Robertshaw SMART 3000 Touchscreen Thermostat Quick start guide

Type
Quick start guide

Robertshaw SMART 3000 Touchscreen Thermostat is a multi-function thermostat that offers precise temperature control and advanced features for enhanced comfort and energy efficiency. With its intuitive touchscreen interface, you can effortlessly adjust settings and monitor your home's temperature. The SMART 3000 is designed to seamlessly integrate with your HVAC system, providing optimal performance and reliability.

Key capabilities of the Robertshaw SMART 3000 Touchscreen Thermostat include:

  • Manual thermostat: Set and adjust the desired temperature with ease using the intuitive touchscreen interface.

Robertshaw SMART 3000 Touchscreen Thermostat is a multi-function thermostat that offers precise temperature control and advanced features for enhanced comfort and energy efficiency. With its intuitive touchscreen interface, you can effortlessly adjust settings and monitor your home's temperature. The SMART 3000 is designed to seamlessly integrate with your HVAC system, providing optimal performance and reliability.

Key capabilities of the Robertshaw SMART 3000 Touchscreen Thermostat include:

  • Manual thermostat: Set and adjust the desired temperature with ease using the intuitive touchscreen interface.
SMART 3000 Touchscreen Thermostat
Quick Start Guide
www.robertshaw.com
©2015 Robertshaw
7/15 – 352-00198-001 RevB
by Uni-Line®
2
IMPORTANT SAFETY INFORMATION
WARNING: ELECTRICAL SHOCK HAZARD – Turn off power at the main
power source by unscrewing fuse or switching circuit breaker
to the OFF position before installing, removing, or cleaning
this thermostat.
WARNING: FIRE AND ELECTRIC SHOCK HAZARD – This device should be
installed by a qualified service technician with due regard
for safety as improper installation could result in a fire and
electric shock hazard.
WARNING: FIRE AND ELECTRICAL SHOCK HAZARD – This is a 24V AC
low-voltage thermostat. Do not install on voltages higher
than 30V AC.
• Do not switch system to cool if the temperature is below 50°F (10°C). This
can damage your cooling system and may cause personal injury.
• Do not short (jumper) across terminals on the gas valve or at the system control
to test installation. This will damage the thermostat and void the warranty.
• Do not connect ground to any terminal in this unit.
• All wiring must conform to local and national building and electrical codes
and ordinances.
• Use this thermostat only as described in the manual.
3
Thank you for purchasing a SmartSense
TM
thermostat by Uni-Line
®
. The SMART 3000
isamul-funconthermostat.Severalconguraonsmaybeprogrammed
throughthebuoninterfaceorremotely,usingModbuscommunicaons.
Thisisaquickstartguideonhowtoperformthebasicinstallaon,programming
andtesngoftheSMART3000soitfunconsasasingle-stage,manual
thermostat.
Onlythestepsneededtoprovideafunconingthermostatwithminimalfeatures
andprogrammingwillbediscussed.Whennished,thethermostatwillbe
operaonalforthefollowing:
• Manual thermostat
• 1 Speed Fan
• 1 Heat/1 Cool
• 2 pipe mode
• Thermostat controlled fan
• Short cycle timer at five minutes
• Single setpoint
4
Mounting the SMART 3000 Thermostat
IMPORTANT: The SMART 3000 can only be as accurate as the onboard
temperaturesensor,oritsoponalremotetemperaturesensor(s)
permit. The SMART 3000 should be mounted in a location that is
typical of the ambient room temperature. Do not install near the
floor,inadraft,behindadoor,oronanon-insulated,exteriorwall.
InstalltheSMART3000awayfromexposuretosunlightandfourto
five feet (1.2 to 1.5 m) above the floor.
Figure 1
• Locate the slot on the housing at the bottom. Take note of the hinge points
and the connection between the two halves.
• Insert a screwdriver or coin into the slot and twist. This will separate the two
halves.
5
• Continue to swing the top half upward. This will release the tabs holding the
top half in place.
• Pull the control wires through the large opening in the base plate.
• Position the base plate on the wall and attach it with appropriate fasteners
(two screws with drywall anchors are supplied). The base plate should be
visibly level.
• Block any holes where wires are pulled through a wall opening. This will
prevent drafts from entering the back of the thermostat.
Do not use
these holes for
mounting.
Figure 2
IfthisinstallaonwillbeusingModBuscontrolsorremotesensors,becertainto
includetheproperwirestomakethoseconnecons.
6
Switch Set-Up
LocatetherowofeightfunconDIPswitches.
Figure 3
Switch 1 2 3 4 5 6 7 8
Position OFF OFF ON ON ON OFF OFF OFF
NOTE: ThiswillconfiguretheSMART3000asamanualheat/cool,singlestage,
single setpoint thermostat.
7
Wiring
Terminal Funcon
C 24V Common or Neutral
R 24V AC - This voltage is switched back through the relays
Hi Indoor Fan High Speed (NOT Used in Single fan speed mode -
Sw 1 = OFF)
Med Indoor Fan Medium Speed (NOT Used in Single fan speed mode -
Sw 1 = OFF)
Low Indoor Fan Low Speed (Used in single and three fan speed mode)
Y Compressor or Cool - (Based on Sw 2 setting)
W - O/B Reversing Valve or Heat - (Based on Sw 2 setting)
A1 – Cool 0 to 10V Output for Cooling (Typically used to control modulating valves)
A2 – Heat 0 to 10V Output for Heating (Typically used to control modulating valves)
A3 – Fan 0 to 10V Modulating Output for Indoor DC Fan
Com – 0V 0Vterminal-Usedfor0to10V,sensorordigitalinputsgroundreference
A ModBus Data A
B ModBus Data B
SI Remote temperature sensor input (Remote/average/ModBus data use)
DI Digital (Switched input) for forced unoccupied or initiate doorbell
function
8
Terminal Funcon
WC Window Contact - Forces SMART 3000 OFF if window open > five min
(Adjustable)
DS Door Switch – Monitors room door status for occupancy detection
PIR PIR (Movement sensor) input for occupancy detection
TheSMART3000ispoweredby24VACandrequiresthe24VACacveand
neutraltobeconnectedtotheR(acve)andC(Neutral)terminalstofuncon.
The 24V AC applied to the SMART 3000 R terminal is switched back through the
2A relays to the equipment.
Figure 4
9
Fan
Cool
Heat
24 V AC
24 C Neutral
Figure 5
Close the Cover
• Hold the cover up and connect the top hinge points between the two halves.
• Position the top cover with the pins in the base plate openings.
• Swing the top half downward until it snaps in place. The electrical pins at the
bottom will slide into the terminal strips.
10
Apply Power
• Apply the 24V AC power to the SMART 3000. The screen should display the
current temperature.
Test
Eachpressofabuonshouldproduceanaudiblebeep.
Figure 6
• Press the Fan button to test the fan operation.
• Use the Up and Down arrow buttons to adjust the setpoint.
• Adjust the setpoint five degrees above the room temperature. After a few
moments the heating system should come ON.
• Adjust the setpoint five degrees below the room temperature. After a few
11
moments the heat system will stop. The cooling system should come ON.
NOTE: There may be a delay of up to four minutes performing this test due to
anticycle delay timer.
The SMART 3000 system is now operational. It will function as a single
setpoint, manual thermostat with a single speed fan.
www.uni-line.com
www.robertshaw.com
©2015 Robertshaw
07/15 – 352-00198-001 RevB
Robertshaw®,Uni-Line®andSmartSense
TM
aretrademarksofRobertshaw,itssubsidiaries
and/or affiliated companies. All other brands
mentioned may be the trademarks of their
respective owners.
Customer Service Telephone 1.800.304.6563
Customer Service Facsimile 1.800.426.0804
HVACCustomerService@robertshaw.com
For Technical Service
Telephone 1.800.445.8299
Facsimile 1.630.260.7294
TechnicalService@robertshaw.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Robertshaw SMART 3000 Touchscreen Thermostat Quick start guide

Type
Quick start guide

Robertshaw SMART 3000 Touchscreen Thermostat is a multi-function thermostat that offers precise temperature control and advanced features for enhanced comfort and energy efficiency. With its intuitive touchscreen interface, you can effortlessly adjust settings and monitor your home's temperature. The SMART 3000 is designed to seamlessly integrate with your HVAC system, providing optimal performance and reliability.

Key capabilities of the Robertshaw SMART 3000 Touchscreen Thermostat include:

  • Manual thermostat: Set and adjust the desired temperature with ease using the intuitive touchscreen interface.