H3C SR6616 Installation guide

  • Hello! I am an AI chatbot trained to assist you with the H3C SR6616 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
H3C SR6616 Router
Installation Guide
Hangzhou H3C Technologies Co., Ltd.
http://www.h3c.com
Document version:
6W110-20160229
Copyright © 2009-2016, Hangzhou H3C Technologies Co., Ltd. and its licensors
All rights reserved
No part of this manual may be reproduced or transmitted in any form or by any means without prior written
consent of Hangzhou H3C Technologies Co., Ltd.
Trademarks
H3C, , H3CS, H3CIE, H3CNE, Aolynk, , H
3
Care, , IRF, NetPilot, Netflow, SecEngine,
SecPath, SecCenter, SecBlade, Comware, ITCMM and HUASAN are trademarks of Hangzhou H3C
Technologies Co., Ltd.
All other trademarks that may be mentioned in this manual are the property of their respective owners
Notice
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute the warranty of any kind, express or implied.
Environmental protection
This product has been designed to comply with the environmental protection requirements. The storage, use,
and disposal of this product must meet the applicable national laws and regulations.
Preface
The H3C SR6616 Router Installation Guide includes eight chapters, which describe the hardware
features of the H3C SR6616 Router and provide examples to help you install the router.
This preface includes:
Audience.
Conventions.
About the H3C SR6616 documentation set.
Obtaining documentation.
Technical support.
Documentation feedback.
Audience
This documentation is intended for:
Network planners.
Field technical support and servicing engineers.
Network administrators working with the SR6616 routers.
Conventions
This section describes the conventions used in the documentation.
Port numbering in examples
The port numbers in the documentation are for illustration only and might be unavailable on your
device.
Command conventions
Convention Description
Boldface Bold
text represents commands and keywords that you enter literally as shown.
Italic
Italic text represents arguments that you replace with actual values.
[ ] Square brackets enclose syntax choices (keywords or arguments) that are optional.
{ x | y | ... }
Braces enclose a set of required syntax choices separated by vertical bars, from which
you select one.
[ x | y | ... ]
Square brackets enclose a set of optional syntax choices separated by vertical bars,
from which you select one or none.
{ x | y | ... } *
Asterisk marked braces enclose a set of required syntax choices separated by vertical
bars, from which you select at least one.
[ x | y | ... ] *
Asterisk marked square brackets enclose optional syntax choices separated by vertical
bars, from which you select one choice, multiple choices, or none.
&<1-n>
The argument or keyword and argument combination before the ampersand (&) sign
can be entered 1 to n times.
# A line that starts with a pound (#) sign is comments.
GUI conventions
Convention Description
Boldface
Window names, button names, field names, and menu items are in Boldface. For
example, the
New User
window appears; click
OK
.
>
Multi-level menus are separated by angle brackets. For example,
File
>
Create
>
Folder
.
Symbols
Convention Description
WARNING!
An alert that calls attention to important information that if not understood or followed
can result in personal injury.
CAUTION:
An alert that calls attention to important information that if not understood or followed
can result in data loss, data corruption, or damage to hardware or software.
IMPORTANT:
An alert that calls attention to essential information.
NOTE:
An alert that contains additional or supplementary information.
TIP:
An alert that provides helpful information.
Network topology icons
Convention Description
Represents a generic network device, such as a router, switch, or firewall.
Represents a routing-capable device, such as a router or Layer 3 switch.
Represents a generic switch, such as a Layer 2 or Layer 3 switch, or a router that
supports Layer 2 forwarding and other Layer 2 features.
Represents a security card, such as a firewall, load balancing, NetStream, SSL VPN,
IPS, or ACG card.
About the H3C SR6616 documentation set
The H3C SR6616 documentation set includes the following categories of documents:
Category Documents Purposes
Product description and
specifications
Marketing brochures Describe product specifications and benefits.
Technology white papers
Provide an in-depth description of software
features and technologies.
Category Documents Purposes
Hardware specifications
and installation
Compliance and safety
manual
Provides regulatory information and the safety
instructions that must be followed during
installation.
Quick start
Guides you through initial installation and setup
procedures to help you quickly set up and use your
device with the minimum configuration.
Installation guide
Provides a complete guide to hardware installation
and hardware specifications.
Interface Module Guide
Describe Interface Module specifications, features,
and standards.
H3C Transceiver
Modules User Guide
Describes transceiver modules available for the
H3C high-end network products, their external
views, and specifications.
Power Supply Manual
Provide the hardware specifications of power
supply manual.
Software configuration
Configuration guides
Describe software features and configuration
procedures.
Command references
Provide a quick reference to all available
commands.
Configuration examples
Describe typical network scenarios and provide
configuration examples and instructions.
Operations and
maintenance
Release notes
Provide information about the product release,
including the version history, hardware and
software compatibility matrix, version upgrade
information, technical support information, and
software upgrading.
Troubleshooting
Provides troubleshooting information for common
problems of using the product.
FAQ
Covers the most frequently asked questions about
the hardware, software and system specifications.
System log messages Explains the system log messages.
Obtaining documentation
Access the most up-to-date H3C product documentation on the World Wide Web
at http://www.h3c.com
.
Click the following links to obtain different categories of product documentation:
[Technical Documents]
—Provides hardware installation, software upgrading, and software feature
configuration and maintenance documentation.
[Products & Solutions]
—Provides information about products and technologies, as well as solutions.
[Software Download]
—Provides the documentation released with the software version.
Technical support
service@h3c.com
http://www.h3c.com
Documentation feedback
You can e-mail your comments about product documentation to info@h3c.com.
We appreciate your comments.
i
Contents
Preparing for installation ················································································· 1
Safety recommendations ··································································································································· 1
Safety symbols ··········································································································································· 1
General safety recommendations ·············································································································· 1
Electricity safety ········································································································································· 1
Laser safety ················································································································································ 1
Router moving ············································································································································ 2
Examining the installation site ···························································································································· 2
Temperature and humidity ························································································································· 2
Altitude ······················································································································································· 3
Cleanliness ················································································································································· 3
Cooling system ··········································································································································· 3
ESD prevention ·········································································································································· 4
EMI ····························································································································································· 5
Lightning protection ···································································································································· 6
Rack-mounting ··········································································································································· 6
Installation accessories ······································································································································ 6
Pre-installation checklist ···································································································································· 7
Installing the router ························································································· 9
Check before installation ···································································································································· 9
Installing the router in a 19-inch rack ··············································································································· 10
Attaching cage nuts to the rack ················································································································ 10
Installing the cable management brackets ······························································································· 11
Attaching the mounting brackets to the router ························································································· 12
Installing the router in the rack ················································································································· 13
Grounding the router ········································································································································ 14
Installing an MPU ············································································································································· 15
Installing an RPE-X1/RPE-X3 MPU ········································································································· 15
Installing an RSE-X1 MPU ······················································································································· 17
Installing an MCP MPU ···························································································································· 18
Installing a FIP module ···································································································································· 19
Installing a SAP/OAP ······································································································································· 20
Installing a HIM/MIM ········································································································································ 21
Installing a fan tray ··········································································································································· 22
Installing a CF card ·········································································································································· 23
Installing a power module ································································································································ 23
Connecting a power cord ································································································································· 24
Connecting an AC power cord ················································································································· 24
Connecting a DC power cord ··················································································································· 24
Installing FRUs ······························································································ 27
Installing an air filter ········································································································································· 27
Installing a fiber management tray ··················································································································· 27
Installing a lightning protector for a network port ····························································································· 28
Connecting the AC power supply to a power strip with lightning protection ···················································· 29
Installing a surge protector ······························································································································· 30
Connecting interface cables ·········································································· 33
Connecting the AUX cable ······························································································································· 33
Overview ·················································································································································· 33
Connecting the AUX cable ······················································································································· 33
Connecting an Ethernet cable ·························································································································· 34
Overview ·················································································································································· 34
Making an Ethernet cable ························································································································ 35
Connecting an Ethernet cable ·················································································································· 36
Connecting a fiber cable ·································································································································· 36
ii
Transceiver module overview ·················································································································· 36
Fiber cable overview ································································································································ 37
Connecting a fiber cable ·························································································································· 38
Connecting an E1/T1 cable ······························································································································ 40
E1/T1 cable overview ······························································································································· 40
Connecting an E1/T1 cable ······················································································································ 41
Connecting a CE3/CT3 cable ·························································································································· 43
CE3/CT3 cable overview ·························································································································· 43
Connecting a CE3/CT3 cable ··················································································································· 43
Connecting a serial port cable ························································································································· 43
Overview ·················································································································································· 43
Connecting a serial port cable ·················································································································· 46
Accessing the router ····················································································· 47
Login methods ················································································································································· 47
Logging in through the console port ················································································································· 47
Setting up a configuration environment ···································································································· 47
Setting terminal parameters ····················································································································· 50
Powering on the router ····································································································································· 53
Checking before power-on ······················································································································· 53
Checking after power-on ·························································································································· 53
Displaying boot information ······················································································································ 53
Logging in to the router through Telnet ············································································································ 54
Logging in to the router through the AUX port ································································································· 54
Configuring basic settings ································································································································ 55
Hardware management and maintenance ···················································· 56
Displaying hardware information for the router ································································································ 56
Displaying the software and hardware version information for the router ················································ 56
Displaying the operational statistics for the router ··················································································· 57
Displaying detailed information about a module ······················································································ 57
Displaying the electrical label information for a module ··········································································· 58
Displaying the CPU usage of a module ··································································································· 59
Displaying the memory usage of a module ······························································································ 59
Displaying the CF card information ·········································································································· 60
Displaying the operational status of the fan ····························································································· 60
Displaying the operational status of power modules ················································································ 60
Displaying the alarming thresholds of a module ······························································································ 61
Port configuration and management ················································································································ 61
Configuring a combo interface ················································································································· 61
Displaying transceiver module information and alarming information ······················································ 62
Active and standby MPU switchover ················································································································ 63
Solving system faults ······································································································································· 64
Solving system faults ······························································································································· 64
Viewing the system fault solving method ································································································· 64
Saving the current configuration of the router ·································································································· 65
Rebooting a module or router ·························································································································· 65
Replacement procedures ·············································································· 67
Safety recommendations ································································································································· 67
Replacing a power module ······························································································································ 67
Replacing an MPU ··········································································································································· 67
Prerequisites ············································································································································ 67
Replacing an RPE-X1/ RPE-X3 MPU ······································································································ 68
Replacing an RSE-X1 MPU ····················································································································· 68
Replacing an MCP ··········································································································································· 69
Replacing a FIP module ··································································································································· 70
Replacing a SAP/OAP module ························································································································ 71
Replacing a HIM/MIM ······································································································································ 72
Replacing a CF card ········································································································································ 73
Replacing a transceiver module ······················································································································· 74
Replacing a fan tray ········································································································································· 75
iii
Replacing an air filter ······································································································································· 76
Replacing a memory module ··························································································································· 76
When to replace a memory module ········································································································· 76
Memory module structure ························································································································ 77
Memory module slot ································································································································· 78
Replacing a memory module ··················································································································· 78
Troubleshooting ···························································································· 80
MPU failures ···················································································································································· 80
RUN LED is off ········································································································································· 80
RUN LED fast flashes ······························································································································ 80
ALM LED is steady on or flashes ············································································································· 80
FIP module failures ·········································································································································· 81
RUN LED is off ········································································································································· 81
RUN LED fast flashes ······························································································································ 81
Power module failures ····································································································································· 81
Power LED is off ······································································································································ 81
Red power LED is on ······························································································································· 82
Fan failures ······················································································································································ 82
Fan tray is absent ····································································································································· 82
ALM LED is red ········································································································································ 82
HIM/MIM failures ·············································································································································· 83
Configuration system problems ······················································································································· 83
No terminal display ··································································································································· 83
Garbled terminal display ·························································································································· 83
No response from the serial port ·············································································································· 84
Dealing with password loss ······························································································································ 84
Examining the state of password recovery capability ·············································································· 85
Dealing with console login password loss when password recovery capability is enabled ······················ 86
Dealing with user privilege level password loss when password recovery capability is enabled ············· 87
Dealing with password loss when password recovery capability is disabled ··········································· 88
Cooling system failure ······································································································································ 89
Ethernet port failure ········································································································································· 90
Interface module, cable, and connection failure ······························································································ 90
Software upgrade failures ································································································································ 90
No response from the serial port of the MPU ··························································································· 90
TFTP upgrade failure ······························································································································· 91
FTP upgrade failure ································································································································· 91
System software image file missing errors······································································································· 92
Appendix A Chassis views and Technical specifications ······························ 93
Chassis views ·················································································································································· 93
Dimensions and weights ·································································································································· 97
Power consumption ········································································································································· 98
Power module ·················································································································································· 99
AC power module ····································································································································· 99
DC power module ·································································································································· 101
Fan tray ·························································································································································· 102
MPU ······························································································································································· 102
RPE-X1 ·················································································································································· 103
RPE-X3 ·················································································································································· 104
RSE-X1 ·················································································································································· 105
MCP-X1/X2 ············································································································································ 106
Components ··········································································································································· 107
Flexible interface platform modules ··············································································································· 112
FIP-10 ···················································································································································· 112
FIP-20 ···················································································································································· 113
FIP-110 ·················································································································································· 114
FIP-210 ·················································································································································· 116
FIP-240 ·················································································································································· 117
FIP-300 ·················································································································································· 118
FIP-310 ·················································································································································· 119
iv
FIP-600 ·················································································································································· 122
Service aggregation platform modules ·········································································································· 123
SAP-48GBE ··········································································································································· 123
SAP-24GBP ··········································································································································· 124
SAP-48GBP ··········································································································································· 126
SAP-20GE2XP ······································································································································· 128
SAP-28GE ·············································································································································· 131
OAP cards ······················································································································································ 133
HIMs and MIMs ·············································································································································· 133
Lightning protector for a port ·························································································································· 134
Power strip with lightning protection ·············································································································· 134
Surge protector ·············································································································································· 134
Appendix B Hardware compatibility matrixes ·············································· 135
MPU and Comware compatibility matrix ········································································································ 135
LPU and MPU compatibility matrix ················································································································ 135
Interface module and Comware compatibility matrix ····················································································· 136
Interface module and FIP compatibility matrix ······························································································· 137
Appendix C LEDs ························································································ 138
MPU LEDs ····················································································································································· 139
FIP LEDs ························································································································································ 145
SAP LEDs ······················································································································································ 149
HIM/MIM LEDs ··············································································································································· 153
Power module LEDs ······································································································································ 153
Fan tray LEDs ················································································································································ 154
Appendix D Slot and interface numbering··················································· 155
Slot numbering ··············································································································································· 155
Slot arrangement for MPUs and LPUs ··········································································································· 156
Interface numbering ······································································································································· 157
Examples ······················································································································································· 157
Example 1 ·············································································································································· 157
Example 2 ·············································································································································· 158
Index ··········································································································· 159
1
Preparing for installation
Safety recommendations
To avoid any equipment damage or bodily injury caused by improper use, read the following safety
recommendations before installation. Note that the recommendations do not cover every possible
hazardous condition.
Safety symbols
When reading this document, note the following symbols:
WARNING means an alert that calls attention to important information that if not understood or
followed can result in personal injury.
CAUTION means an alert that calls attention to important information that if not understood or
followed can result in data loss, data corruption, or damage to hardware or software.
General safety recommendations
Keep the chassis and installation tools away from walk areas.
Make sure the ground is dry and flat and anti-slip measures are in place.
Remove all the external cables (including power cords) before moving the chassis.
Electricity safety
Locate the emergency power-off switch in the room before installation. Shut the power off at
once in case accident occurs.
Make sure the router has been reliably grounded.
Do not open or close the chassis cover when the router is powered on.
Use an uninterrupted power supply (UPS).
If there are two power inputs, disconnect the two power inputs to power off the router.
Do not work alone when the router has power.
Always verify that the power has been disconnected.
Laser safety
WARNING!
Do not stare into any fiber port when you connect an optical fiber. The laser light emitted from the
fiber port might hurt your eyes.
The H3C SR6616 routers are Class 1 laser devices.
2
Router moving
CAUTION:
Do not hold the handle of the fan tray or power module, the handle of the back cover of the chassis,
or the air vents of chassis to carry the router. Any attempt to carry the router with these parts might
cause equipment damage or even bodily injury.
When moving an H3C SR6616 router, follow these guidelines:
When moving the router, hold the handles at both sides of the chassis.
Use at least two people to move the router.
Move the router carefully.
Examining the installation site
The H3C SR6616 router can only be used indoors. To make sure the router operates correctly and to
prolong its service lifetime, the installation site must meet the following requirements:
Temperature and humidity
Cleanliness
EMI
Temperature and humidity
Maintain temperature and humidity in the equipment room in an acceptable range.
Lasting high relative humidity can cause poor insulation, electricity creepage, mechanical
property change of materials, and metal corrosion.
Lasting low relative humidity can cause washer contraction and ESD and bring problems
including loose screws and circuit failure.
High temperature can accelerate the aging of insulation materials and significantly lower the
reliability and lifespan of the switch.
For the temperature and humidity requirements of the router, see Table 1 an
d Table 2.
Table 1 Temperature requirements
Item Temperature
Operating temperature 0°C to 45°C (32°F to 113°F)
Storage temperature –40°C to +70°C (–40°F to +158°F)
Table 2 Humidity requirements
Item Humidity
Operating humidity (noncondensing) 10%RH to 95%RH
Storage humidity (noncondensing) 5%RH to 95%RH
3
Altitude
Table 3 Altitude requirements
Item Altitude
Operating altitude –60 m (–196.85 ft) to +4 km (2.49 miles)
Storage altitude –60 m (–196.85 ft) to +4.5 km(2.8 miles)
Cleanliness
Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of
metal components and contact points, especially when indoor relative humidity is low. In the worst
case, electrostatic adsorption can cause communication failure.
Table 4 Dust concentration limit in the equipment room
Substance Concentration limit (particles/m
3
)
Dust particles
3 x 10
4
(No visible dust on desk in three days)
NOTE:
Dust particle diameter 5 µm
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion
and premature aging of components, as shown in Tabl e 5 .
Table 5
Harmful gas limits in the equipment room
Gas Max. (mg/m
3
)
SO
2
0.2
H
2
S 0.006
NH
3
0.05
Cl
2
0.01
Cooling system
The H3C SR6616 router has a horizontally-oriented fan tray slot at the top and uses bottom to top
airflow for heat dissipation.
To ensure good ventilation, the following requirements must be met:
Leave a minimum clearance of 10 cm (3.94 in) at the inlet and outlet air vents.
The installation site has a good cooling system.
4
Figure 1 SR6616 airflow
ESD prevention
CAUTION:
Make sure the resistance reading between human body and the ground is in the range of 1 to 10
megohms (Mohms).
To prevent electrostatic discharge (ESD), note the following guidelines:
Make sure the router and the floor are reliably grounded.
Take dust-proof measures for the equipment room.
Maintain the humidity and temperature in the acceptable range.
Always wear an ESD wrist strap when touching a circuit board or transceiver module.
Place the removed memory module, CF card, or HIM/MIM on an antistatic workbench, with the
face upward, or put it into an antistatic bag.
Touch only the edges, instead of electronic components when observing or moving a removed
memory module, CF card, or HIM/MIM.
5
To attach the ESD wrist strap:
1. Wear the wrist strap on your wrist.
2. Lock the wrist strap tight around your wrist to keep good contact with the skin.
3. Insert the ESD wrist strap into the specially designed hole on the router chassis or attach it to
the grounding screw of the chassis with the alligator clips.
4. Make sure the rack is reliably grounded.
Figure 2 Attaching an ESD wrist strap
(1) ESD wrist strap (2) Lock (3) Alligator clip
EMI
All electromagnetic interference (EMI) sources, from outside or inside of the switch and application
system, adversely affect the switch in the following ways:
A conduction pattern of capacitance coupling.
Inductance coupling.
1
2
3
6
Electromagnetic wave radiation.
Common impedance (including the grounding system) coupling.
To prevent EMI, perform the following tasks:
If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE) to
filter interference from the power grid.
Keep the switch far away from radio transmitting stations, radar stations, and high-frequency
devices.
Use electromagnetic shielding, for example, shielded interface cables, when necessary.
Lightning protection
To protect the router from lightning better, perform the following tasks:
Make sure the grounding cable of the chassis is reliably grounded.
Make sure the grounding terminal of the AC power receptacle is reliably grounded.
Install a lightning protector at the input end of the power module to enhance the lightning
protection capability of the power module.
Install a special lightning protector at the input end of outdoor signal lines (for example, E1/T1
line) to which interface modules of the router are connected to enhance the lightning protection
capability.
NOTE:
For how to install a lightning protector and surge protector, see "Connecting the AC power supply to
a power st
rip with lightning protection" and "Installing a surge protector."
Rack-mounting
Before mounting the router in a standard 19-inch rack, follow these guidelines:
Install the router in a rack that has rack shelves.
For ease of installation and maintenance, reserve a minimum clearance of 0.8 m (2.62 ft)
between the rack and walls or other devices.
Verify that the headroom in the equipment room is not less than 3 m (9.84 ft).
Installation accessories
Console cable Grounding cable ESD wrist strap Cable tie Mounting brackets
M6 screws (user
supplied)
Cage nuts (user
supplied)
7
Pre-installation checklist
Table 6 Pre-installation checklist
Item Requirements Result
Installati
on site
Ventilation
There is a minimum clearance of 10 cm (3.9 in) around the
inlet and outlet vents for heat dissipation of the router
chassis.
A ventilation system is available at the installation site.
Temperature 0°C to 45°C (32°F to 113°F)
Relative humidity 10% to 95% (noncondensing)
Cleanliness
Dust concentration 3 × 104 particles/m
3
No dust on desk within three days
ESD prevention
The equipment and floor are reliably grounded.
The equipment room is dust-proof.
The humidity and temperature are in the acceptable range.
Wear an ESD wrist strap and uniform when touching a
circuit board.
Place the removed memory module, CF card, or HIM/MIM
on an antistatic workbench, with the face upward, or put it
into an antistatic bag.
Touch only the edges, instead of electronic components
when observing or moving a removed memory module, CF
card, or HIM/MIM.
EMI prevention
Take effective measures to protect the power system from
the power grid system.
Separate the protection ground of the router from the
grounding device or lightning protection grounding device
as far as possible.
Keep the router far away from radio stations, radar and
high-frequency devices working in high current.
Use electromagnetic shielding when necessary.
Lightning
protection
The grounding cable of the chassis is reliably grounded.
The grounding terminal of the AC power receptacle is
reliably grounded.
A port lightning arrester is installed. (Optional)
A power lightning arrester is installed. (Optional)
A signal lightning arrester is installed at the input end of an
external signal cable. (Optional)
Electricity safety
Equip an uninterrupted power supply (UPS).
In case of emergency during operation, switch off the
external power switch.
Workbench
The workbench is stable enough
Well grounding
Rack-mounting
requirements
Install the router in an open rack if possible. If you install the
router in a closed cabinet, make sure the cabinet is
equipped with a good ventilation system.
The rack is sturdy enough to support the weight of the
router and installation accessories.
The size of the rack is appropriate for the router.
The front and rear of the rack are a minimum of 0.8 m
(31.50 in) away from walls or other devices.
8
Item Requirements Result
Safety
precauti
ons
The router is far away from any moist area and heat source.
The emergency power switch in the equipment room is located.
Tools
Installation accessories supplied with the router
User supplied tools
Referen
ce
Documents shipped with the router
Online documents
9
Installing the router
IMPORTANT:
Keep the packages of your router and its accessories safely for future use.
Figure 3 H3C SR6616 router installation flow
Check before installation
To prepare for installing an H3C SR6616 router:
Make sure you have read "Preparing for installation" carefully and the installation
site meets all
the requirements.
10
Prepare a 19-inch rack. For more information about how to install a rack, see the installation
guide provided with the rack.
Make sure the rack is sturdy and securely grounded.
Make sure there is sufficient clearance around the rack for heat dissipation and installation.
Make sure there is no debris inside or around the rack.
Move the router to a place near the rack.
Installing the router in a 19-inch rack
To install the router in a rack, you need mounting brackets and a rack shelf.
Attaching cage nuts to the rack
1. Determine where to install the router in the rack, and then install a rack shelf to the rack.
2. As shown in Figure 4, mark the po
sitions of cage nuts on the front rack posts by using a front
mounting bracket according to the position of the rack shelf.
Figure 4 Marking the positions of the cage nuts
/