Fläkt Woods 8419 GB 2009.03 4 Specifications are subject of alteration without further notice.
ECONET® MANUAL
A ALARMS
1. Ice alarm, GT 42
1.a. What ?
Low liquid temperature (GT 42) after the exhaust air
coil. Risk of destroying the heat / cooling exchangers,
set value for temperature alarm, standard +2 °C.
1.b. Analysis
SV 40: BY PASS VALVE
• SV40closed,Heatrecoverysignal100%(10V)
– ok
• SV40open
– error in valve or cabling
– heat recovery signal 0 - 30%
– cooling sequence
– manual position of valve, shall be in automatic
position.
GF 10, 20: AIR FLOW
• Exhaustair,GF20<<supplyair,GF10
• Exhaustair,GF20<<ofdimensioned.
EXHAUST AIR COIL
• Frostformationontheexhaustaircoil.
GT 20: EXHAUST AIR TEMPERATURE
• Exhaustairtemperature,GT20<<ofdimensioned.
GP 41: LIQUID FLOW
• Liquidflow>1/3ofsupplyairflow?
– ok
• Otherwise,ECONETdoesnotincreasetheliquidflow
due to the risk of ice formation
– check the parameters
– check the frequency inverter, shall be in auto-
matic position.
WHEN AT STATE NOT RUNNING
• When continuous Ice alarm the supplementary
heating valve has to open during ‘state not running’,
setvalueforopeningSV30(heatingvalve)forexample
GT 42 = +10 °C, look at ECONET functional descrip-
tion.
WHEN AT STATE START UP
• StartsequenseforAHU,firststartECONETandexhaust
air unit, after some minutes start supply air unit.
OTHER ALARMS
• HastherebeenanotheralarmbeforeIcealarm?
A ALARMS
2. Frost alarm, GT 41
2.a. What ?
Low liquid temperature (GT 41) after the supply air coil.
Risk of frost formation in the exhaust air coil, set value
for temperature alarm, standard -10 °C.
2.b. Analysis
GT 10: SUPPLY AIR TEMPERATURE
• Setvalue=actualvalueGT10
– ok
• Setvalue>actualvalueGT10andSV30inposition
100%
– reduced supplementary heating power
–toolowheatingtemperatureatSV30
– recovered heat from the exhaust air too low
GP 41: LIQUID FLOW
• Liquidflow>1/3ofsupplyairflow?
– ok
• GT40>GT10+6°C
– ECONET does not increase the liquid flow due
to the risk of frost formation
– check the parameters
GT 00 OUT DOOR AIR TEMPERATURE
• Outdoorair,GT00lowerthandimensioningcircum-
stances.
WHEN AT STATE START UP
• StartsequenseforAHU,firststartECONETand
exhaust air unit, after some minutes start supply air
unit.
• No or too slow availability of supplementary
heating.
OTHER ALARM
• HastherebeenanotheralarmbeforeFrostAlarm?
ECONET® Fault and error manual