TFT Display & Buttons
There are TFT screen and 4 buttons on the cover, they are SET, ▲, ▼, and .
Power: used to turn on/off the transmitter/controller by each pressing. Under turning off station, OFF
displays on the right bottom corner, and under this station, all outputs are ineffective.
TFT display: CO2, temperature and humidity measuring value display on first line, second line and bottom line
respectively. If the output is linear, when customer press any key among SET, ▲, and ▼, it will display “Linear”
to indicate, the keys are in-effective, see below Fig. 3. TFT 3-color screen is controlled by CO2 measuring value,
with below default setpoint. End user can adjust the setpoint via Advanced Setup parameter P8 & P9.
│ Green: CO2 < 800ppm │ Yellow: 800ppm ≤ CO2 < 1200ppm │ Red: CO2 ≥ 1200ppm │
SET button: be used to switch parameter items and PID/relay set points. The parameter item switches to next by
each pressing, and will switch quickly by continuous pressing.
▲ & ▼: be used to adjust the setpoint/target value. The setpoint/target value only changes one by each pressing,
and will switch quickly by continuous pressing.
Lock/Unlock the buttons: Please refer to Advanced Parameter P72.
Table 1 - DIPs setting
DIPs Setting
End user can enter Advanced Setup by adjusting DIP1=ON and return to normal suing by adjusting DIP1=OFF.
DIP2 is used to adjust analog 3, when DIP2= ON, analog 3 is for TVOC, when DIP2=OFF, analog is for RH. See
above Table1.
Analog Output Setting
The default analog output is PID before leaving factory, unless otherwise stated by customers. End user can reset the
analog output as linear by Advanced Setup P20 according to below table 2. Voltage output or current output can be
selected by connecting/disconnecting the jumpers, as shown on table 3 and Fig 4. End user also may get 2~10V or
4~20mA by adjusting parameters P22, P24, P26, P28, P30, P32, P34, P36 in Advanced Setup.
Table 2 – Analog linear/PID output instruction