Harman Absolute63 Pellet Stove Installation guide

Category
Stoves
Type
Installation guide
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2313-90-999000I
Model(s):
Absolute63 Freestanding Pellet Stove
Installation Manual
Installation and Appliance Setup
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
NOTICE: SAVE THESE INSTRUCTIONS
Please read this entire manual before
installation and use of this pellet fuel-
burning room heater.
Failure to follow these instructions could
result in property damage, bodily injury
or even death.
• Donotstoreorusegasolineorotherammablevapors
andliquidsinthevicinityofthisoranyotherappliance.
• Donotoverre-Ifanyexternalpartstartstoglow,you
areoverring.Reducefeedrate.Overringwillvoid
yourwarranty.
• Complywithallminimumclearancestocombustibles
asspecied.Failuretocomplymaycausehousere.
WARNING
Hot glass will cause burns.
• Donottouchglassuntilitiscooled.
• NEVERallowchildrentotouchglass.
• Keepchildrenaway.
• CAREFULLYSUPERVISEchildreninsameroomas
stove.
• Alertchildrenandadultstohazardsofhightemperatures.
High temperatures may ignite clothing or other
ammable materials.
• Keepclothing,furniture,draperiesandotherammable
materialsaway.
HOT SURFACES!
Glassandothersurfacesarehotduring
operationANDcooldown.
WARNING
Testedandapprovedforwoodpelletfuelonly.Burningof
anyothertypeoffuelvoidsyourwarranty.
CAUTION
!
To obtain a French translation of this manual, please
contactyourdealerorvisitwww.harmanstoves.com
Pourobtenirunetraductionfrançaisedecemanuel,s’il
vous plaît contacter votre revendeur ou visitez www.
harmanstoves.com
NOTE
Checkbuildingcodespriortoinstallation.
• InstallationMUSTcomplywithlocal,regional,stateand
nationalcodesandregulations.
• Contactlocalbuildingorreocialsaboutrestrictions
andinstallationinspectionrequirementsinyourarea.
CAUTION
!
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2323-90-999000I
TABLE OF CONTENTS
InstallationStandardWorkChecklist...............3
1 Product Specic and Important Safety Information
A.ApplianceCertication .......................4
B.GlassSpecications.........................4
C.MobileHomeApprovals......................4
D.BTUSpecications..........................4
E.ElectricalCodes............................4
F. CaliforniaSafetyInformation ..................4
2 Getting Started
A.DesignandInstallationConsiderations ..........5
B.ToolsandSuppliesNeeded ...................6
C.InspectApplianceandComponents.............6
3 Framing and Clearances
A.ApplianceDimensionDiagram.................7
B.Non-CombustibleMaterialsSpecication.........8
C.CombustibleMaterialsSpecication.............8
D.ClearancestoCombustibles...................8
E.FloorProtection ............................9
F. MobileHomeInstallation .....................9
4 Termination Location and Vent Information
A.VentTerminationMinimumClearances .........10
B.ChimneyDiagram..........................15
C.Venting&UseofElbows ....................16
D.OutsideAir ...............................18
E.LocatingYourApplianceandChimney..........19
F. Draft ....................................19
G.NegativePressure .........................19
H.AvoidingSmoke&Odors....................20
I. FireSafety ...............................21
J. InspectAppliance&Components..............21
5 Appliance Setup
A.Unpacking................................22
B.FireboxDraftandCombustionFanRPM........22
C.FirebrickInstallation........................23
D.WirelessRoomSensor......................23
E.FlameGuide..............................23
6 Reference Materials
A.SafetyReminders..........................24
B.WiringDiagram............................25
Safety Alert Key:
DANGER! Indicatesahazardoussituationwhich,ifnotavoidedwillresultindeathorseriousinjury.
WARNING!Indicatesahazardoussituationwhich,ifnotavoidedcouldresultindeathorseriousinjury.
CAUTION! Indicatesahazardoussituationwhich,ifnotavoided,couldresultinminorormoderateinjury.
NOTICE:Indicatespracticeswhichcouldcausedamagetothestoveortoproperty.
!
= Contains updated information
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2333-90-999000I
Installation Standard Work Checklist
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Thisstandardworkchecklististobeusedbytheinstallerinconjunctionwith,notinsteadof,theinstructionscontainedin
thisinstallationmanual.
Customer: ________________________________ Date Installed: __________________________
Lot/Address: ________________________________ Location of Stove: __________________________
________________________________ Installer: __________________________
Model: ________________________________ Dealer/Distributer Ph # __________________________
Serial Number: __________________________
WARNING! Risk of Fire or Explosion! Failure to install appliance to these instructions can lead to a re
or explosion.
Appliance Install
Section 3 YES IF NO, WHY?
Requirednon-combustibleoorprotection     ________________________________
Veriedclearancestocombustible.      ________________________________
UnitisLeveledandsecured.       ________________________________
Venting/Chimney Section 4
VentingCongurationcompliestoventdiagrams.    ________________________________
Ventinginstalled,sealedandsecuredinplacewithproperclearances.  ________________________________
Exteriorwall/roofashinginstalledandsealed     ________________________________
Terminationsinstalledandsealed.      ________________________________
Electrical Section 1
120VACunswitchedpowerprovidedtotheappliance.    ________________________________
Checkoutletwithmulti-meterforpropervoltage.(115-120VAC)   ________________________________
 Recordvoltagereading:___________
Appliance Setup Section 5
Allpackagingandprotectivematerialsareremoved    ________________________________
Accessoriesinstalledproperly       ________________________________
Manualbagandallit’scontentsareremovedfrominsidetheappliance
andgiventopartyresponsibleforuseandoperation    ________________________________
Startedapplianceandveriedthatallmotorsandblowersoperate
astheyshould.         ________________________________
CheckeddraftusingaManometer.Recordreadings:__________  ________________________________
Duringoperation,verifythatthehopperlidswitch(Ifapplicable)
andpressureswitchareworkingproperlybybrieyopeningthehopper
lidandmaindoorandverifyingthatthefeedmotorisinterrupted.  ________________________________
HearthandHomeTechnologiesrecommendsthefollowing:
Photographingtheinstallationandcopyingthischecklistforyourle.
Thischecklistremainvisibleatalltimesontheapplianceuntiltheinstallationiscomplete.
Comments:Furtherdescriptionoftheissues,whoisresponsible(Installer/Builder/OtherTrades,etc.)andcorrectiveaction
needed__________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
Commentscommunicatedtopartyresponsible____________________by________________________on__________
     (Builder/GenContractor)(Installer)   (Date)
04/23
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2343-90-999000I
A. Appliance Certication
B. Glass Specications
This appliance is equipped with 5mm mirrored ceramic
glass.Replaceglassonlywith5mmmirroredceramicglass.
Pleasecontactyourdealerforreplacementglass.
C. Mobile Home Approved
This appliance is approved for mobile home installations
whennotinstalledinasleepingroomandwhenanoutside
combustionairinletisprovided.
Thestructuralintegrityofthemobilehomeoor,ceiling,and
wallsmustbemaintained.Theappliancemustbeproperly
groundedtotheframeofthemobilehomeanduseonlylisted
pelletvent,Class“PL”connectorpipe.
A Harman® Outside Air Kit must be installed in a mobile
home installation.
Note: This installation must conform with local codes.
Intheabsenceoflocalcodesyoumustcomplywiththe
ASTM E1509-2012, ULC S628-93, (UM) 84-HUD
* Weighted average LHV eciency using data collected
duringEPAemissionstest.
**Weighted average HHV eciency using data collected
duringEPAemissionstest.
***ArangeofBTUoutputsbasedonHHVTestedEciency
andtheburnratesfromthelowandhighEPAtests.
****Basedonthemaximumfeedrateperhourmultipliedby
approximately8600BTU’swhichistheaverageBTU’sfrom
apoundofpellets.
E. Electrical Codes
115VAC,60Hz,Start3.5AMPS,Run2.5AMPS
D. BTU & Eciency Specications
Note: Hearth&HomeTechnologies,manufacturerofthis
appliance, reserves the right to alter its products, their
specicationsand/orpricewithoutnotice.
Harman® is a registered trademark of Hearth & Home
Technologies.
F. California
1 1 Product Specic and Important Safety Information
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED
HOME FLOOR, WALL, AND CEILING/ROOF MUST BE
MAINTAINED.
DO NOT INSTALL IN SLEEPING ROOM.
WARNING
!
Note: Somegeneratororbatteryback-upsystemsmay
not be compatible with the micro-processor electronics
on this appliance. Please consult the power supply
manufacturerforcompatiblesystems.
MODEL: Absolute63PelletStove
LABORATORY: OMNITestLaboratories,Inc
REPORT NO. 0135PS036S&0135PS036E
TYPE: PelletFueled/SupplementaryFor
ResidentialUse
STANDARD(s): ASTME2779-10,ASTME2515-11,
ASTME1509-12,ULC-S627-00,
EPAMethod28R
ELECTRICAL
RATING:
115VAC,60Hz,Start3.5Amps,
Run2.5Amps
GLASS
SPECIFICATION: 5mmmirroredceramicglass
EPA Certication Number: 54-16
EPA Certied Emissions: 1.4g/hr
*LHV Tested Eciency: 83.2%
**HHV Tested Eciency: 77.7%
***EPA BTU Output: 10,200-46,400
****BTU Input 14,100-61,800
Vent Size: 3Inch
Hopper Capacity: 72lbs
Fuel: WoodPellets
The Absolute63 is Certied to comply with
2020particulateemissionstandards.
This product and the fuels used to operate this product
(wood), and the products of combustion of such fuels,
can expose you to chemicals including lead and carbon
black, which is known to the State of California to cause
cancer,andcarbonmonoxide,whichisknowtotheStateof
Californiatocausebirthdefectsorotherreproductiveharm.
Formoreinformationgoto:www.P65Warnings.ca.gov
WARNING
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2353-90-999000I
A
.
Design and Installation Considerations
1. Appliance Location
Marginal Location:
• Below peak
Location NOT recommended:
• Not the highest point of the roof
• Wind loading possible
Multi-level Roofs
Windward
Leeward
Recommended:
Outside Air Intake
on windward side
NOT recommended:
Outside Air Intake
on leeward side
Recommended Location:
• Above peak
Recommended:
• Insulated exterior chase
in cooler climates
Recommended Location:
• Above peak
• Inside heated space
Location NOT recommended:
• Too close to tree
• Below adjacent structure
• Lower roof line
• Avoid outside wall
Marginal Location:
Wind loading possible
Figure 2.1
2 2 Getting Started
Sincepellet exhaustcancontainash,sootorsparks,you
mustconsiderthelocationof:
• Windows
• AirIntakes
Air Conditioner
• Overhang,sots,porchroofs,adjacentwalls
• Landscaping,vegetation
When locating vent and venting termination, vent above
rooflinewhenpossible.
• InstallationMUSTcomplywithlocal,regional,stateand
nationalcodesandregulations.
• Consult insurance carrier, local building inspector, re
ocialsorauthoritieshavingjurisdictionoverrestrictions,
installationinspectionandpermits.
Itisagoodideatoplanyourinstallationonpaper,usingexact
measurementsfor clearancesand oorprotection, before
actuallybeginningtheinstallation.
Considerationmustbegivento:
• Safety,convenienceandtracow.
• Placementofthechimneyandchimneyconnector.
• If you are not using an existing chimney, place the
appliance where there will be a clear passage for a
factory-builtlistedchimneythroughtheceilingandroof.
• Installing an optional outside air kit would aect the
locationoftheventtermination.
NOTE: Check building codes prior to installation.
NOTE: Locating the appliance in a location of considerable
air movement can cause intermittent smoke spillage from
appliance. Do not locate appliance near:
Frequently open doors
Central heat outlets or returns
WARNING
!
Risk of Fire!
Damaged parts could impair safe operation.
Do NOT install damaged, incomplete or
substitute components.
Installationandserviceofthisapplianceshouldbeperformedby
qualiedpersonnel.Hearth&HomeTechnologiesrecommends
HHTFactoryTrainedorNFIcertiedprofessionals.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2363-90-999000I
•ReciprocatingSaw
•Hammer
•PhillipsScrewdriver
•TapeMeasure
•Level
•Non-CombustibleSealant
•Gloves
•SafetyGlasses
•ElectricDrill&Bits
May also need:
•VentSupportStraps
•VentingPaint
B. Tools And Supplies Needed
Tools and building supplies normally required for
installation, unless installing into an existing masonry
replace:
C. Inspect Appliance and Components
• Carefullyremovetheapplianceandcomponentsfromthe
packaging.
• Report to your dealer any parts damaged in shipment,
particularlytheconditionoftheglass.
Read all of the instructions before starting the
installation. Follow these instructions carefully during
the installation to ensure maximum safety and benet.
DO NOT:
Install or operate a damaged appliance.
Modify appliance.
Install other than as instructed by Hearth & Home
Technologies.
Operate the appliance without fully assembling all
components.
• Overre.
Install any component not approved by Hearth &
Home Technologies.
Install parts or components not Listed or approved.
Disable safety switches.
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage.
Forassistanceoradditionalinformation,consultaqualied
installer, service agency or your dealer.
Hearth&HomeTechnologiesdisclaimsanyresponsibility
for,andthewarrantywillbevoidedbythefollowingactions:
• Installationanduseofanydamagedapplianceorvent
systemcomponent.
• Modicationoftheapplianceorventsystem.
• InstallationotherthanasinstructedbyHearth&Home
Technologies.
Installation and/or use of any component part not
approvedbyHearth&HomeTechnologies.
Any such action may cause a re hazard.
WARNING
!
Risk of Fire, Explosion or Electric Shock! DO NOT use
this appliance if any part has been under water. Call a
qualied service technician to inspect the appliance
and to replace any part of the control system which
has been under water.
WARNING
!
RISK OF FIRE OR EXPLOSION!
DAMAGED PARTS COULD IMPAIR
SAFE OPERATION. DO NOT install
damaged, incomplete or substitute
components. Keep appliance dry.
Thiswoodheaterhasamanufacturer-setminimumlowburn
ratethatmustnotbealtered.Itisagainstfederalregulations
toalterthis settingor otherwiseoperate thiswood heater
inamannerinconsistentwithoperatinginstructionsinthis
manual.
Thiswoodheaterneedsperiodicinspectionandrepairfor
properoperation.Itisagainstfederalregulationstooperate
this wood heater in a manner inconsistent with operating
instructionsinthismanual.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2373-90-999000I
3 3 Clearances
Figure 3.1
A. Appliance Dimension Diagram
Dimensionsareactualappliancedimensions.Useforreferenceonly.
7-15/16”
32-9/16”
29-9/16”
1”
1-1/4”
5-5/8”
12-1/2”
27-5/8”
28-1/16”
OutsideAir
Intake
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2383-90-999000I
NOTICE
Clearancesmayonlybereducedbymeansapprovedby
theregulatoryauthorityhavingjurisdiction.
Duetohightemperatures,thestoveshouldbeplacedaway
fromtrac,furnitureanddraperies.
Childrenandadultsshouldbealertedtothehazardsof
highsurfacetemperaturesandshouldstayawaytoavoid
burnstoskinand/orclothing.
Youngchildrenshouldbecarefullysupervisedwhenthey
areinthesameroomasthestove.
Clothing and other ammable materials should not be
placedonornearthisunit.
Figure 3.2
2" (51mm)
6" (450mm)
6" (152mm)
CAUTION
!
THIS APPLIANCE MUST BE VENTED TO THE OUTSIDE.
WARNING
!
RISK OF FIRE OR BURNS! Provide adequate
clearance around air openings and for service
access. Due to high temperatures, the appliance should
be located out of trac and away from furniture and
draperies.
Illustrations reect typical installations and are FOR
DESIGN PURPOSES ONLY. Actual installation may vary
due to individual design preference.
Placethestoveawayfromcombustiblewallsatleastasfar
asshowninFigure3.2.
Notethattheclearancesshownareminimumforsafetybutdo
notleavemuchroomforaccesswhencleaningorservicing.
Pleasetakethisintoaccountwhenplacingthestove.
When installing the unit into an alcove it is important to
considertherequiredclearanceslistedbelow.
6.25”
(159mm)
6.25”
(159mm)
B. Non-Combustible Materials Specication
Materialwhichwillnotigniteandburn.Suchmaterialsare
thoseconsistingentirelyofsteel,iron,brick,tile,concrete,
slate,glassorplasters,oranycombinationthereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in
a Vertical Tube Furnace at 750° C and UL763 shall be
considerednon-combustiblematerials.
C. Combustible Materials Specication
Materials made of or surfaced with wood, compressed
paper,plantbers,plastics,orothermaterialthatcanignite
andburn,whetherameproofedornot,orplasteredorun-
plasteredshallbeconsideredcombustiblematerials.
D. Clearances to Combustibles
Whenselectingalocationfortheapplianceitisimportantto
considertherequiredclearancestowalls(seeFigure3.2).
Note: Top of unit must be a minimum of 12” (305mm) to
ceiling
48” High
40-1/16” Wide
Min. Height = 48”, Min. Width = 40-1/16”, Max. Depth = 24”
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2393-90-999000I
E. Floor Protection Floor Protection
Requirements US Canada
JSides 6" 152mm
KFront 6” 152mm
LRear 0” 0mm
Corner Installation:
Minimumsizeoorprotectionforacornerinstallationhearth
padis28-1/2”WideBy29-1/2”Deep(724mmX749mm).
Note: Floor protector WILL NOT touch the wall using
minimum clearances.
If corner oor protection is desired to touch the wall, the
oorprotectionwillneedtobeatleast42-5/16”x42-5/16”
(1075mm x 1075mm). Note: This will allow the floor
protection to touch the wall as shown. Figure 3.4.
Alternateoorprotectordimensionmaybeusedaslongas
theysatisfythemeasurementrequirements.
Figure 3.4
FloorProtector
Install fasteners here.
Figure 3.5
F. Mobile Home Installation
Wheninstallingthisunitinamobilehome,severalrequirements
mustbefollowed:
1. Theunitmustbeboltedtotheoor.Thiscanbedoneusing
anappropriatefastenerfortheapplication.
2. The unit must be connected to an outside combustion
air inlet. Proper supports and spark arresters must be
considered when installing venting. See “Termination
LocationandVentInformation”SectionD.
3. Floorprotectionandclearancesmustbefollowedasshown.
4. Theappliancemustbeproperlygroundedtotheframeof
themobilehomeusingaminimumof8AWGcoppersolid
orstranded,insulatedorbarewireorequivalent.
Figure 3.3
JK
Floor
Protector
L
Door Opening
Parallel Installation:
Place the stove on a noncombustible oor or oor protector
thatextendsaminimumof6inches(152mm)tothefrontofthe
loaddooropening,6inches(152mm)tothesidesofthedoor
opening,and0inchestotherear.
Note: There is no required oor protection from the rear
of the unit. The oor protection should be ush with the
rear most edge of the unit, but does not need to extend
any further.
Theminimumoorprotectormaterialis20gaugesheetmetal.
Otheroorprotectormaterialsareceramictile,stone,brick,etc.
MinimumSizeoorprotectionis28-1/2”WideBy29-1/2”Deep
(724mmX749mm).Figure3.3.
Alternate oor protector dimension may be used as long as
they satisfy the measurement requirements shown below.
Venting:
US- FollowPL vent manufacturersrecommendations when
conguringventpipeinstallation.
Canada - Must extend 2” (51mm) beyond each side of any
horizontaluepipe.
CAUTION
HearthandHomeTechnologiesdoesnotrecommendadhesive
based vinyl ooring due to thermal expansion. Floating-style
ooring(LVP-luxuryvinylplankorLVT–luxuryvinyltile)canbe
used,butitwillreachtemperaturesupto110°Finaroomwith
ambienttemperatureof70°F.Consultooringspecicationsto
ensurecompatibility.
HHTrecommendswoodstovesandinsertshave29inchesof
alternativeooringinfrontofthestovebeforeusingLVP/LVT
regardless if they sit ush on the oor or are elevated on a
raisedhearth.
Forallotherooring,continuetofollowclearancetocombustible
requirementsintheinstallationmanual.
NOTICE: Clearances that do not meet the minimum guidelines
couldresultindamageorbucklingtothevinylooringandis
done at the installer’s risk.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2310 3-90-999000I
4 4 Termination Location and Vent Information
A. Vent Termination Minimum Clearances
Figure 4.1
Figure 4.2
Note: Followventingmanufacturer’srecommendationsfor
sealingpipejoints.
#1 Preferred method (Figure 4.1)
Thismethodprovidesexcellentventingfornormaloperation
andallowsthestovetobeinstalledclosesttothewall.Two
inches from the wall is safe; however, four inches allows
betteraccesstoremovetherearpanel.Theverticalportionof
theventshouldbethreetovefeethigh.Thisverticalsection
willhelpprovidenaturaldraftintheeventofapowerfailure.
Note: Do not place joints within wall pass-through.
THE CHIMNEY MUST BE OF A TYPE SUITABLE FOR
SOLID-FUEL BURNING.
#2 Preferred method (Figure 4.2)
This method also provides excellent venting for normal
operationbutrequiresthestovetobeinstalledfartherfrom
thewall.Theverticalportionoftheventshouldbethreeto
vefeethighandatleast1”fromacombustiblewall.This
vertical section will provide natural draft in the event of a
powerfailure.
If the stove is installed below grade be sure the vent
termination is at least 12" above grade (with outside air
only). The outlet must also be 12” from the house/building.
Note: Do not place joints within wall pass-through.
CAUTION
!
Keep combustible materials (such as grass, leaves,
etc.) at least 3 feet away from the ue outlet on the
outside of the building.
3 Ft.
to
Combustibles
3 Ft.
to Combustibles
3 Ft.
to
Combustibles
3 Ft.
to Combustibles
DO NOT USE MAKESHIFT COMPROMISES WHEN
INSTALLING THIS APPLIANCE. DAMAGE AND/OR
INJURY MAY RESULT.
CAUTION
!
WARNING
!
THE CHIMNEY AND CONNECTOR MUST BE
MAINTAINED IN GOOD CONDITION AND KEPT CLEAN.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2311 3-90-999000I
Figure 4.3
Figure 4.4
#3 Installing into an existing chimney (Figure 4.3)
Thismethodprovidesexcellentventingfornormaloperation.
This method also provides natural draft in the event of a
powerfailure.Ifthechimneyconditionisquestionable*you
maywanttoinstallalinerasinmethod#6.
InsomeplacesintheUSandCanadaitisrequiredthatthe
ventpipeextendallthewaytothetopofthechimney.
*The chimney should be inspected and cleaned before
installingyourstove.Ifyoudiscoverthatthechimneydoes
nothaveaclaytilelinerorhascracksorakingofthetile
liner you will need to install a stainless steel liner within
thechimney.Inmostcasestheinsidediameterofthisliner
shouldbe4".Eitherexibleorrigidlinermaybeusedforthis
purpose.Refer to Method 5 & 6.
Besuretodesigntheventingsothatitcanbeeasilycleaned.
#4 Installing into an existing replace chimney (Figure 4.4)
Thismethodprovidesexcellentventingfornormaloperation.
This method also provides natural draft in the event of a
powerfailure.Ifthechimneyconditionisquestionable*you
maywanttoinstallalinerasinmethod#5.
InsomeplacesintheUSandCanadaitisrequiredthatthe
ventpipeextendallthewaytothetopofthechimney.
*The chimney should be inspected and cleaned before
installingyourstove.Ifyoudiscoverthatthechimneydoes
nothaveaclaytilelinerorhascracksorakingofthetile
liner you will need to install a stainless steel liner within
thechimney.Inmostcasestheinsidediameterofthisliner
shouldbe4".Eitherexibleorrigidlinermaybeusedforthis
purpose.Refer to Method 5 & 6.
The chimney should be sealed at the damper using a
steel plate. Kaowool, mineral wool or an equivalent non-
combustibleinsulationisrecommendedtobeinstalledontop
ofthesealingplatetoreducethepossibilityofcondensation.
The connector pipe should extend through the smoke
chambertothebaseorintotherstuetile.
Besuretodesigntheventingsothatitcanbeeasilycleaned.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2312 3-90-999000I
#5 Installing into an existing replace chimney (Figure
4.5) w/Full Liner
Thismethodprovidesexcellentventingfornormaloperation.
This method also provides natural draft in the event of a
powerfailure.
InsomeplacesintheUSandCanadaitisrequiredthatthe
ventpipeextendallthewaytothetopofthechimney.
Inthismethodacapshouldalsobeinstalledonthechimney
tokeepoutrain.Besuretouseapprovedpelletventpipe
ttings.Pipesizeshouldbeincreasedto4"usingthismethod.
Inthismethodacapshouldalsobeinstalledonthechimney
tokeepoutrain.
#6 Installing into an existing chimney (Figure 4.6) w/Full liner
Thismethodprovidesexcellentventingfornormaloperation.
This method also provides natural draft in the event of a
powerfailure.
InsomeplacesintheUSandCanadaitisrequiredthatthe
ventpipeextendallthewaytothetopofthechimney.The
pipeorlinerinsidethechimneyshouldbe4"diameter.
Inthismethodacapshouldalsobeinstalledonthechimney
tokeepoutrain.
Figure 4.5
Figure 4.6
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2313 3-90-999000I
#7 Installing through the ceiling (Figure 4.7)
FollowPLventmanufacturersrecommendationswhenusing
wallandceilingpassthrough.
Note: Do not place joints within wall pass-through.
Figure 4.7
Figure 4.8
12"
min. above ground level
Minimum ue vent conguration
It is recommended that outside
air be installed with this venting
conguration. Smoke spillage may
bepossibleduringapoweroutage.
PL vent manufacturer's
restop spacer and support.
1" MIN.
No insulation or other
combustible materials
are allowed within 3"
of the PL vent pipe.
ashing
storm collar
1" MIN.
1" MIN.
1” MIN.
12”
Min
12” Minimum
clearance to ceiling.
Figure 4.9
12"
min. wall to outlet
36"
min. clearance to any
combustible material
Areawithindottedcirclerepresentstheminimumclearanceto
combustiblematerialssuchasshrubbery,mulchortallgrasses.
DO NOT USE MAKESHIFT COMPROMISES WHEN
INSTALLING THIS APPLIANCE. DAMAGE AND/OR
INJURY MAY RESULT.
CAUTION
!
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2314 3-90-999000I
Optional Top Vent Pipe Clearances #8 Installing into an existing chimney using the Optional
Top Vent option. (Figure 4.10)
Thismethodprovidesexcellentventingfornormaloperation.
This method also provides natural draft in the event of a
powerfailure.Ifthechimneyconditionisquestionable*you
maywanttoinstallalinerasinmethod#6.
InsomeplacesintheUSandCanadaitisrequiredthatthe
ventpipeextendallthewaytothetopofthechimney.
*The chimney should be inspected and cleaned before
installingyourstove.Ifyoudiscoverthatthechimneydoes
nothaveaclaytilelinerorhascracksorakingofthetile
lineryouwillneedtoinstallastainlesssteellinerwithinthe
chimney.
Besuretodesigntheventingsothatitcanbeeasilycleaned.
4"/102mm from back of top
ue vent to wall
Minimum 6” (25mm)
from top of pipe to ceiling
6"/152mm from
pipe to wall
View of Top Vent Option Installed
Figure 4.10
Singlewall6”
Chimneyconnector
Chimney Connectors
Follow venting manufacturer’s recommendations for
sealingpipejoints.
Figure 4.11
33-1/2”
Measurementfromoortothebeginningofthe6”ventcollar.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2315 3-90-999000I
B. Chimney Diagram
V=Vent Terminal A=Air Supply Inlet =Area where termination is not permitted
Door
Sidewalk
Fixed
Closed
Openable
Openable Fixed
Closed
Inside Corner
Detail
Porch or
Openable
Deck
or Fixed
Requirements for Terminating the Venting
Figure 4.12
I. The clearance to service regulator vent outlet must be a
minimumof6feet.
J. Theclearancetoanon-mechanicalairsupplyinlet to the
buildingorthecombustionairinlettoanyotherappliance
mustbeaminimumof48”.
K. Theclearance toamechanicalairsupplyinletmustbea
minimumof10feet. (with outside air installed, 6 feet)
L. Theclearanceaboveapavedsidewalkorapaveddriveway
locatedonpublicpropertymustbeaminimumof7feet.
M. Theclearanceunderaveranda,porch,deckorbalconymust
beaminimumof12inches. (B. also)
The clearance to vegetation and other exterior combustibles
such as mulch is 36” as measured from the center of the
outlet or cap. This 36” radius continues to grade.
CertainCanadianandorLocalcodesorregulationsmayrequire
dierentclearances.
Aventshallnotterminatedirectlyaboveaside-walkorpaved
drivewaywhichislocatedbetweentwosinglefamilydwellings
andservesbothdwellings.
Onlypermittedifveranda,porch,deck,orbalconyisfullyopen
onaminimumof2sidesbeneaththeoor.
See NFPA 211 for more installation clearance reductions
when using outside air.
Where passage through a wall, or partition of combustible
construction is desired, the installation shall conform to
CAN/CSA-B365. (if in Canada)
WARNING
!
Venting terminals must not be recessed into a wall
or siding.
Only PL vent pipe wall pass-through and re stops should
be used when venting through combustible materials.
Always take into consideration the eect the prevailing wind
direction or other wind currents will cause with yash and
/or smoke when placing the termination.
In addition, the following must be observed:
A. Theclearanceabovegrademustbeaminimumof12”.
B. Theclearancetoawindowordoorthatmaybeopenedmust
beaminimumof48”totheside,48”belowthewindow/door,
12”abovethewindow/door. (with outside air installed, 12”
to side and below)
C. A 12” clearance to a permanently closed window is
recommendedtopreventcondensationonthewindow.
D. Theverticalclearancetoaventilatedsotlocatedabovethe
terminalwithinahorizontaldistanceof2feet(60cm)from
thecenter-lineoftheterminalmustbeaminimumof18”.
E. Theclearancetoanunventilatedsotmustbeaminimum
of12”.
F. Theclearancetoanoutsidecorneris11”fromcenterofpipe.
G. Theclearancetoaninsidecorneris12”.
H. Aventmustnotbeinstalledwithin3feet(90cm)abovea
gas meter/regulator assembly when measured from the
horizontalcenter-lineoftheregulator.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2316 3-90-999000I
C. Venting & Use of Elbows
Figure 4.13
=Positivestaticpressure
=Negativestaticpressure
+
-
+
+
-
Harmanpelletstovesdependonacombustionfantopullair
throughtheunitforcombustion.Theventingsystemrestricts
theabilityofthecombustionfantomovetherequiredamount
ofairthroughtheunit.Asystemwithtoomuchresistance
willresultinincompletecombustion,morefrequentrequired
cleaning and poor unit performance. It is always best to
choosealocationfortheappliancethatwillresultinaventing
systemwiththeshortestequivalentventlength(EVL).
ItisbesttohaveyourventingsystemdesignedbyaHarman
authorizeddealerbefore younalize yourpurchase ofan
appliance.
Equivalent Vent Length: The equivalent vent length for
common pellet vent components are:
•90°ElbowsorTee:5EVLUnits
•45°elbow:3EVLUnits
•VerticalPipeorLiner:½EVLUnit
•HorizontalPipeorliner:1EVLUnit
The total allowable equivalent vent length is:
•20EVLfor3”pelletventpipeorliner.
•30EVLfor4”pelletventpipeorliner.
Dueto the potentialfor yash accumulationin horizontal
ventingsections,themaximumpermissiblehorizontalventing
lengthis:
•4ft.for3”&4”pelletventpipe.
Example: First Floor Installation
Aunitistobeinstalledusing3”PelletVentPipewith3
feetofhorizontalpipe,aTee,10feetofverticalpipe,a
90°elbowandaterminationcap.
The equivalent vent length is:
3ft.ofHorizontalPipe(1x3EVL) =3EVL
90°ElboworTee(1xEVL)  =5EVL
10ft.ofVerticalPipe(10x.5EVL) =5EVL
90°ElboworTee(1xEVL)  =5EVL
TerminationCap   =0EVL
EquivalentVentLength   =18EVL
Intheexamplesystemdetailedabove,theEVLwas18
whichislessthanthemaximumof20EVLfor3”pellet
ventpipe,thusthisisasatisfactoryventingconguration.
Example: Connection to Masonry Chimney
Aunitistobeinstalledusing3”PelletVentPipewith2
feetofhorizontalpipe,aTee,4feetofverticalpipe,an
elbow,aTee,21feetofverticalliner,andatermination
cap.
The equivalent vent length is:
2ft.ofHorizontalPipe(1x2EVL) =2EVL
90°Tee(1x5EVL)   =5EVL
4ft.ofVerticalPipe(4x.5EVL) =2EVL
90°Elbow(1x5EVL)   =5EVL
90°Tee(1x5EVL)   =5EVL
21ft.ofVerticalLiner(21x.5EVL) =10.5EVL
TerminationCap   =0EVL
EquivalentVentLength   =29.5EVL
In the example system detailed above, the EVL was
29.5whichexceedsthemaximumof20ft.for3”pellet
ventpipe, thus 3”ventpipe shouldnot beusedin this
installation.However,since4”pipecansupportanEVL
upto30,theuseof4”pipewouldcreateasatisfactory
installation.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2317 3-90-999000I
C. Venting & Use of Elbows continued
Note:Whentheamountofverticalpelletventpipeinthesystemexceeds15feet,4”pelletventpipeshouldbeused.
Note:EquivalentVentingLengthdecreasesasaltitudeincreases.
Example:
AunitwithanEVLof13,istobeinstalledatanaltitude
of3,000feetabovesealevel.
Fromthe chartto the left,at 3,000feet of altitude,the
maximum permissible equivalent venting length is 26
feet.
However,ifthesameunit(EVL13)wastobeinstalled
analtitudeof9,000feetabovesealevel,theinstallation
wouldnolongerbeacceptableandtheequivalentvent
lengthofthepipewouldhavetobereducedforproper
unitoperation.
0 Ft5 Ft 5 Ft
10,000
9,000
8,000
7,000
6,000
5,000
4,000
3,000
5 Ft
0 Ft
10 Ft
Comb. Blower at max at
changover line.
Altitude
10 Ft
15 Ft
20 Ft
25 Ft
30 Ft
5 Ft
0 Ft
15 Ft
Equivalent Vent Length (EVL)
Maximum Horizontal Run
• LongrunsofexorPLventpipeinstalleddirectlyverticalfromtheuestubmayrequiremorefrequentcleaningdueto
yashfallingoinsideandcollectingdirectlyabovethecombustionbloweroutlet.
• 4" stainless steel ex vent piping is only allowed for use in masonry replaces and chimneys or factory built wood-
burningreplaceswithClassAmetalchimneys.
• Allpelletventpipemustbesecuredtogethereitherbymeansprovidedbythepipemanufacturerorby3screwsateach
joint.
• Useonlythespeciedventingcomponents.Useofanyothercomponentswillvoidtheproductwarrantyandmaypose
ahazard.
• DoNotInstallaFlueDamperInTheExhaustVentingSystemofThisAppliance.
• DONOTCONNECTTHISUNITTOACHIMNEYFLUESERVINGANOTHERAPPLIANCE.
• SimpsonDuraVentPelletVentProHarman®AdapterPart#3PVP-ADHBandPelletVentProHarman®AdapterIncreaser
Part#3PVPX4ADHBarehighlyrecommendedtobeinstalledonthestartercollartoinsureaproperpipeconnectionto
theunit.
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.
• Usesiliconetocreateaneectivevaporbarrieratthelocationwherethechimneyoroutsideairductingpassesthrough
totheexteriorofthestructure.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2318 3-90-999000I
Outside Air:
Hearth & Home Technologies recommend attaching
outside air in all installations, especially lower level and
main oor locations.
Pernationalbuildingcodes,considerationmustbegivento
combustionairsupplytoallcombustionappliances.Failure
tosupplyadequatecombustionairforallappliancedemands,
mayleadtoback-draftingofthoseandotherappliances.
Whentheapplianceisside-wallvented:Theairintakeisbest
locatedonthesameexteriorwallastheexhaustventoutlet
andlocatedloweronthewallthantheexhaustventoutlet.
When the appliance is roof vented: The air intake is best
locatedontheexteriorwallorientedtowardstheprevailing
winddirectionduringtheheatingseason.
Theoutsideairconnectionwillsupplythedemandsofthe
pellet appliance, but consideration must be given to the
totalhousedemand. Housedemand mayconsume some
airneededforthestove,especiallyduringapowerfailure.It
maybenecessarytoaddadditionalventilationtothespacein
whichthepelletapplianceislocated.Consultwithyourlocal
HVACprofessionaltodeterminetheventilationdemandsfor
yourhouse.
Toinstalloutsideairuse3"non-combustibleexpipe.There
isabreak-away holeon therear paneloftheAbsolute63
stovewhichmustberemovedbeforeconnectingtheexpipe,
Figure4.14.Thepipeshouldberunoutsideandterminateto
thesideorbelowtheventpipeoutletsotheueoutletismore
than12"fromtheinletcover.TheTerminationCapshouldbe
usedtokeepbirds,rodents,etc.outofthepipe,Figure4.15.
YoumaychoosetousetheoptionalDirectVentWallPass-
throughKitwhichincorporatestheventingpass-throughand
outsideairinletintoonecomponent,Figure4.16.
D. Outside Air
Direct Vent Wall Pass-through Kit
Part#1-00-677177
Figure 4.16
Termination Cap
Part#1-10-09542
Figure 4.15
Outsideairex
pipegoeshere.
Figure 4.14
Removeknockout
toinstalloutsideair.
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2319 3-90-999000I
E. Locating Your Appliance & Chimney
Locationoftheapplianceandchimneywillaectperformance.
• Installthroughthewarmairspaceenclosedbythebuilding
envelope.Thishelps toproducemoredraft,especially
duringlightinganddie-downofthere.
• Penetratethehighestpartoftheroof.Thisminimizesthe
eectsofwindloading.
Locate termination cap away from trees, adjacent
structures,unevenrooflinesandotherobstructions.
• Minimizetheuseofchimneyosets.
• Considertheappliancelocationrelativetooorandceiling
andatticjoists.
G. Negative Pressure
F. Draft
Draftisthepressuredierenceneededtoventappliances
successfully.Whenanapplianceisdraftingsuccessfully,all
combustion byproducts are exiting the home through the
chimney.
Considerationsforsuccessfuldraftinclude:
• Negativepressureintherebox
• Locationofapplianceandchimney
Tomeasurethedraftornegativepressureinyourappliance
use a magnahelic or a digital pressure gauge capable of
reading0-1inchesofwatercolumn(W.C.).
The appliance should be running on high for at least 15
minutesforthetest.
Withthestoverunningonhighyoushouldhaveanegative
pressureequaltoorgreaterthanthenumbergiveninthe
chartbelow.Ifyouhavealowerreadingthanyoundonthe
chart,yourappliancedoesnothaveadequatedrafttoburn
thefuelproperly.
Minimum Vacuum Requirements: .20
Priortoinstallingtheuepipe,connectadraftmeter.(The
draftmetermusthaveaminimumrangeof0-.5”)Recordthe
rstreading.Connectuepipetostoveandbesurealldoors
andwindowsinthehomeareclosed.Recordtheseconddraft
reading_______.Ifthesecondreading is more than.05”
lowerthantherstreading,checkforpossiblerestrictions
ortheneedforoutsideair.Formoreinformationonthedraft
testprocedure,refer to “Appliance Set-Up” Section C.
• DONOTCONNECTTHISUNITTOACHIMNEYFLUE
SERVICINGANOTHERAPPLIANCE.
• DO NOT CONNECT TOANYAIR DISTRIBUTION
DUCTORSYSTEM.
Mayallowuegasestoenterthehouse.
CAUTION
!
Negativepressureresultsfromtheimbalanceofairavailable
fortheappliancetooperateproperly.Itcanbestrongestin
lowerlevelsofthehouse.
Causesinclude:
• Exhaustfans(kitchen,bath,etc.).
• Rangehoods.
• Combustionairrequirementsforfurnaces,waterheaters
andothercombustionappliances.
• Clothesdryers.
• Locationofreturn-airventstofurnaceorairconditioning.
• ImbalancesoftheHVACairhandlingsystem.
• Upperlevelairleakssuchas:
- Recessedlighting
- Attichatch
- Ductleaks
Tominimizetheeectsofnegativeairpressure:
• Installtheoutsideairkitwiththeintakefacingprevailing
windsduringtheheatingseason.
• Ensureadequateoutdoorairforallcombustionappliances
andexhaustequipment.
• Ensurefurnaceandairconditioningreturnventsarenot
locatedintheimmediatevicinityoftheappliance.
• Avoidinstallingthe applianceneardoors,walkwaysor
smallisolatedspaces.
• Recessedlightingshouldbea“sealedcan”design.
• Attichatchesweatherstrippedorsealed.
• Atticmountedductworkandairhandlerjointsandseams
tapedorsealed.
Risk of Asphyxiation! Negative pressure can cause
spillageofcombustionfumesandsoot.
WARNING
!
NOTICE
Hearth&HomeTechnologiesassumesnoresponsibility
for the improper performance of the chimney system
causedby:
• Inadequatedraftduetoenvironmentalconditions
• Downdrafts
• Tightsealingconstructionofthestructure
• Mechanicalexhaustingdevices
Harman® • Absolute63 Installation Manual_R17 • 2016 - ___ • 08/2320 3-90-999000I
H. Avoiding Smoke and Odors
Negative Pressure, Shut-down, and Power Failure:
To reduce the probability of back-drafting or burn-back in
the pellet burning appliance during power failure or shut-
down conditions, the stove must be able to draft naturally
withoutexhaustbloweroperation.Negativepressureinthe
housewillresistthisnaturaldraftifnotaccountedforinthe
pelletapplianceinstallation.
Heatrisesinthehouseandleaksoutatupperlevels.This
airmustbereplacedwithcoldairfromoutdoors,whichows
into lower levels of the house. Vents and chimneys into
basementsandlowerlevelsofthehousecanbecomethe
conduitforairsupply,andreverseundertheseconditions.
Outside Air
Anoutsideairkit is recommendedin all installations.The
OutsideAirKitmustbeorderedseparately.
Pernationalbuildingcodes,considerationmustbegivento
combustionairsupplytoallcombustionappliances.Failure
tosupplyadequatecombustionairforallappliancedemands
mayleadtobackdraftingofthoseandotherappliances.
• Whentheapplianceisroofvented(stronglyrecommended):
The air intake is best located on the exterior wall
oriented towards the prevailing wind direction during
theheatingseason.
• Whentheapplianceisside-wallvented:
Theairintakeisbestlocatedonthesameexteriorwall
as the exhaust vent outlet and located lower on the
wallthantheexhaustventoutlet.
Theoutsideairsupplykitcansupplymostofthedemands
ofthepelletappliance,butconsiderationmustbegivento
thetotalhousedemand.
House demand may consume the air needed for the
appliance.Itmaybenecessarytoaddadditionalventilation
tothespaceinwhichthepelletapplianceislocated.
ConsultwithyourlocalHVACprofessionaltodeterminethe
ventilationdemandsforyourhouse.
Vent Pipe
Besure touseapproved pelletvent pipe walland ceiling
pass-throughttingstogothroughcombustiblewallsand
ceilings.Besuretouseastartingcollartoattachtheventing
systemtothestove.Thestartingcollarmustbesecuredto
theuestubwithatleastthreescrews,andsealedwithhigh
tempsiliconecaulking.
4” stainless steel ex vent piping is only allowed for use
inmasonryreplacesandchimneysorfactorybuiltwood-
burningreplaceswithclassAmetalchimneys.
Pelletventpipeisconstructedoftwolayerswithairspace
betweenthelayers.Thisairspaceactsasaninsulatorand
reducestheoutsidesurfacetemperaturetoallowaclearance
to combustibles of only 1 inch. The sections of pipe lock
togethertoformanairtightsealinmostcases;however,in
somecasesaperfectsealisnotachieved.Forthisreason
and the fact that theAbsolute63 operates with a positive
ventpressure,wespecifythatthejointsalsobesealedwith
siliconeoraluminumtapeinadditiontothesealingsystem
usedbythemanufacturer.
Wherepassingthroughanexteriorwallorroof,usesilicone
tomaintainaneectivevaporbarrieratthelocationwhere
thechimneyorcomponentpenetratestotheexteriorofthe
structure.
Vent Congurations:
To reduce probability of reverse drafting during shut-
down conditions, Hearth & Home Technologies strongly
recommends:
• Installingthepelletventwithaminimumverticalrunof
vefeet.
• Installingoutsideair.
Topreventsootdamagetoexteriorwallsofthehouseand
topreventre-entryofsootorashintothehouse:
• Maintainspeciedclearancestowindows,doors,andair
inlets,includingairconditioners.
• Ventsshouldnotbeplacedbelowventilatedsots.Run
theventabovetheroof.
• Avoidventingintoalcovelocations.
• Ventsshouldnot terminateunder overhangs, decksor
ontocoveredporches.
Maintain minimum clearance of 12 inches from the
ventterminationtotheexteriorwall.Ifyouseedeposits
developing on the wall, you may need to extend this
distancetoaccommodateyourinstallationconditions.
Hearth & Home Technologies assumes no responsibility
for, nor does the warranty extend to, smoke damage
caused by reverse drafting of pellet appliances under
shut-down or power failure conditions.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26