12 Check Our Web Site For FAQs: www.wattstopper.com
the CS-200 and receiver are confirmed, reset the addresses of both
according to your system documentation. If the lighting still does not
operate refer to documentation for the receiver and/or control module
and correct the installation.
Do not leave your CS-200 set to the Universal address, as it will then
operate all lighting receivers within transmitter range.
The lights don’t come on when I enter the area:
In Auto-Restore operation the CS-200 will restore lights and outlets to
the state they were in when the area was vacated. If you turned them
off manually, you will have to turn them back on manually.
If you did not turn the lights or outlets off manually and they don’t
come back on with occupancy, the CS-200 has been customized
for Manual-On operation.
The button functions are wrong:
Refer to pages 6 and 7 for a description of proper button functions.
If buttons are operating in the wrong mode, check the rotary mode
selection switch on the base of the CS-200. Select the appropriate
operating mode from the chart on page 6 and reset the switch.
If the buttons appear to be operating the wrong lights or are performing
unexpected functions, the addressing of either the CS-200 or one or
more of the receivers is incorrect. Refer to system documentation for
the correct addressing, and to pages 10 and 11 for instructions for
resetting the CS-200 address.
The controlled devices turn off while I am in the room:
Adjust the location of the Control Tower or rotate the sensor to better
view the motion in the area (see “Placement”). You may want to choose
an operating mode with a longer time delay.
The controlled devices turn on when someone walks by
my office or area:
Reorient or rotate the sensor so that even its peripheral view will not
sense occupants through an open door or in an adjacent area (see
“Placement”).
13
TROUBLESHOOTING
First, check installation:
Check that the CS-200 is properly connected to the Isolé power strip.
Toggle the large On/Off button. It should glow green when power is
supplied to the controlled outlets. If the indicator light glows, proceed
to the next section. If the light does not function, check the power strip.
It must be plugged into a properly wired and grounded outlet. If the
line and neutral are reversed, or there is no ground, no power will be
available to the CS-200 even though the uncontrolled outlets on the
strip may have power. Check the Reset(On)/Off switch and the
indicator light labeled "Wiring" on the power strip to test the building
outlet. If this green light is on, proceed. If not, correct the wiring or
choose an alternate outlet.
Controlled outlets don't respond, but On/Off indicator light
functions:
Check any local switches on the loads connected to the controlled
outlets. With the CS-200 On/Off button on (green light glowing),
activate the switches on the equipment.
CS-200 doesn't operate, but On/Off indicator light flashes
when pressed:
Check the rotary mode selection switch on the base of the CS-200.
It has been left in a setup mode (position A-F), not an operating mode
(positions 0–9). Press the On/Off button once to turn the indicator light off,
then refer to pages 6 and 7, select the appropriate operating mode
and reset the switch.
Overhead lighting does not respond to buttons 1–4, but
controlled outlets switch when On/Off is pressed:
Either the lighting control receiver is not properly installed, or the address
of the CS-200 and the lighting receiver do not match.
To verify that the lighting receiver is installed and operating properly,
reset the CS-200 to the Universal address for lighting control (Group 16,
Channel 10), then reset the rotary switch to the desired operating mode
and verify that buttons 1–4 control the lighting. If proper operation of
✆Call 1(800)879-8585 For Technical Support✆