Power transducer function ..................................................................... 39
9 Alarm Event................................................................................ 40
9.1 Serious/minor alarm................................................................................ 40
9.2 Reset alarm status .................................................................................. 42
10 LAN.............................................................................................. 45
10.1 LAN local network management ............................................................. 45
Controller for Row-DENCO Table of Contents
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 3
10.2 LAN network functions............................................................................. 48
10.3 Configuring the software for unit recognition and management .............. 49
11 Connection to the remote terminal from the board................ 50
11.1 Electrical connections ............................................................................. 51
11.2 Maximum distance between the terminal and the board ......................... 51
11.3 Displaying the network from the terminal................................................. 51
12 Serial Boards and Supervisory System................................... 52
13 Alarm Event................................................................................ 55
PROTECTION NOTICES
The reproduction, distribution and utilization of this document as well as the communication of its contents
to others without express authorization is prohibited. Offenders will be held liable for the payment of dama-
ges. All rights reserved in the event of the grant of a patent, utility model or design.
Safety and User Information Controller for Row-DENCO
4FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
1 Safety and User Information
This is an original operation manual verified by the manufacturer.
FläktGroup Row-DENCO units are designed in accordance with state-of-the-art tech-
nological and engineering standards as well as in conformity with the recognized safety
regulations.
Use the FläktGroup unit in a technically sound condition for the intended purpose
observing the current operation manual, taking safety aspects and potential hazards
into account.
It is important to appreciate that failure to follow the instructions in this manual may
result in danger to health and safety, material-only damage and incorrect unit opera-
tion. Have all faults repaired by an authorized specialist without delay!
1.1 Availability of the operation manual
This operation manual contains important information regarding safe and correct ope-
ration of the unit.
This manual must always be available at the site where unit is operating. Every person
working on the equipment must read this manual fully before commencing the work
and take note of all relevant information while performing a task.
The operation manual is intended to be used by fitting and installation companies, buil-
ding services engineers, technical personnel or trained persons as well as electrical
and refrigeration engineering specialists.
1.2 Used symbols
The following symbols are used to highlight particular text sections in this operation
manual:
This symbol is used to indicate normal lists.
This symbol indicates instructions to follow.
The result of an action is indicated with this symbol.
ATTENTION
Risk of damage to the unit!
In case of alarms and faults, always make sure that the cause of the fault is iden-
tified. In particular, multiple resets of an alarms without first rectifying the cause
can damage the unit and invalidate the warranty.
Notice!
Additional details on using the unit are specified here.
Recycling!
This symbol is used to highlight instructions for the proper recycling of packaging
material and assembly groups no longer in use (separated according to recyclable
materials).
Controller for Row-DENCO Safety and User Information
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 5
1.3 Labelling of safety information
To designate the safety instructions the following symbols and notices are provided in
appropriate places throughout this document:
1.3.1 DANGER – Death/serious irreversible injury
Indicates an extremely hazardous situation which will result in death or serious irre-
versible injury, if the safety instruction is not followed.
Example:
1.3.2 WARNING – Death/serious injury
Indicates a hazardous situation which can result in death or serious irreversible injury,
if the safety instruction is not followed.
Example:
1.3.3 CAUTION – Minor or moderate injury
Indicates a hazardous situation which can result in minor or moderate injury, if the
safety instruction is not followed.
Example:
Electrocution through hazardous voltage will lead to death or serious injury.
Disconnect the unit from the power supply and ensure the power cannot be
switched back on.
Ensure the unit is voltage-free and isolated, earth and short circuit the unit, cover
or shield off neighboring live components.
High concentration of refrigerants in the air can result in death or serious in-
jury!
High concentration of refrigerants in the air may have an anaesthetic effect and
cause unconsciousness. Prolonged exposure may cause irregular heartbeat and
sudden death. Very high concentration of refrigerant may cause suffocation by
reduced oxygen content in the surrounding air.
You should therefore only work in an adequately ventilated environment, and
exercise due care and attention when carrying out the work.
Wear protective clothing and, if necessary, an autonomous breathing apparatus.
Sharp edges can cause injuries!
Observe precaution when cleaning due to risk of cuts on thin and sharp edges.
Wear protective gloves.
Safety and User Information Controller for Row-DENCO
6FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
1.3.4 ATTENTION – Environmental or material damage
Indicates actions that can result in equipment or property-damage only accidents.
Examples:
1.4 Used safety symbols
1.5 Safety-conscious work procedures
Observe the following instructions when carrying out installation, adjustment or repair
jobs:
Wear suitable protective clothing during work, such as protective footwear, gloves,
safety goggles, etc..
When working on Row-DENCO equipment you may need to wear suitable Personal
Protective Equipment (P.P.E.) to comply with EN 378-3. Only qualified staff with a
history of assessing and minimising risk should be allowed to work on the equipment.
As a minimum we would suggest suitable safety footwear, suitable gloves, suitable eye
ATTENTION
ATTENTION
Risk of environmental damage!
Heavily contaminated filters can have a negative impact on production processes.
Depending on the filtered-out materials, contaminated filters are therefore classi-
fied as hazardous waste and must be properly disposed of according to the pre-
vailing guidelines and laws.
ATTENTION
Risk of damage to the unit!
If dampers are abruptly shut during unit operation, the unit can be damaged
beyond repair as a result of negative pressure or overpressure.
Electrical hazard
Toxic substances
Static discharge
Sharp cutting edges
Environmental damage
Damage to the unit
ATTENTION
Danger of damage due to static discharge!
This symbol warns about risk of static discharge-related damage to the unit.
Controller for Row-DENCO Safety and User Information
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 7
protection and suitable overalls. More P.P.E. may be required depending on your per-
sonal risk assessment.
When working within range of mains voltage:
Please comply with the installation and shipping instructions for FläktGroup units.
Observe the pre-commissioning check points.
Always make sure that the FläktGroup unit is accessible only to authorized and
trained technical personnel. If necessary, use appropriate equipment to keep
unauthorized persons away from the unit.
Have all leaks eliminated by the FläktGroup Service or a specialist refrigeration
company immediately.
Pay attention to the safety labels fitted to the unit.
1.6 Proper use
FläktGroup Units of Row-DENCO series are designed as indoor units for connection
with an associated heat rejection system (condensing unit or chiller) and are design to
perform cooling, humidification and filtering of air at atmospheric temperatures.
Unless otherwise stated the equipment will not be suitable for use in a corrosive atmo-
spheres such as, areas near large volumes of salt water, for example.
Proper use also comprises adherence to the operation manual for the controller and
inspection and maintenance requirements stipulated by FläktGroup.
Improper use Any use other than that described above is considered improper. The manufacturer/
supplier is not liable for damage arising from improper use. The user alone bears the
risk.
1.7 Modifications and changes
Changes, alterations or modifications of the unit are not allowed. Tampering with the
unit or its misapplication will invalidate the CE conformity and void warranty.
If delivered units are disassembled by others on-site, the factory warranty is rendered
invalid. In this case professional services by FläktGroup should be arranged in
advance.
1.8 Spare parts
Only original FläktGroup spare parts are allowed, since FläktGroup is not liable if third-
party spare parts are used.
Electrocution through hazardous voltage will lead to death or serious injury.
Disconnect the unit from the power supply and ensure the power cannot be
switched back on.
Ensure the unit is voltage-free and isolated, earth and short circuit the unit, cover
or shield off neighboring live components.
Personal injury and damage to the unit!
It is not allowed to operate FläktGroup units of Row-DENCO series:
in explosion risk areas
in areas with strong electromagnetic fields, (electromagnetic immunity as of
EMC Directive; refer to the Declaration of Conformity in the unit documentation)
in environment with high levels of air contamination
in environments with corrosive and/or aggressive air
Safety and User Information Controller for Row-DENCO
8FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
1.9 Disposal
Equipment, operating supply materials, components and filters must be disposed of
according to the material type in a safe and environmentally friendly manner.
1.10 Personnel selection and qualification
Ensure that every person working on the unit has read and understood entire operation
manual. Please read this document fully before commencing any work, and not while
performing a task.
All jobs must only be carried out by qualified licensed staff or other individuals with
proper professional training and experience in the following areas:
occupational health and safety regulations
accident prevention regulations
directives and recognized codes of practice
All jobs with the refrigeration circuit shall be performed only by certified and licensed
staff in accordance with the valid EG Regulation 842/2006 Article 5, EG Regulation
303/2008 Article 4 and 5 as well as "Ordinance on climate protection against changes
caused by release of certain fluorinated greenhouse gases" Article 5, passed by the
German parliament.
All skilled staff must be able to assess the entrusted work and must be able to recog-
nize and avoid all associated dangers.
Controller for Row-DENCO General Characteristics
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 9
2 General Characteristics
2.1 User interface
The user interface comprises:
132x64 pixel backlit LCD display
backlit buttons
The microprocessor board and user interface are connected by a 4-wire telephone
cable via jack J7.
The terminal is supplied directly from the control board via the above-mentioned cable.
Like the control board, this is already configured for operation in a LAN (local network)
so as to share the remote terminal.
Fig. 2-1: User interface
2.1.1 General function of the buttons
ALARM button:
reset the alarm (if held for 5 seconds)
PRG button:
enter the parameter setting menu
ESC button:
exit the screens
UP button:
scroll and/or change screen
change values
scroll inside the menus
ENTER button:
confirm changes
access setting areas
DOWN button:
scroll and/or change screen
modify the values
scroll inside the menus
General Characteristics Controller for Row-DENCO
10 FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
2.1.2 LED signals
Yellow LED
on the PRG button the yellow LED on the PRG button is always on when the unit is operating (fans acti-
ve)
Red LED
on the ALARM button the red LED on the ALARM button flashes in the event of an alarm or maintenance
signal
The green LEDs
include: the LEDs on the ESC, UP, ENTER and DOWN buttons
display backlighting
The green LEDs
come on when: the unit is switched on
a button is pressed
there is an alarm or maintenance signal
The green LEDs
go off: when an alarm event has ceased
after 180 seconds (3 minutes) of complete inactivity on the user terminal keypad
2.1.3 Adjusting display contrast
PRG + ALARM + UP
increase contrast
PRG + ALARM + DOWN
decrease contrast
2.1.4 ON/OFF from keypad
ENTER + PASSWORD – when OFF
switches the unit on
ENTER + PASSWORD – when ON
switches the unit off
++
++
+ PASSWORD
+ PASSWORD
Controller for Row-DENCO Main Screen
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 11
3 Main Screen
3.0.1 Password management
All the parameter setting screens can be accessed after entering a numerical
password. Three password levels are available:
USER password for the user
MAINTENANCE password for use by maintenance technicians/service centres
MANUFACTURER pass-
word only available to the manufacturer's personnel (not disclosed externally)
How to enter the password:
Pressing the PRG button once displays the screen for entering the user/
maintenance password
Pressing the PRG button for 5 seconds displays the screen for entering the
manufacturer password
3.0.2 General layout of the main screen
Below is the layout of the main screen, showing the numbered areas this is divided into:
Area 1 This area shows a schematic representation of the controlled unit
Area 2 General unit status
unit off
unit on in normal operation
Main Screen Controller for Row-DENCO
12 FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
Area 3 Detailed unit status
active alarm
maintenance signal
manual controls active
unit on/off from terminal
unit on/off from remote contact
unit on/off from supervisory system
reserve unit off in pLAN
unit on in pLAN
reserve unit on in pLAN due to: high/low temperature/humidity
compressor called but shutdown by high pressure function at start up
compressor called but shutdown by unbalanced pressure function at start up
Area 4 This area features an icon that, in the event of an alarm or maintenance signal, indicates either the type of alarm
or device that requires maintenance
With active alarm signal
Pressure
difference DRX
Control envelope shape inconsistent inconsistent DRX
Envelop compressore
inverter DRX
Compressor
inverter DRX
Fire/smoke
alarm
Water
in the condensate
collection
pan
Risk of
condensate
formation DRC
Fan 4 disconnected
Fan 3 disconnected
Fan 2 disconnected
Fan 1 disconnected
Flow alarm DRC/DRX
High compressor discharge temperature alarm DRX
High compressor discharge temperature DRX
High pressure DRX
Frost protection alarm DRX
Low pressure DRX
Electronic thermostatic
valve DRX
Electric heater thermal
protector DRC/DRX
No power DRC
Dirty filters DRC/DRX
Humidifier generic alarm DRC/DRX
Humidifier water drain alarm DRC/DRX
Humidifier cylinder lifetime alarm DRC/DRX
Humidifier offline alarm DRC/DRX
Humidifier high current alarm DRC/DRX
Controller for Row-DENCO Main Screen
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 13
Area 4 With active alarm signal – continued
Humidifier no water
alarm DRC/DRX
Humidifier low current
alarm DRC/DRX
EEPROM
fault
Door
open
Compressor discharge temperature probe DRX
Circuit
2 water temperature
probe
fault DRC
Circuit
1 water temperature
probe
fault DRC
Outlet
air
temperature probe
4
Outlet
air
temperature probe
3
Outlet
air
temperature probe
2
Outlet
air
temperature probe
1
Intake
air
temperature probe
4
Intake
air
temperature probe
3
Intake
air
temperature probe
2
Intake
air
temperature probe
1
Room temperature
probe
Room humidity probe
fault
pLAN
alarm DRC/DRX
High outlet air temperature
High intake air temperature
High
room
temperature
Low
room
temperature
High
room
humidity
Low
room
humidity
High water
temperature, circuit
2DRC
High water
temperature, circuit
1DRC
Power transducer
alarm
Expansion
alarm
Incorrect password
(5 attempts)
If more than one alarm is active, the area displays the most serious alarm. The seriousness of the alarms displayed
in this area reflects the order these are listed in the table, from the most serious to the least serious. The seriousness
of alarms is evaluated based on the consequences these have on operation of the airconditioning unit.
Area 4 With maintenance signal
Inverter-driven compressor hour threshold
Heater 1 and 2 hour threshold
Humidifier cylinder hour threshold
Fan 5 hour threshold
Fan 4 hour threshold
Fan 3 hour threshold
Fan 2 hour threshold
Fan 1 hour threshold
Area 5 This area displays icons corresponding to the currently active devices
Circuit 1 water valve open
Circuit 2 water valve open
Compressor operating level
Main Screen Controller for Row-DENCO
14 FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
Area 6 This area displays icons corresponding to the currently active devices
Circuit 2 water valve open (freecooling unit)
Area 7 This area displays icons corresponding to the currently active devices
Humidifier active
Dehumidification active
Area 8 This area displays icons corresponding to the currently active devices
Heaters 1 and/or 2 active
Area 9 This area shows the unit LAN address
Area 10 This area indicates unit on/off from user terminal
press ENTER to switch the unit off
press ENTER to switch the unit on
Area 11 This area shows the time and dates
Area 12 This area displays the maximum outlet temperature read by the 4 probes or the room temperature
(if the corresponding probe is fitted)
Area 13 This area displays the relative humidity of the intake air
(if the corresponding probe is fitted)
Controller for Row-DENCO Status Screen
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 15
4 Status Screen
3
4
5
2
1
6
7
8
9
10
11
USER password
MAINTENANCE password
MAINTENANCE password
MAINTENANCE password
Change set point
Change maintenance threshold
Reset operating hours
Reset number of starts
MAINTENANCE password
Delete alarm log
Display alarm log
Software INFO
Access log
Number of starts
Operating hours
Read electrical parameters
Set-points
Humidifier status
LAN STATUS
Water valve status
Status of electronic valve
PROBE READINGS
MAIN SCREEN
TO MODIFY
TO MODIFY
TO RESET
TO DISPLAY
TO MODIFY
NB: the screens described above only
provide information via graphic icons
Status Screen Controller for Row-DENCO
16 FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
Starting from the main screen, pressing UP/DOWN accesses the following status screens, in sequence:
1FAN STATUS AND PROBE READINGS: A screen displaying the temperature values read by the
probes (outlet and intake air temperature probe) and percentage of fan operation 1PROBE READINGS
2WATER VALVE STATUS/OPTIONAL PROBE READINGS: A screen displaying the
temperature values read by the probes, chilled water temperature probe and the opening 2Water valve status
Optional Probe readings
of the chilled water modulating valves, as a percentage
3Local Area Network (LAN) status: A screen displaying the status of all the units connected to the
LAN (local network) 3LAN STATUS
4HUMIDIFIER STATUS: A screen displaying the status of the humidifier, with all
the technical operating values 4Humidifier status
5Electronic Valve Status: A screens displaying the data corresponding
to the operation of the electronic thermostatic valve 5Electronic Valve Status
6SET POINTS: A screen displaying the active control set points; from this screen,
pressing PRG and entering the USER password, a further screen can be accessed 6Set Points
for modifying the set point and proportional band
7OPERATING HOURS: A screen displaying the total operating hours of the components on the unit;
from this screen, following the instructions shown on the display 7Operating hours
and after entering the MAINTENANCE password, the operating hours for each component can be
reset (set to zero) or different thresholds can be set for the maintenance alarm
8NUMBER OF STARTS: A screen displaying the total number of starts for the
components on the unit; from this screen, following the instructions shown on the display 8Number of starts
and after entering the MAINTENANCE password, the number of starts for
each component can be reset
9ELECTRICAL PARAMETERS: A screen displaying the electrical parameters
(for units with optional power transducer) 9Electrical parameters
10 ACCESS LOG: A screen to access and display the alarm log. On this screen, the alarm/events log
can be reset, by following the instructions shown on the display after entering 10 Access log
the MAINTENANCE password
11 SOFTWARE INFO: A screen displaying information on the software installed 11 Software INFO
Controller for Row-DENCO Parameter Setting Screens
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 17
5 Parameter Setting Screens
Password
TEST/
Configure type of unit
Presence of remote ON/OFF sensors
MANUALS
TEST
digital input simulators
Temperature and
ADVANCED
SETUP
password (*)
FREE
COOLING
PRG
MAIN SCREEN
CLOCK SETTING
(*) the screens visible with the USER password
are shown in bold.
To display all these screens, the MAINTENANCE
password needs to be entered.
SETUP
SET POINT
SETUP
SENSOR
SETUP
ALARMS SERIOUS
ALARM
RESET ALARMS OUTPUT A/B
SERIAL SETUP LAN SETUP
DUAL
COOLING
MANUALS
TEST
digital output ramp
Enable fans
Setup evaporator fan + “Economy” mode
DEFAULT
SETUP
SETUP
Setup fan modulation
setup fans
door open alarm
setup valve control
ADAPTIVE SETPOINT
DEW POINT control
AIR FLOW-RATE MODULATION
CONDENSER MANAGEMENT
HUMIDIFIER CONFIGURATION
CONDENSER CONTROL VALVE
MANUFACTURER password
FROST
Parameter Setting Screens Controller for Row-DENCO
18 FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
5.1 Password management
Starting from the main screen, pressing the PRG button and entering the correct
password accesses a menu used to set all the other parameters that are not available
on the status screens, as described in the previous paragraph.
Three passwords can be entered:
USER password: allows access to parameters considered useful and easy to understand for the user
MAINTENANCE password: allows access to all the fundamental configuration parameters, which includes user
parameters and the MAINTENANCE parameters.
MANUFACTURER password: allows access to all USER-MAINTENANCE-MANUFACTURER parameters and for
exclusive use by authorised FläktGroup personnel. If required, this password must be
requested, along with reasoning from Customer Technical Service, which will provide
all information if appropriate.
5.2 Menu items
The complete menu items are as follows:
5.2.1 A SETUP (alarms setting)
(USER password) This is used to set the address of the alarm digital outputs available on the controller.
(MAINTENANCE password) This is used to set the thresholds for alarms activated when exceeding a certain limit
(high and low room temperature, high and low relative humidity, high water tempera-
ture).
(MANUFACTURER password) To access to set the delays for some alarms, how serious the alarms are, the type of
reset (automatic or manual) for some alarms, and the addresses of the alarm digital
outputs available on the controller.
5.2.2 B SETUP (serial)
(MAINTENANCE password) To access to configure the serial communication parameters to configure the Local
Area Network (LAN).
5.2.3 C SETUP (control settings)
(MAINTENANCE password) This is used to modify some critical parameters that are part of the control algorithm
installed inside the control system.
5.2.4 D SETUP (clock setup):
(USER password) This is used to set the current time and date.
5.2.5 E TEST/ (test/manual control)
(MAINTENANCE password) This menu is used to manually control all the devices on the unit, for a maximum of
30 minutes, disabling normal automatic control; moreover, the status of all the contacts
(inputs and outputs) that are managed by the control board can be checked.
Controller for Row-DENCO Parameter Setting Screens
FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications 19
5.2.6 F SETUP (unit configuration)
(MAINTENANCE password) Settings that involve the configuration of the devices, probes and sensors on the unit.
5.2.7 G SETUP
(MANUFACTURER password) Settings corresponding to the electronic expansion valve. This menu is only active on
direct expansion units.
5.2.8 H DEFAULT SETUP
(MANUFACTURER password) This is used to restore the default parameter values.
5.3 Group A screens
5.3.1 Screen A1-A2 “Temperature and humidity thresholds”
(MAINTENANCE password)
This screen is used to change the thresholds to alarms
activated when parameters exceed their limits (room
temperature, room humidity, water temperature).
5.3.2 Screen A3 “ALARM DELAY”
(MANUFACTURER password) This screen is used to change the alarm delays, in particular: the delay in signalling the
alarms when exceeding the room temperature and humidity limits.
5.3.3 Screen A4 “SERIOUS ALARM”
(MANUFACTURER password) This screen is used to set whether each alarm is SERIOUS or MINOR:
SERIOUS: stops the unit from functioning
MINOR: display only, normal cooling and functions resume
See the table in the paragraph „Alarm Event“ auf Seite 55.
IMPORTANT
Damage to the unit!
This operation deletes the entire buffer memory (including the alarm log!), then
installs the default values. The unit then needs to be reconfigured after having
upgraded the software on the board and after having installed the default parame-
ters.
Parameter Setting Screens Controller for Row-DENCO
20 FläktGroup DC-2014-0110-GB 2019-02/R3 • Subject to modifications
5.3.4 Screen A5 “RESET MODE”
(MANUFACTURER password) This screen is used to change the RESET MODE (automatic or manual) for certain
alarms.
5.3.5 Screen A6 “ALARM OUTPUT STATUS”
(USER password) This screen is used to change the status (at rest) of the alarm contacts available.
The control board features two relay outputs for alarm signals.
Accessing the alarm setting screens with the USER password, this item is used to con-
figure the alarm outputs available.
The following functions are available in these screens:
set the status of the output contacts when de-energised
set the alarm signal contact
Setting output contact status
This configuration screen is used to set the status of the output
contacts when de-energised.The options are:
Normally open
Normally closed
(in this case, power failures to the board can also be signal-
led)
Setting the signal contact
For each type of alarm available on the unit, the contact used to signal the alarm can
be configured. The options are:
Output "A"
Output "B"
No output
By default all alarms are signalled via output "A", which in this case represents a
general alarm output.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54