FläktGroup eQ MASTER Owner's manual

Category
Thermostats
Type
Owner's manual
eQ MASTERÂŪ
COMMISSIONING
CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
Safety check
Commissioning
Display handling
Menu structure
Settings/Functions
Save/Restore
Communication
Adjustment protocol
3
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
SAFETY CHECK
WARNING!
MAIN POWER SWITCH/ISOLATOR SWITCH
The eQ MASTER unit has an integrated main power switch in the electrical cabinet.
Access to the rotary switch is on the outside of the unit. Parts that are powered separately, such as electric heaters, require a
separate isolator switch.
Prior to servicing or inspection, the unit’s main power switch and all isolator switches must remain switched off for at least
1 minute before opening the inspection doors. Reset all safety devices before restarting.
The main power switch may not be used for normal starting and stopping of the unit. This must be done using the hand-held
terminal.
Before putting the air handling unit into operation, t any unused connections with protective mesh.
In addition, all electrical and mechanical safety devices must be installed according to the eQ MASTER installation manual
before putting the air handling unit into operation.
Take extra care when opening the exhaust air valves for the hot water supplied to the air heater.
Risk of water hammer or steam discharge.
If the eQ MASTER is dismantled, FlÃĪktGroup will cease to be responsible for its compliance with the specied tightness class.
The unit’s doors are tted with locking handles. Ensure that the unit is always left locked, and that the keys cannot be
accessed by unauthorized persons. Follow the separate instructions for replacement of casing parts.
Local rules and regulations must always be followed.
Read these instructions carefully before commissioning the unit.
The unit’s owner or the installation rm is responsible for ensuring that the relevant safety rules are followed.
No unauthorised persons may operate the unit. Only qualied staff members may use the unit.
Make sure that all the included parts and tools for installing the unit are removed before operating the unit.
1
4
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
COMMISSIONING
Start by switching off the electricity supply
Check that the unit is horizontal.
Check that the inspection doors open and close smoothly. Adjust the hinges if necessary.
Check that the unit is clean on the inside and outside.
Dampers with actuators
Check that the connected dampers are in the closed position when the damper motor is in its end position.
Filter
Check that the lter cassettes are in place and the locking system is closed.
Rotor
Check that the rotary heat recovery unit rotates easily when pushed manually.
Manometers and ow metering instruments
Check that the instruments are set to zero and correctly connected (+/–) to the test points (+/–).
Check that all the safety restraints have been removed.
Switch on the main power switch
The control system settings are factory congured, but certain settings must be congured for each
installation. It can be useful to ll in the settings in the commissioning protocol at the end of this document.
P
P
P
P
P
P
P
P
Follow the instructions below regarding any parts that are included in your unit.
2
5
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
DISPLAY HANDLING/LOGIN/LANGUAGE SELECTION/TIME ADJUSTMENT
Two types of display are available for the eQ Master. The text shown in the window is identical in both displays, but the
method for selecting parameters and changing values differs between the displays.
2. Info button
Press to access Main index
â€Ē Extinguished = Stop,
OverRun
â€Ē Green steady illumination
= Normal operation
â€Ē Flashes green = StartUp,
Night kick, Free cooling,
Night kick heating/cooling
â€Ē Orange steady
illumination = Emergency
stop and alarm with stop
â€Ē Flashes orange = Fire
damper auto test from
display
â€Ē Alternating green/orange
= Manual operation
3. ESC button
â€Ē Press to return to previous menu/screen
â€Ē Press to cancel editing of a value
5. Dial
Turn anti-clockwise/
clockwise to navigate
up and down in menus.
Press the dial to enter a
menu or change a value.
Turn to change the value.
Hold down to go straight
to the login menu if the
value to be changed
requires login.
4. Alarm button
Function, see alarm
acknowledgement
â€Ē Flashes red = alarm
â€Ē
Red steady illumination
= alarm acknowledged
but persists
1. Display
Display of values and settings
3. ESC button
â€Ē Press to return to previous menu/screen
â€Ē Press to cancel editing of a value
1. Display
Display of values and settings
5. Up/increase
Press to navigate up the
list or to increase the
parameter value.
6. Down/decrease
Press to navigate down
the list or to decrease the
parameter value.
7. Enter button
Press the dial to enter a
menu or to conrm new
value. Hold down to go
straight to the login menu
if the value to be changed
requires login.
2. Info button
Press to access Main
index
â€Ē Extinguished = Stop,
OverRun
â€Ē Green steady illumination
= Normal operation
â€Ē Flashes green = StartUp,
Night kick, Free cooling,
Night kick heating/cooling
â€Ē
Orange steady illumination
= Emergency stop and
alarm with stop
â€Ē Flashes orange = Fire
damper auto test from
display
â€Ē Alternating green/orange
= Manual operation
4. Alarm button
Function see alarm
acknowledgement
â€Ē Flashes red = alarm
â€Ē Red stead illumination =
alarm acknowledged
but persists
3
6
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
DISPLAY HANDLING/LOGIN/LANGUAGE SELECTION/TIME ADJUSTMENT
PASSWORD ENTER
There are four predened user levels as standard.
User level Password Comment
Not logged in No login required Detailed information and time/date are displayed.
Application information and software version.
Setpoints and special settings not permitted.
User 1000 Same as Not logged in plus permission to change all setpoints. Reset of operational
settings permitted.
Service 2000 Same as User, plus permission to change controller settings and congure external
communication. Change of alarm classes and alarm limits is also permitted.
Factory Contact FlÃĪktGroup
The selected user level must be “User” or higher in order for
the user to make changes.
If “Password enter” is not shown on the second row of the
display, press the Info button. Select Password enter and go into
that level. Enter password and Accept.
3
Main overview
Manual operation Auto
Act operating mode Oîđą
Outdoor air temp 18.4 °C
Supply air temp 21.4 °C
Act room tmp 21.3 °C
Start page
Password enter
Enter password
Item
7
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
DISPLAY HANDLING/LOGIN/LANGUAGE SELECTION/TIME ADJUSTMENT
LANGUAGE SELECTION
Login is required to manage language settings.
MAIN INDEX Ú SYSTEM OVERVIEW Ú
LANGUAGE SELECTION
Language selection is done in the display. Other language settings
are managed in the same menu.
ADJUST THE DATE AND TIME
To set the date and time, open Main index → System overview, select
the row for date and time and adjust as necessary.
3
Air handling unit
Global functions
Main index
System overview
Overview IO conî‚ŋg/rawvalues
Version
Save / restore
Trend Stop
Event history O
Alarm snap shot Unused
Password handling
HMI
System overview
Language selection
HMI language Swedish
+Alarm snap shot
Save ->SD Swedish
+Modem
SMS language. English
Language selection
Communication
Application info
Version
Save / restore
Trend Stop
Event history O
Alarm snap shot Unused
System overview
O2.O3.2017 O8:O2:38
8
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
MENU STRUCTURE
MENU STRUCTURE eQ FLÄKT 3.XX
The menus in the display are extensive. This document
describes selected parts of the menu structure to enable
the user to get the system up and running. The menus differ
depending on the activated functions and the selected
login.
From now on, the menus shown in this document will be
the ones in the “Service” user level with all functions
activated.

u
Start page

u
Password enter

u
Main index

u
Air handling unit
 
u
Main overview
 
u
Inputs
 
u
Outputs
 
u
Operating mode
  
u
Time switch program
  
u
External control
  
u
Night kick exh tmp
  
u
Night cooling
  
u
Tmp start
  
u
Boost
 
u
Setpoints/settings
 
u
Damper control
 
u
Fan control
 
u
Temp control
 
u
Humidity control
 
u
Air quality control
 
u
Auxiliary
 
u
Loop controllers
 
u
Operating hours
 
u
IPSUM
 
u
External alarms
 
u
Energy display

u
Global functions
 
u
Su/Wi calculation
 
u
Manual mode
u
Enable manual alarm
u
Enable comm test
u
Communication test
u
Alarm Snap Shot -> SD
u
Archiv Enable
u
Trendarchiv Export
u
I/O ext. modul Reliability Dly
u
Reset I/O to Auto
 
u
Cooling/Heating register for kick interval pump

u
System overview
 
u
Date / time
 
u
Communication
 
u
Application info
 
u
Version
 
u
Save/Restore
 
u
Trend
 
u
Event history
 
u
Alarm – Snap shot
 
u
Password handling
 
u
HMI
 
u
Language selection

u
Overview IO config/rawvalues
 
u
Temperatures
 
u
Pressures / flows
 
u
Humidity
 
u
Digital inputs
 
u
Digital alarms
 
u
Specials
 
u
Outputs damper
 
u
Outputs fans
 
u
Outputs temp. control
u
Outputs humidifier
 
u
Outputs auxiliary
 
u
Outputs alarm

u
Main overview
4
9
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
MENU STRUCTURE
PASSWORD ENTER
(See section 3)
MAIN INDEX
Air handling unit
Main overview Provides a detailed overview of the actual operating status and access to further settings.
Inputs Status, measured values and alarm settings for all analog and digital inputs.
Outputs Status and alarm settings for all analog and digital outputs.
The outputs can also be manually overridden.
Operating mode Main index for stop/low speed/high speed-related operation.
Time switch program Settings/schedule for timer switch.
External control Settings and status for External control.
Night kick exh tmp Settings for temperature control for tmp start/summer night cooling.
Night cooling Summer night cooling status and settings.
Tmp start Tmp start status and settings
Boost Boost function status and settings.
Setpoints/Settings Portal for all setpoint, limit and time settings.
Damper control Menu for damper settings.
Fan control Fan operating status, setpoints and settings.
Temp control Temperature control operating status, setpoints and settings.
Humidity control Humidity control operating status, setpoints and settings.
Air quality control Air quality control operating status, setpoints and settings
Auxiliary Auxiliary operating status, setpoints and settings.
Loop controllers Portal for all activated controllers, for reading of all controller signals and faster access to
controller settings.
Operating hours Reading and resetting of operating hours for each object.
IPSUM Reading of signals from IPSUM system.
External alarms External alarms status and settings.
Energy display Reading of instantaneous power, energy use/savings from recycling, fans, heating and cool-
ing coils.
Global functions Overview and change of general functions that do not depend directly on the function of the
selected application.
Su/Wi calculation Summer/Winter mode status and settings.
Manual mode Manual mode status and settings.
Activate manual alarm Menu for manual alarm activation.
Activate comm test Menu for manual communication test activation.
Communication test Menu with various communication test settings.
Alarm Snap Shot -> SD Menu for controlling mode for saving alarm to/from SD card.
Archiv Enable Menu for controlling mode for archiving events.
Trendarchiv Export -> SD Menu for setting time and frequency of exporting trend archive to SD card.
MENU STRUCTURE eQ FLÄKT 3.XX
START PAGE
(This page is displayed after startup. The page shows selected information regarding operating status and temperatures.)
4
10
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
I/O ext. module reliability delay Delay time for communication to extension module.
Reset I/O to Auto Reset all I/O points to Auto read/control or perform a conduction test.
Cooling-Heating registers General time settings for pump heat recovery kick.
System overview Portal for changing/reading of time, date, communication settings, backup/reset, history/
trends and language.
Date / time Reading/setting of actual time.
Communication Reading/setting of communication (external and internal), IP addresses, protocols, modem,
SMS and passwords.
Application info The software version currently used in the controller and rows for entering name and address
of installation.
Version Reading of versions and serial numbers on the hand control and connected units.
Save/Restore Portal for saving congured settings on SD card, resetting settings from SD card or resetting
to factory settings. Update of new software.
Trend Settings for logging.
Event history
Alarm-snap shot Alarm snap shot settings.
Password handling Menu for login and change of password.
HMI Display settings.
Language selection Language settings.
Overview IO cong/rawvalues Shows which inputs/outputs are used for the various functions and the actual raw value of
the signal.
MAIN OVERVIEW
(Same as previously.)
MANUAL OPERATION
(Shortcut for starting and stopping the unit directly from the top menu.)
ACT OPERATING MODE
Shows current mode.
MENU STRUCTURE
MENU STRUCTURE eQ FLÄKT 3.XX
4
11
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
MENU STRUCTURE
MENU STRUCTURE eQ EXTRAS
These menus only occur in the separate controller with functions for Extra Zones 1 and 2, control of extra fans and control of water circuits.
u Start page
u Password enter
u Main index
u Air handling unit
u Zone 1
u Zone 2
u Extra fans
u Water circuits
 u Radiator circuit
 u Cold water circuit
 u Domestic hot water
u Global functions
 u Su/Wi calculation
 u Manual mode
u Enable manual alarm
u Enable comm test
u Communication test
u Alarm Snap Shot -> SD
u Archiv Enable
u Trendarchiv Export
u I/O ext. modul Reliability Dly
u Reset I/O to Auto
 u Cooling/Heating register for kick interval pump
u System overview
 u Date / time
 u Communication
 u Application info
 u Version
 u Save/Restore
 u Trend
 u Event history
 u Alarm – Snap shot
 u Password handling
 u HMI
 u Language selection
u Overview IO config/rawvalues
START PAGE
This page is displayed after the system has been commissioned.
The page shows selected information regarding operating status and temperatures.
PASSWORD ENTER
See section 3.
MAIN INDEX
Air handling unit
Zone 1 Extra temperature zone 1 for aftertreatment. Gives detailed information on function, input and output
signals, operation, setpoints and settings.
Zone 2 Extra temperature zone 2 for aftertreatment. Gives detailed information on function, input and output
signals, operation, setpoints and settings.
Extra fans Operating information, settings and handling of Extra fans.
Water circuits
4
12
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
Radiator circuit Detailed information and settings for radiator circuit, including any pre-congured outdoor temperature
control.
Cold water circuit Detailed information and settings for cold water circuit, including any pre-congured dew point
compensation.
Domestic hot water Detailed information and settings for domestic hot water including any pre-congured legionella
decontamination calender.
Global functions Overview and change of global functions that do not depend directly on the function of the selected
application.
Su/Wi calculation Summer/Winter mode status and settings.
Manual mode Manual mode status and settings.
Activate manual alarm Menu for manual alarm activation.
Activate comm test Menu for manual communication test activation.
Communication test Menu with various communication test settings.
Alarm Snap Shot -> SD Menu for controlling mode for saving alarm to/from SD card.
Archiv Enable Menu for controlling mode for archiving events.
Trendarchiv Export -> SD Menu for setting time and frequency of exporting trend archive to SD card.
I/O ext. modul Reliability Dly Delay time for communication to extension module.
Reset I/O to Auto Reset all I/O points to Auto read/control or perform a conduction test.
Cooling-Heating registers General time settings for pump heat recovery kick.
System overview Portal for changing/reading of time, date, communication settings, backup/reset, history/trends and
language.
Date / time Reading/setting of actual time.
Communication Reading/setting of communication (external and internal), IP addresses, protocols, modem, SMS and
passwords.
Application info The software version currently used in the controller and rows for entering name and address of
application.
Version Reading of versions and serial numbers on the display and connected units.
Save/Restore Portal for saving congured settings on SD card, resetting settings from SD card or resetting to factory
settings. Update of new software.
Trend Settings for logging.
Event history
Alarm-snap shot Alarm snap shot settings.
Password handling Menu for login and change of password
HMI Display settings.
Language selection Language settings.
Overview IO cong/rawvalues Shows which inputs/outputs are used for the various functions and the actual raw value of the signal.
MENU STRUCTURE
MENU STRUCTURE eQ EXTRAS
4
13
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
SETTINGS/FUNCTIONS
If a function is not activated, its menus or settings will not be
visible. The same applies within the function, depending on which
sub-functions are activated. For instance, if only fan stage 1 is acti-
vated, fan stages 2 and 3 cannot be selected in other functions.
DAMPERS
Multiple dampers can be connected and controlled by the eQ
Master. The dampers are controlled either via Modbus or via IO.
No additional settings need to be congured for damper actua-
tors connected via Modbus. The settings are factory congured.
Settings for directly connected damper actuators (i.e. damper
actuators connected to IO by an installation engineer) are under
MAIN INDEX Ú UNIT Ú
DAMPER CONTROL
An Off delay time is congured here. This means the time the
damper waits before switching off after the fans are switched off.
An “Opening time” is specied under Dampers The opening time
is the operating time allowed in order for the damper to open. All
directly connected dampers have the same operating parameters.
In other words, the supply air damper and the extract damper have
the same parameters. If the selected damper actuators have diffe-
rent opening times, the longest time should be specied.
Supply air control
Supply air control is a temperature control function where the
supply air temperature is kept constant, with or without some type
of setpoint offset, without any data being sent from the room. This
control function is suitable in rooms where the heating and cooling
loads are relatively constant and predictable, or rooms with indivi-
dual room control.
Room control
Room control is available in two versions, either with or without
a cascade function. The room temperature is measured and the
supply air temperature is adjusted as necessary. The user sets
minimum and maximum limits for the supply air temperature.
If room control is used, two sensors can be used to control the
temperature based on an average value.
Extract air control
Extract air control is the same as the room control function above,
except instead of the room temperature being measured, the
primary sensor is installed in the extract air duct.
Heating-cooling
setpoint
Set the heating setpoint and cooling
setpoint as separate values.
Cooling setpoint â‰Ĩ Heating setpoint.
Heating setpoint +
dead zone
Specify heating setpoint and dead zone.
Cooling setpoint = Heating setpoint +
dead zone.
Cooling setpoint –
dead zone
Specify cooling setpoint and dead zone.
Heating setpoint = Cooling setpoint –
dead zone.
Setpoint ÂąÂ― dead
zone
Specify the setpoint as the average
of the heating and cooling setpoints,
with the desired dead zone distributed
equally above and below the setpoint
value.
SECTION 5.
DAMPER............................................................................................................ 13
TEMPERATURE .........................................................................................13–14
OUTDOOR TEMPERATURE COMPENSATION .........................................14
OUTDOOR TEMPERATURE CURVE ...........................................................14
COOLING RECOVERY TEMPERATURE .....................................................14
COOLING RECOVERY ENTHALPY ............................................................. 15
FANS .................................................................................................................. 15
EXTRA FANS eQ EXTRA ........................................................................15–16
RECOVERY UNIT.......................................................................................17–19
AFTERTREATMENT ................................................................................20–22
PUMP CONTROL .....................................................................................22–23
EXTRA ZONES eQ EXTRA ............................................................................24
HUMIDITY ................................................................................................. 24–25
COMBINED PRODUCTS ................................................................................26
FILTERS .............................................................................................................27
PRE-HEATING ..................................................................................................27
OPERATING MODE .................................................................................28–30
OTHER FUNCTIONS ................................................................................31–35
WATER CIRCUITS eQ EXTRA ..............................................................36–38
TEMPERATURE
It generally applies to all temperature control that there are several
ways of setting the desired setpoint. When the temperature drops
below the heating setpoint, the heating sequence is activated, and
when it rises above the cooling setpoint the cooling sequence is
activated. When the actual temperature is within the dead zone,
all output signals that affect temperature will be zero. The compo-
nents that deliver cooling/heating are controlled in sequence in a
predetermined order, which is factory congured.
5
14
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
The settings for outdoor temperature compensation are under
Here you can choose the settings for either Summer compensation
or Winter compensation.
OUTDOOR TEMPERATURE CURVE
As an alternative to outdoor temperature compensation, the
temperature setpoint can be controlled by an outdoor temperature
curve with four break points.
The temperature remains constant above or below the curve’s
limits. The control setpoint changes linearly between the break
points. The heating and cooling setpoints are separated by an
adjustable dead zone, Cooling setpoint = Heating setpoint + Dead
zone.
Settings
The setpoint settings for the curve itself are under
The dead zone settings are one level up in the menu. The dead
zone settings cannot be congured if only heat recovery is availa-
ble as a cooling/heating stage.
COOLING RECOVERY TEMPERATURE
If the extract air temperature is lower than the outdoor air tempera-
ture and there is a demand for cooling, the heat recovery unit can
be started for full recovery. This saves energy by recovering cooling
energy from the extract air. The temperature difference between
the extract air and the outdoor air is set to 1 °C on delivery, but can
be changed under
SETTINGS/FUNCTIONS
Min./Max. limitation of supply air temperature
This is a subfunction of Room control and Extract air control. This
function limits the setpoint for the supply air temperature to prevent
the supply air temperature from becoming too high or low.
Settings
The settings for Min./Max. limitation are under
OUTDOOR TEMPERATURE COMPENSATION
Outdoor temperature compensation is a function that adjusts the
setpoint according to the actual outdoor temperature. The compen-
sation can be either positive or negative depending on demand.
The control has four break points.
MAIN INDEX Ú UNIT Ú TEMP CONTROL Ú
TMP SETPOINTS
MAIN INDEX Ú UNIT Ú TEMP CONTROL Ú
TMP SETPOINTS ÚCALC.HTG.SETPOINT
Outdoor
temperature
Control setpoint
X1/Y1 X2/Y2 X3/Y3
X4/Y4
âžĪ
âžĪ
âžĪ
âžĪ
MAIN INDEX Ú UNIT Ú TEMP CONTROL Ú
TMP SETPOINTS ÚACTIVATE COOLING RECOVERY Ú
TEMP. DIFF.
Here is an example of positive compensation, both in winter and
summer. Winter compensation is activated at 0 °C and reaches
maximum effect (+3K) at -15 °C, while summer compensation
starts at 15 °C and reaches maximum effect (+5K) at 25 °C. The
basic setpoint is 21 °C. The control setpoint depends on the
settings set for the dead zone.
27
25
23
21
19
17
15
Active setpoint
-20 -15 -10 -5 0 5 10 15 20 25 30
MAIN INDEX Ú UNIT Ú TEMP CONTROL Ú
TMP SETPOINTS Ú SUMMER COMP/WINTER COMP
Setpoints
Setpoints are changed under
MAIN INDEX Ú UNIT Ú
TEMP CONTROL Ú TMP SETPOINTS
The PID settings and control limits are changed individually for each
type of congured control in the following menu
MAIN INDEX Ú UNIT Ú TEMP CONTROL Ú
CONTROLLER ÚSPECIAL SETTINGS
5
15
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
SETTINGS/FUNCTIONS
COOLING RECOVERY ENTHALPY
Cooling recovery enthalpy is a variant of standard cooling recovery.
This function requires humidity sensors in the outdoor and the
extract air. No settings are required.
FANS
Flow control
This is the standard function, which means that the control equip-
ment tries to keep the ow constant. This function should not be
used if the installation has dampers that could affect the duct
pressure.
Pressure control
This function keeps the duct pressure constant in the installation. It
requires a pressure sensor to be installed in the duct. This function
is suitable for IPSUM or similar VAV systems.
Slave control
If one of the fans is selected with slave function, that fan will be
controlled as a slave by the other fan. In other words, it will be
ow-controlled and will get its control setpoint from the other fan’s
actual ow value Âą of offset. This function can be useful if one of the
fans is controlled by demand and the other fan always needs to
adjust accordingly to balance the ow.
Fan compensation
The fan setpoint can be affected by room temperature, air quality,
room humidity, outdoor temperature, a ReCooler device or as part
of the temperature sequence. The compensation can be positive or
negative according to user preference.
Settings
All setpoint settings for individual fans are found here
The offset settings (if slave control is used) are under
MAIN INDEX Ú UNIT Ú FAN CONTROL Ú
SUPPLY FAN/EXHAUST FAN ÚSETPOINTS/SETTINGS
MAIN INDEX Ú UNIT Ú FAN CONTROL Ú
SLAVE OFFSET
The Fan compensation settings are under
or under
depending on which fan compensations have been selected. If
compensation based on an outdoor temperature curve has been
selected, the settings can be found under
The controller settings are under each individual fan and controller.
MAIN INDEX Ú UNIT Ú TEMP CONTROL
MAIN INDEX Ú UNIT Ú AIR QUALITY CONTROL
MAIN INDEX Ú UNIT Ú FAN CONTROL Ú SUPPLY
FAN/EXHAUST FAN ÚSETPOINTS/SETTINGS
MAIN INDEX Ú EXTRA FANS Ú EXTRA FAN ON/OFF
Control Operation mode switch
Time switch
program
Settings for separate scheduler.
See Timer switch for more information
Actual Provides information on actual
operating mode
Command Override control of fan for testing
Alarms Alarm settings, alarm class, alarm
conguration, alarm delay, alarm input
NO/NC
Setpoints/
settings
Settings for re mode (if applicable) and
minimum operating time
EXTRA FANS eQ EXTRA
Up to three fans can be controlled together with the ventilation unit.
The fans can have their own schedulers or operate together with
the ventilation unit.
Extra fan ON/OFF
This fan can only be controlled ON/OFF, either with a separate
scheduler, constantly on or according to one the ventilation unit’s
operation modes.
Settings
The settings are under
5
16
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
Extra fan 1 and 2
These two fans are operated via a frequency converter. They can
be pressure- or ow-controlled, operated in 1 or 2 stages with xed
rotor speeds and either operate together with the ventilation unit or
have their own schedulers.
Settings
Settings are under (X = 1 or 2)
MAIN INDEX Ú EXTRA FANS Ú EXTRA FAN X
SETTINGS/FUNCTIONS
Operation St1 Operation mode switch for stage 1.
Operation St2 Operation mode switch for stage 2.
Time switch program Settings for separate scheduler.
See Timer switch for more information.
Controller PID settings, actual output signal,
actual setpoint.
Output signal Override control of controller signal.
Command Command output settings.
Alarm
Pressure/Flow Settings for pressure/ow alarms
high/low pressure/ow.
Setpoints/settings Settings for setpoints, ow compen-
sation on the unit, re operation mode
and deviation alarm, as well as the
actual electrical parameters (if they are
available from the frequency converter).
Warning
5
17
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
RECOVERY UNIT
Rotary heat recovery (hrec)
Check that the heat recovery unit runs smoothly and that the seals
are intact and tight. The heat recovery unit may need help starting
if its running direction has been changed. The heat recovery unit
should rotate so that when the wheel is downstream of the extract
air, it passes the purging sector before reaching the supply air.
Check that the pressure balance between the supply air and the
extract air is correct.
The pressure should be measured at nominal air ow in the ducts.
When the pressure is measured between P1 (-) and P2 (+) in the
picture, the pressure gauge should show a positive reading of 0-20
Pa for optimal functionality.
If the pressure difference is too large, the pressure in the supply
air duct should be increased, and if the difference is too small the
pressure in the extract air duct should be increased.
Frost protection
The rotary heat recovery unit can be equipped with various frost
protection systems if required.
SETTINGS/FUNCTIONS
Pressure Switch A pressure Pressure Switch (ON/OFF) that measures the pressure above the extract air on the rotor or an ex-
ternal thermostat in the duct can be used to detect frosting. The operating level for defrosting and the time delay
are set in the control system, while the temperature or pressure level is set on each individual sensor.
Temperature
A temperature sensor installed in the exhaust air stream limits the exhaust air temperature by restricting the output
signal to the recovery unit. An alarm function is also available which is triggered if the temperature drops too low.
The temperature limit and controller settings are congured in the control system.
Temperature and
Pressure Switch
A combination of both of the above.
Pressure sensor A pressure sensor (0–10V/Modbus) measures the pressure above the extract air on the rotor. When the desired
pressure is reached, the rotor speed decreases by one step, depending on the controller settings. The function
can be congured with I-time, D-time and an alarm limit for stopping the unit.
Pressure sensor
and Temperature
Pressure Switch
This is a combination of functionalities from the duct thermostat (monitor) and the pressure sensor specied
above. There is also an adjustable value for setting the max. rotor speed during defrosting.
Dew point A combined humidity/temperature sensor in the extract air stream measures actual extract air temperature
and humidity.
The actual dew point is calculated. The exhaust air temperature is calculated based on the supply air and
extract air ows, the outdoor and extract air temperatures and the actual rotor speed.
The exhaust air temperature is kept within the minimum limit by reducing the rotor speed so that it never falls
below the actual dew point plus a safety margin if this value is lower than 0 °C.
Only the safety margin needs adjusting.
Pre heating A pre-heating coil in the outdoor air can also be used to prevent frosting on the rotary heat recovery unit. The
frost detection function works according to the same principle as described above, except that instead of lim-
iting the recovery unit’s rotor speed, the pre-heating unit’s temperature setpoint is adjusted to prevent frosting.
Only the safety margin needs adjusting.
Settings
The frost protection settings are under
Exhaust air P1 Extract air
Outdoor air P2 Supply air
MAIN INDEX Ú UNIT Ú TEMP CONTROL Ú
HEAT RECOVERY
5
18
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
Heat recovery kick
The rotary heat recovery unit will remain idle for long periods during
the spring and autumn. At these times, the heat recovery unit
should be exercised in the same way as a pump or valve. This also
removes dirt and dust.
This function and its settings are under
MAIN INDEX Ú UNIT Ú CONFIGURATION Ú
CONFIGURATION 2 Ú ROT. HEATRECOVERY KICK
after setting “Hrec kick” to “Yes” in the same search path, while the
user is logged in as “Factory”.
Plate heat recovery unit
This type of recovery unit comes in two versions: one with cross
ow and one with counterow. Both versions function according to
the same basic principle, and their power is controlled by opening/
closing a damper so that the air is either directed through or past
the heat recovery block and all combinations in between.
Several frost protection/defrosting functions are available for the
heat recovery unit, two of which are completely independent of the
unit’s controller.
SETTINGS/FUNCTIONS
Pressure Switch A pressure monitor (ON/OFF) that measures the pressure above the extract air on the rotor or an external
thermostat in the duct can be used to detect frosting. The operating level for defrosting and the time delay are
set in the display, while the temperature or pressure level is set on each individual sensor.
Temperature level 1 Defrosting “Cold corner”. A temperature sensor next to the “cold corner” measures the temperature and limits
the control signal to the recovery unit, to prevent the temperature dropping too low.
Temperature level 1
plus monitor
A combination of both of the above.
Pressure sensor A pressure sensor gauges the pressure drop above the heat recovery unit’s extract air unit. If the pressure rises
above the set value, the control signal to the recovery unit is reduced, which lowers the efciency and prevents
further frosting.
If the pressure rises above the alarm limit value, the unit stops and an alarm is generated.
Pressure sensor +
Monitor
A combination of Pressure sensor and Monitor as referred to above.
Level 2 Section defrosting. All the logic is in the recovery unit’s internal control system. The unit’s control system only
controls demand from 0-100 %.
Level 3 A combination of pre-heating and section defrosting. All the logic is in the recovery unit’s internal control system.
The display only controls demand from 0–100%.
Settings
The frost protection settings are under
MAIN INDEX Ú UNIT Ú TEMP CONTROL Ú
HEAT RECOVERY
5
19
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
ECOTERM coil heat recovery
The underlying functional principle is that warm extract air heats
the liquid in the extract air coil, which is then circulated by a pump
over the supply air coil, where the heat is released into the supply
air and the liquid is cooled.
Humidity in the extract air, low outdoor temperatures and high
efciency cause frosting on the extract air coil.
SETTINGS/FUNCTIONS
Pressure Switch A pressure monitor (ON/OFF) that measures the pressure above the extract air on the rotor or an external
thermostat in the duct can be used to detect frosting. The operating level for defrosting and the time delay
are set in the display, while the temperature or pressure level is set on each individual sensor.
Temperature A temperature sensor in the liquid circuit that measures the inlet temperature into the extract air coil.
If this temperature drops below the set limit, the output signal to the pilot valve is reduced, which prevents
frosting. The temperature must be indicated in the display.
Temperature +
Pressure Switch
A combination of both of the above.
Pressure sensor A pressure sensor gauges the pressure drop above the heat recovery unit’s extract air unit. If the pressure
rises above the set value, the control signal to the recovery unit is reduced, which lowers the efciency
and prevents further frosting. If the pressure rises above the alarm limit value, the unit stops and an alarm
is generated.
Pressure sensor +
Pressure Switch
A combination of Pressure sensor and Monitor as referred to above.
Dew point A combined temperature/humidity sensor in the extract air stream measures humidity and temperature.
The display calculates the actual dew point in the extract air based on these data. A temperature sensor
in the liquid circuit measures the inlet temperature to the extract air coil. The display calculates the lowest
liquid temperature that is permitted in relation to the actual dew point, and limits the temperature of the
liquid by reducing the output signal to the pilot valve.
Settings
The frost protection settings are under
MAIN INDEX Ú UNIT Ú
TEMP CONTROL Ú HEAT RECOVERY
5
20
eQ MASTER COMMISSIONING
FlÃĪktGroup DC_9990GB 20190107_R0 Specifications are subject to alteration without notice
AFTERTREATMENT
Up to three heating coils (Heating 1, 2 and 3) and three cooling coils
(Cooling 1, 2 and 3) can be used for aftertreatment in the eQ Master.
They can all be different, and heating and cooling coils can also
be combined into a combi coil. Heating 1 and Cooling 1 = Combi 1,
Heating 2 and Cooling 2 = Combi 2, Heating 3 and Cooling 3 cannot
be combined to make a Combi 3 coil. The different coils (max. 4 in
total) can be installed anywhere in the heating/cooling sequence.
Install them where they are most effective.
Settings
The settings for loop controllers and reading of actual values are
under (X = 1 to 3)
Heating coil water
A pilot valve controls the liquid temperature or the liquid ow to the
coil. The coil can be equipped with various types of frost protection
and pump control systems.
Frost monitor function
Settings
The setpoints for Frost monitor and Frost monitor 2 are under
There are no settings for Frost monitor in the display, so this
function must be adjusted manually on the sensor.
Electric heater
There is a power control function inside the electric heater. The
coils are controlled from 0-10 V or via Modbus from the control
system, according to demand in the sequence with the other
aftertreatments.
Frost monitor A temperature sensor in the liquid circuit measures the return temperature of the liquid from the coil.
The return temperature is controlled against the setpoint that has been set for the frost protection
controller. If the temperature drops below the lower limit value, the valve opens.
If the liquid drops below the alarm limit value, an alarm is generated and the unit stops.
Frost monitor 2 setpoint Same as above, except that there are two different setpoints for forced opening of the pilot valve,
depending on whether the unit is in operation or idle. Default setting.
Frost monitor det. A thermostat (ON/OFF) is either tted in the airow downstream of the coil or in the liquid return ow
from the coil. When the thermostat senses that the temperature is too low, an alarm is generated.
SETTINGS/FUNCTIONS
MAIN INDEX Ú UNIT Ú
TEMP CONTROL Ú HEATING X/COOLING X Ú
CONTROLLER Ú SPECIAL SETTINGS
MAIN INDEX Ú UNIT Ú TEMP CONTROL Ú
HEATING X ÚFROST PROTECTION
5
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103

FläktGroup eQ MASTER Owner's manual

Category
Thermostats
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI