  • Hello! I am an AI chatbot trained to assist you with the ABB doGATE Installation Instructions Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
1473-1-8479 13.03.2014
Technical Reference Manual
doGATE Installation instruction
geb ic h
doGATE
DGT
-.-.K-AB
Technical Reference Manual
do
GATE - Installation instruction
Technical Reference Manual | 1473-1-8479
2
1 Technical data .......................................................................................................................................................... 3
1.1 Environmental characteristics ................................................................................................................. 3
1.2 Mechanical characteristics ...................................................................................................................... 3
1.3 Electrical characteristics .......................................................................................................................... 3
2 Connectors and button ............................................................................................................................................. 4
3 Networks .................................................................................................................................................................. 5
4 Installation ................................................................................................................................................................ 6
4.1 Using precautions ................................................................................................................................... 6
4.2 Power On Power Off ............................................................................................................................ 6
5 Scope of delivery doGATE box ................................................................................................................................ 7
6 Documentation ......................................................................................................................................................... 8
GATE - Installation instruction
Technical data
Technical Reference Manual | 1473-1-8479
3
1 Technical data
1.1 Environmental characteristics
Parameter
Value
Ambient temperature range
-2C to +70°C ambient temperature with ventilation
Storage temperature range
-40°C to +85°C
Relative humidity
10 to 95% at 40°C without condensation
Vibrations
1,5 g.ms from 5 to 500Hz
Resistance to shock
20G (11ms), Stop 60G
1.2 Mechanical characteristics
Parameter
Vakue
Material
Aluminum alloy
Mounting
On table, vertical or horizontal DIN rail via MDRC mounting kit
Weight
2 kg
Dimension
252 x 199 x 33 mm
1.3 Electrical characteristics
Parameter
Value
Input voltage
10 VDC to 28 VDC
Max. power
25 W
Processor
Intel Atom N270 1.6GHz
Memory
1 GB RAM
Hard drive*
250 GB
Compact Flash*
4 GB
* following chosen option
GATE - Installation instruction
Connectors and button
Technical Reference Manual | 1473-1-8479
4
2 Connectors and button
Caution
Risk of damaging the device !
If the power supply has been disconnected without stopping the device, risk of damaging the
device is possible. Before unplugging power supply, make sure doGATE is stopped.
You must
connect to LAN1
for doGate
configuration.
GATE - Installation instruction
Networks
Technical Reference Manual | 1473-1-8479
5
3 Networks
Port
Media
Supported protocols
COM1
RS232
ModBus, M-Bus
COM2
RS485
ModBus
COM3
RS485 ModBus
USB
Currently none
LAN1
Ethernet
BACnet, ModBus IP, KNX, EIA-852
LAN2
Ethernet
BACnet, ModBus IP, KNX, EIA-852
LAN 1 default address: 192.168.1.254
LAN 2 default address: 192.168.2.254
RJ45 connectors wiring COM1, COM2 und COM3:
Pin
COM1
COM2
COM3
1 DSR NET+ NET +
2
DCD
NET -
NET -
3
DTR
4
GND
5
RXD
6
TXD
7
CTS
8
RTS
Wiring of DB9 connector for RS232 or RS485.
Pin
RS232
RS485
1
DCD
NET -
2
RXD
3
TXD
4
DTR
5
GND
6
DSR
NET +
7
RTS
8
CTS
9
Note
Do not plug 120 Ohms bus terminator on RS485 port!
GATE - Installation instruction
Installation
Technical Reference Manual | 1473-1-8479
6
4 Installation
4.1 Using precautions
Caution
Risk of damaging the device !
The following using precautions must be observed. Otherwise risk of damaging the device is
possible:
Do not install in an overheated environment.
Do not install in a overly humid environment.
Do not cover doGATE in order to keep natural ventilation.
Make sure to check input voltage and polarity before plugging the power supply.
Connect and disconnect peripherals after powering off doGATE.
Before unplugging power supply, press Power button to stop doGATE.
IT IS RECOMMENDED TO USE AN UNINTERRUPTIBLE POWER SUPPLY IN ORDER
TO AVOID MALFUNCTION OR DEVICE DETERIORATION.
Guaranty does not apply if doGATE has been opened!
4.2 Power On Power Off
By pressing the button, you start or stop doGATE.
Light
Status
Light is off
doGATE has no power supply.
Light is red
doGATE has power supply and is stopped.
Light is green
doGATE is working.
Red: Off
Green: On
GATE - Installation instruction
Scope of delivery doGATE box
Technical Reference Manual | 1473-1-8479
7
5 Scope of delivery doGATE box
The doGATE box contains:
doGATE device (station)
RJ45-DB9 wire
Installation instruction
CD-ROM with documentations and software tools
Software key paper sheet
Note
Configuration of the station is realized with doMOOV Dashboard software (included on CD) that
must be installed on a Windows PC.
GATE - Installation instruction
Documentation
Technical Reference Manual | 1473-1-8479
8
6 Documentation
The configuration documentation is delivered on the included CD ROM. It is available in PDF format.
Technical Reference Manual
do
GATE - Installation instruction
A member of the ABB Group
Busch
-Jaeger Elektro GmbH
PO box
58505 Lüdenscheid
Freisenbergstraße 2
58513 Lüdenscheid
Germany
www.
BUSCH-JAEGER.com
Central sales
service:
Phone
: +49 (0) 2351 956-1600
Fax:
+49 (0) 2351 956-1700
Notice
We reserve the right to at all times make
technical changes as well as changes to the
contents of this document without prior
notice.
The detailed specifications agreed to at the
time of ordering apply to all orders. ABB
accepts no responsibility for possible errors
or incompleteness in this document.
We reserve all rights to this document and
the topics and illustrations contained therein.
The document and its contents, or extracts
thereof, must not be reproduced, transmitted
or reused by third parties without prior written
consent by ABB.
Copyright© 2014 Busch-Jaeger Elektro GmbH