" TROUBLESHOOTING
No on/off or dimming control:
If the transmitter’s LED does not flash when a control button is pressed, check the
battery.
1. Remove the back of the transmitter (see “Installation”).
2. Check that a 9VDC alkaline battery is installed correctly (see embossed diagram
in battery compartment).
If the transmitter’s LED does flash when a control button is pressed (indicating that the
battery is ok), the transmitter may be set to the wrong address for the control module.
1. Remove the back of the transmitter (see “Installation”). Note the transmitter’s
address setting, then reset its address to the universal address (Channel
10,11,12–Group 16).
2. Press control buttons to see if the lights respond correctly.
• If yes, the transmitter was not set to one of the control module’s addresses.
Reset the transmitter and/or control module to the addresses for desired opera-
tion (see “Setting Addresses”).
• If the lights still do not respond.
- Make sure that the power is on at the circuit breakers.
- Check all connections to the control module (see “Wiring”).
- Check connections of the low voltage, Black, Red and Blue wires, from the
power pack (see “Wiring”).
- Using all proper precautions, check all high voltage connections to the power
pack and lighting system (see “Wiring”).
No on/off control, but dimming works:
This can happen if a signal wire input from an occupancy sensor is connected to the
blue signal wire of the power pack instead of the +SW input of the control module.
• The only wire that should connect to the blue signal wire of the power pack is the
control module’s signal wire output to the power pack (see “Wiring”).
• All occupancy sensor or other signal wire inputs must be connected to the control
module’s signal wire input connection; this is different than the connection made for
occupancy sensors without the IRC-1000 system (see “Wiring”).
Transmitter controls not functioning properly:
Check that addresses are set correctly. Insure that channel settings are correctly set
to either: 1,2,3
, 4,5,6, 7,8,9, or 10,11,12, only.
The wrong lights are being controlled by transmitter:
• Insure that the transmitter being used is the correct one for the lights being con-
trolled.
• Address settings may have been changed or are incorrect. Reprogram the neces-
sary transmitters and control modules for the control desired (see “Setting
Addresses”).
Lights flicker at the low levels:
Some electronic dimming ballasts and tubes will flicker at low lighting levels. In this
case, the minimum light level should be increased to just above the point at which the
flickering stops (see “Setting Minimum Light Level”).