Preset Mode:
factory settings custom settings
1 = Lights ON 100% _____________________
2 = Lights OFF _____________________
3 = Lights ON 50% _____________________
4 = Lights ON 10% _____________________
ON/OFF = Switches Controlled Outlets
" Manual Mode:
1 = Lights ON (to previous level)
2 = Lights OFF
3 = Raise Light Level (hold/release)
4 = Lower Light Level (hold/release)
ON/OFF = Switches Controlled Outlets
Occupancy Sensor Time Delay:
PRIMARY
Outlets turn off and Lights either:
ordim
(all time delays are in minutes)
turn off
. 15 15
" 15
" 15
" 7.5
" 510
SECONDARY
Lights turn off
Lighting Outlets
(follows Primary delay)
. = factory default settings
" = alternate configuration
Occupancy Sensor Control
..Auto-Restore/Automatic Dim or Off
""Manual-On/Automatic Dim or Off
""Disabled (Manual-On and Off)
Automatic Dim or Off immediately follows the selected Primary
Time Delay after occupancy is last sensed.
Buttons 1 through 4 function differently
depending on mode.
Location:
Address:
Note: Mode selections and settings should be made
by the system’s manager only.
Functions and Settings
The Watt Stopper
®
, Inc. Santa Clara, CA 95050
1(800)879-8585 1(972)578-1699
70-0048-00 5/98
1
2
3
4
ON/OFF
Occupancy
Sensor
Overhead
Lighting
Control
Buttons
ON/OFF
Button for
Controlled
Outlets;
has ON
indicator
light
Transmitter
Remain at dimmed level
T
h
e
W
a
t
t
S
t
o
p
p
e
r
UNCO
NTROLLED
C
O
N
T
R
O
L
L
E
D
SENSOR
Isolé Power Strip
Lighting
Receiver
Lights
CS-200
Welcome
The Control Tower Transmitter and Isolé power strip have
been installed in your work area. These products give you
remote control of your overhead lighting and convenient
control of power strip outlets.
With the Tower, you can lower the light level to increase
the visibility of a computer screen, or raise the level to view
documents. You make the choice based on your needs.
An additional feature is the power strip ON/OFF control
button. Devices plugged into the outlets labeled controlled
can be conveniently turned on and off from the Tower. Use
this feature to control task lights, monitors, and radios.
The Control Tower Transmitter and power strip also save
energy for your company. When you leave your work area,
the Tower automatically turns off the devices plugged into
the controlledoutlets and signals the overhead lights to turn
off or go to an energy saving low light level. The reduction in
energy use in your work area will help your company and the
environment.
How it works
The transmitter at the top of the Tower sends an infrared
signal (similar to the remote control for your television) to
remote receivers when a control button is pushed. The top
of the Tower must have a clear line-of-sight to the receivers.
The occupancy sensor looks for the motion of infrared energy
(body heat) to sense occupancy. When motion is sensed, the
lights and controlled outlets will remain on.
When you leave the area for a selected period of time
(Primary Delay), the Tower will switch the controlled outlets
off and will either dim or turn off the lighting. If a Secondary
Delay has been selected, and the area remains vacant for
that additional amount of time, the Tower will turn off the
previously dimmed lighting. When you re-enter the area, the
lighting and outlets will be restored to the state they were in
before you left. If you left the lights or outlets off, they will
remain off until you turn them back on.
Important things to know
It is important that the occupancy sensor has a clear view of
your work area, and is directed away from unwanted coverage
areas such as open doors or entrances. The sensor housing
can be rotated to optimize coverage.
The operating mode, button functions, and time delays
are indicated on the back of this guide.
If set for Automatic-off/Manual-onlights or outlets must be
manually turned on at the Tower. They turn off in the same
automatic manner described above.
Control Tower Transmitter
User Reference Guide
Model#:
CS-200
Controlled outlets
Task lights
Desk lamps
Space heaters
Fans
Calculators
Computer monitors
Printers
1
Uncontrolled outlets
CPUs & Hard Drives
Fax machines
Modems
Printers
1
Printers can use controlled outlets only
if there is occupancy while printing.
WWAARRNNIINNGG:: NEVER plug devices that
must remain on throughout the day
into occupancy controlled outlets.
If Controlled Outlets are
Occupancy Controlled,
here are some suggestions:
General Installation
  • Page 1 1

Legrand CS-200 User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI