FläktGroup CentriFlow 3D GMPM FC101_FC102 Quick start guide

Type
Quick start guide

FläktGroup CentriFlow 3D GMPM FC101_FC102 is a frequency converter for controlling and adjusting the speed of plug fans, ranging from 0.8 kW to 15 kW. With high efficiency (IE4) due to permanent magnets in the rotor, it offers better part load efficiency compared to asynchronous motors. Featuring a special algorithm for PM motors, it optimizes motor performance and enhances operational efficiency.

FläktGroup CentriFlow 3D GMPM FC101_FC102 is a frequency converter for controlling and adjusting the speed of plug fans, ranging from 0.8 kW to 15 kW. With high efficiency (IE4) due to permanent magnets in the rotor, it offers better part load efficiency compared to asynchronous motors. Featuring a special algorithm for PM motors, it optimizes motor performance and enhances operational efficiency.

PUR (A, B, C, D)
SLIDE IN ROTOR CASSETTE
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
FLÄKTGROUP OFFERS A WIDE RANGE OF PER-
MANENT MAGNET MOTORS (PM) AND FREQUENCY
CONVERTERS FOR PLUG FANS. POWER RANGE IS
FROM 0,8 KW TO 15 KW.
CONTENT PAGE
1. General ................................................................................................ 2
2. Fan and Motor data ......................................................................... 3
3.
Frequency converter data
................................................................... 4
4. Separate frequency converter dimensions ............................................... 5
5. Specification for motor ........................................................................................ 5
6. Installation ................................................................................................................ 5
7. Connection diagram ............................................................................................. 6
8. Cabling ........................................................................................................................7
9. Control signals ........................................................................................................ 8
10. Start up and functional testing....................................................................... 8
11. Parameters ............................................................................................................. 8
12. Operating panel FC101 .....................................................................................9
13. Operating panel FC102 ..................................................................................10
14. Alarms and warnings ...................................................................................... 11
CENTRIFLOW 3D PLUG FAN GMPM
FC101 AND FC102 FREQUENCY CONVERTER
QUICK GUIDE
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
2
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
1. GENERAL
FläktGroup offers a wide range of permanent magnet motors (PM)
and frequency converters for plug fans. Power range is from 0,8
kW to 15 kW. PM motor has high efficiency (IE4) due to the per-
manent magnets in rotor. Also part load efficiency is better com-
pared to asynchronous motors.
When rotor has no losses and stator needs less current the tem-
perature inside the motor is lower, which gives longer running
time for bearings.
Direct on-line connection is not possible for perma-
nent magnet motors. Frequency converter is always
needed. This controller has a special algorithm for
PM motors. Frequency converter is programmed
with fan and motor specific parameters.
FC101 and FC102 frequency converters are delivered loose. They
are to be mounted by the customer.
Frequency converter should be mounted near the fan.
Motor cable shall not be longer than 10 m. With longer cables
some motor parameters should be changed. Frequency converter
is deli vered with 3.5 m motor cable for fan sizes up to 050. For
bigger fans motor cable length is 4.5 m. Cable is connected at the
motor end.
PM motor
IP54 and IP55 frequency converter mounted at AHU casing.
FC101 Frequency controller FC102 Frequency controller
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
3
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
2. FAN AND MOTOR DATA
Fan code incl.
Motor and drive
Power
[kW]
Motor Current
[A]
Motor frame
Size IEC
Fan max speed
[rpm]
Fan max freq.
[Hz]
Motor speed
[rpm] at 50 Hz
Motor nominal
speed [rpm]
GMPM-1-bb-025-11e0 1,1 2,4 71 5000 250 1000 4500
GMPM-1-bb-025-06e0 0,8 1,9 71 3960 198 1000 3000
GMPM-1-bb-028-15e0 1,5 3,1 71 4300 215 1000 4500
GMPM-1-bb-028-08e0 0,8 1,9 71 3630 182 1000 3000
GMPM-1-bb-031-30e0 36,8 71 4660 233 1000 4500
GMPM-1-bb-031-22e0 2,2 6,8 71 4140 207 1000 4500
GMPM-1-bb-031-15e0 1,5 3,4 71 3700 185 1000 3600
GMPM-1-bb-031-06e0 0,8 1,9 71 2900 145 1000 3000
GMPM-1-bb-035-30e0 37,5 90 3940 263 750 3600
GMPM-1-bb-035-22e0 2,2 4,4 71 3400 170 1000 3000
GMPM-1-bb-035-15e0 1,5 3,5 71 3120 156 1000 2500
GMPM-1-bb-035-08e0 0,8 3,5 71 2460 123 1000 2500
GMPM-1-bb-040-55e0 5,5 13 90 3940 263 750 3000
GMPM-1-bb-040-40e0 49,1 90 3550 237 750 3000
GMPM-1-bb-040-30e0 39,1 90 3190 213 750 3000
GMPM-1-bb-040-22e0 2,2 4,4 71 2700 135 1000 3000
GMPM-1-bb-040-15e0 1,5 3,5 71 2440 122 1000 2500
GMPM-1-bb-040-08e0 0,8 3,5 71 2000 100 1000 2500
GMPM-1-bb-045-55e0 5,5 13 90 3050 203 750 3000
GMPM-1-bb-045-40e0 49,1 90 2650 177 750 3000
GMPM-1-bb-045-30e0 39,1 90 2500 167 750 3000
GMPM-1-bb-045-15e0 1,5 3,9 71 2200 110 1000 1800
GMPM-1-bb-045-11e0 1,1 3,9 71 1800 90 1000 1800
GMPM-1-bb-050-75e0 7,5 16,2 112 2840 142 1000 2600
GMPM-1-bb-050-55e0 5,5 13 90 2400 160 750 3000
GMPM-1-bb-050-36e0 3,6 7,8 90 2100 140 750 1800
GMPM-1-bb-050-22e0 2,2 5,2 90 1900 127 750 1440
GMPM-1-bb-050-15e0 1,5 3,9 71 1760 88 1000 1800
GMPM-1-bb-056-75e0 7,5 16,3 112 2380 119 1000 2100
GMPM-1-bb-056-55e0 5,5 10,8 90 2150 143 750 2000
GMPM-1-bb-056-40e0 410,8 90 1930 129 750 2000
GMPM-1-bb-056-36e0 3,6 7,8 90 1850 123 750 1800
GMPM-1-bb-056-22e0 2,2 6,5 90 1500 100 750 1100
GMPM-1-bb-063-81e0 11 22,4 112 2240 112 1000 2000
GMPM-1-bb-063-75e0 7,5 17 112 1950 98 1000 1800
GMPM-1-bb-063-55e0 5,5 11,5 112 1760 88 1000 1600
GMPM-1-bb-063-40e0 49,7 90 1550 103 750 1700
GMPM-1-bb-063-22e0 2,2 6,5 90 1200 80 750 1100
GMPM-1-bb-071-81e0 11 21 112 1840 92 1000 1650
GMPM-1-bb-071-75e0 7,5 17,3 112 1620 81 1000 1500
GMPM-1-bb-071-55e0 5,5 12 112 1460 73 1000 1300
GMPM-1-bb-071-40e0 412 112 1320 66 1000 1300
GMPM-1-bb-071-22e0 2,2 6,5 90 1075 72 750 1100
GMPM-1-bb-080-85e0 15 34,5 132 1655 83 1000 1655
GMPM-1-bb-080-81e0 11 22,9 132 1500 75 1000 1350
GMPM-1-bb-080-75e0 7,5 16,8 112 1315 66 1000 1230
GMPM-1-bb-080-55e0 5,5 12,2 112 1185 59 1000 1100
GMPM-1-bb-080-30e0 312,2 112 965 48 1000 1100
GMPM-1-bb-090-75e0 7,5 16,4 132 1093 55 1000 1000
GMPM-1-bb-090-81e0 11 22,9 132 1240 62 1000 1140
GMPM-1-bb-090-85e0 15 35,2 132 1375 69 1000 1375
e = 1 for FC101
e = 5 for FC102
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
4
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
3. FREQUENCY CONVERTER DATA
Mains supply (L1, L2, L3)
Supply voltage 380-480 V ±10%
Supply frequency 50/60 Hz
Max. imbalance temporary
between mains phases 3.0% of rated supply voltage
True Power Factor (λ) 0.9 nominal at rated load
Displacement Power Factor
(cosφ) near unity (> 0.98)
Switching on input supply
L1, L2, L3 (power-ups) maximum 2 times/min.
Environment according to
EN60664-1
overvoltage category III/
pollution degree 2
Motor output (U, V, W)
Output voltage 0 - 100% of supply voltage
Output frequency
for PM motors
FC101 0 - 390 Hz
FC102 0-590 Hz
Digital inputs:
Programmable digital inputs 4
Logic PNP or NPN
Voltage level 0 - 24 V DC
Analog inputs:
Number of analog inputs 2
Modes Voltage or current
Voltage level 0 to + 10 (scalable)
Current level 0/4 to 20 mA (scalable)
Analog output:
Number of programmable
analog outputs
FC101 = 2
FC102 = 1
Current range at analog output 0/4 - 20 mA
Digital output:
Programmable digital 2
Voltage level at digital FC101 = 17 V
FC102 = 24 V
Max. current at digital output: FC101 = 20 mA
FC102 = 40 mA
Relay outputs:
Programmable relay outputs 2
Max. terminal load
(AC-1 Resistive load)
FC101 = 250 V AC, 3 A
FC102 = 240 V AC, 2 A
Control card, 10 V DC output:
Output voltage 10.5 V ±0.5 V
Max. load FC101 25 mA
FC102 15 mA
Control card, 24 V DC output:
Max. load FC101 = 80 mA
FC102 = 200 mA
Surroundings:
Enclosure separate unit FC101 = IP54
FC102 = IP55
Vibration test separate unit 1.0 g
Max. relative humidity,
during operation 5% - 95%(non-condensing)
Maximum ambient temperature FC101 = 40 °C
FC102 = 45 °C (24h average)
Minimum ambient temperature
during full-scale operation 0 °C separate unit
Standard built-in fieldbus communication:
Modbus RTU FC101 and FC102
BACnet embedded FC101 and FC102
N2 Metasys FC101 and FC102
FC Protocol FC101 and FC102
FLN Aapogee FC101 and FC102
Physical layer RS-485
Optional Fieldbus communication:
VLT
®
Profibus DP V1 MCA 101 FC102
VLT
®
DeviceNet MCA 104 FC102
VLT
®
LonWorks MCA 108 FC102
VLT
®
BACnet MCA 109 FC102
VLT
®
ProfiNet MCA 120 FC102
VLT
®
EtherNet/IP MCA 121 FC102
VLT
®
Modbus TCP MCA 122 FC102
VLT
®
BACnet/IP MCA 125 FC102
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
5
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
4. SEPARATE FREQUENCY CONVERTER DIMENSIONS 5. SPECIFICATION FOR MOTOR
Admissible environmental temperature: from -15 °C up to
+40 °C, with altitudes 1000 m above sea level
Mounting: IM B3
Drive operating voltage: 400 VAC
Insulation class: “F”; temperature rise to class B
(TEFC execution)
IP55 degree of protection for the whole range
Reduced dimensions
6. INSTALLATION
Warning: Risk of electric shock
Motor terminals may still be Live if the impeller is
rotating, even when the main incoming supplied has
been isolated. Ensure the impeller is kept stationary
before opening and whilst the terminal box is open.
Frequency converter and motor shall be installed by a qualified
electrician with adequate knowledge how to install speed-con-
trolled drive systems (frequency inverters) and EMC safety.
All cabling must comply with national and local regulations on ca-
ble cross-sections and ambient temperature
b
B
C
Ø
D
aA
FC101
Power
(kW)
Dimensions (mm) Weight
(kg)
Height Width Depth
C
Hole
ØD
A a B b
0.75-4 332 318.5 115 74 225 5.5 5.3
5.5-7.5 369 354 135 89 237 6.5 7.2
11-18.5 476 460 180 133 290 6.5 13.8
Protection class IP 54
FC102
Power
(kW)
Dimensions (mm) Weight
(kg)
Height Width Depth
C
Hole
ØD
A a B b
1.1.-4 420 401 200 171 175 6.5 9.7
5.5-7.5 420 402 242 215 200 6.5 13.5
11-15 480 454 242 210 260 9.0 23.0
Protection class IP 55
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
6
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
7. CONNECTION DIAGRAM
AHU
P1
F1
F2
SUPPLY
L1
L2
L3
PE
L1
12 18 27 +10 V
55 55 01 02 03 04 05 06 61 68 6953
RELAY 1 RELAY 2 RS-485
Com P N
L2 L3
START/STOP
INTERLOCK
ALARM
RUNNING
INDICATION
PE U V W PE
PE min 10 mm2 or two wires
3x400 V AC
F1
S1
PM-MOTOR
FREQUENCY CONVERTER
AHU CONTROLLER
W2 U2 V2
U1 V1 W1
3
– +
CONTROL SIGNAL
0 - 10 V
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
7
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
8. CABLING
8.1. SUPPLY CABLE
Mount mains supply to terminals L1, L2 and L3 and ground wires
to earth terminal and tighten.
SHORT CIRCUIT PROTECTION:
The frequency converter must be protected against short-circuit
to avoid electrical or fire hazard. The fuses mentioned below are
recommended to use to protect service personnel and equipment
in case of an internal failure in the frequency converter. Frequency
converter provides full short circuit protection in case of a short
circuit on the motor output.
OVER CURRENT PROTECTION:
Provide overload protection to avoid fire hazard due to overheat-
ing of the cables in the installation. The frequency converter is
equipped with an internal over-current protection that can be used
for upstream overload protection (UL-applications excluded). See
par. 4-18 Current Limit. Moreover, fuses or circuit breakers can
be used to provide the over-current protection in the installation.
Over-current protection must always be carried out according to
national regulations.
LEAKAGE CURRENT (>3,5 mA)
EN/IEC61800-5-1 (Power Drive System Product Standard) re-
quires special care if the leakage current exceeds 3,5mA. Earth
grounding must be reinforced in one of the
following ways:
Earth ground wire of at least 10mm²
Two separate earth ground wires both complying with the
dimensioning rules
ISOLATION SWITCH
All frequency converters may be used with an isolated input
source as well as with ground reference power lines.
8.2. RECOMMENDED FUSES ON THE SUPPLY SIDE
Power (kW) 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15
3x380-480VAC
Rec. non UL type gG 10 10 10 10 16 16 16 25 25 50 50
See national/international regulations for selecting an applicable
fuse size.
8.3. MOTOR CABLE
Frequency converter is delivered with a 3.5 m motor cable for fan
sizes up to 050. For bigger fans the motor cable length is 4.5 m.
Should the cable be shortened or replaced with a longer one a
few rules must be followed. Motor cable must be of shielded type.
Shield should be grounded 360° at both ends of the cable. The
motor cable must not be longer than 10 meters to achieve EMC-
level EN 55011 Class B with standard FC101 and FC102 frequency
converters. Motor cable can be extended to 50 meters with op-
tional H1 EMC filter in FC102.
Motor is connected to star inside the motor. Phase wires are
connected to terminals U1, V1, W1. Terminal connectors are not
needed.
8.4. CONTROL CABLE
Control cable must be shielded. Keep control cable distance min.
200 mm from mains and motor cable.
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
8
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
9. CONTROL SIGNALS
START/STOP
Fan is started with potential free switch connected between ter-
minals 12 and 18. There is +24 VDC in this circuit. AUTO-mode
should be selected from operation panel.
INTERLOCK
By opening interlock signal between terminals 12-27 the fan can
be stopped and then it is not possible to start from operating
panel manually or via bus. With this signal fan running can be in-
terlocked to circulating pump alarm or ventilation emergency stop.
This function can be activated by setting parameter 5-12 value to
“Coast inverse”.
SPEED REFERENCE
Speed can be controlled with 0…10V signal connected in termi-
nals 53(+) and 55(-).
RELAY OUTPUTS
Alarm signal is available in relay1 (terminals 01, 02 and 03).
Running indication is available in relay 2 (terminals 04, 05 and
06).
SINGLE SPEED OPERATION:
Set constant speed reference (Hz) in parameter 412. Only external
start signal is needed.
TWO SPEED OPERATION:
Lower speed reference (Hz) is set in parameter 412 and higher
speed reference (Hz) in parameter 311. Lower speed is activated
with start signal (terminals 12-18). Higher speed is activated by
closing terminals 12-29.
MODBUS RTU
Frequency converter can be controlled via Modbus RTU. RS-485
cable is connected to the terminals 68 (P), 69 (N) and 61 (COM). If
the frequency converter is the last unit in line, it should be termi-
nated by setting switch S801 in ON position. Modbus operation is
described in frequency converter operation instructions.
10. START UP AND FUNCTIONAL TESTING
After power up test check motor rotation if a separate frequency
converter is delivered:
Set frequency converter to Hand on mode from operation panel.
Motor will start to rotate. For changing the direction of rotation,
disconnect supply voltage and wait for power to discharge. Make
sure that the motor impeller is not rotating when making connec-
tions. Reverse the connection of any two of the three motor cables
on the motor or frequency converter side of the connection.
When direction of rotation is right set frequency converter to Auto
on mode. Then the frequency converter will follow control signals.
11. PARAMETERS
Frequency converter parameters are set at the factory providing
for optimal performance of fan and motor. This includes motor pa-
rameters, ramp times, starting and stopping methods and speed
limitations. Changing these parameters may result in unstable op-
eration or the motor will not start. Original parameter values can
be downloaded from operation panel in case of losing them:
Go to parameter 0-50 LPC Copy
Set parameter value to 2 (All from LCP)
Wait until the copy is completed
Parameters are password protected. Changing motor parameters
may cause a motor failure. Password for main menu is 100 and
for quick menu 200.
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
9
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
12. OPERATING PANEL FC101
Operating panel is standard in frequency converter FC101.
A. ALPHA NUMERIC DISPLAY
The LCD-display is back-lit with 2 alpha-numeric lines. All data is
displayed on the LCP.
Information can be read from the display.
1Parameter number and name.
2Parameter value.
3
Set-up number shows the active set-up and the edit setup.
If the same set-up acts as both active and edit set-up, only
that set-up number is shown (factory setting).
When active and edit set-up differ, both numbers are
shown in the display (Setup 12). The number flashing,
indicates the edit set-up.
4
Motor direction is shown to the bottom left of the display
– indicated by a small arrow pointing either clockwise or
counterclockwise.
B. MENU KEY
Use the menu key to select between status, quick menu or
main menu.
5The triangle indicates if the LCP is in status, quick menu or
main menu.
C. NAVIGATION KEYS AND INDICATOR LIGHTS (LEDS)
6Com led: Flashes when bus communication is
communicating.
7Green LED/On: Control section is working.
8Yellow LED/Warn.: Indicates a warning.
9Flashing Red LED/Alarm: Indicates an alarm.
10 [Back]: For moving to the previous step or layer in the
navigation structure
11
[s] [] [ ]: For maneuvering between parameter
groups, parameters and within parameters.
Can also be used for setting local reference.
12 [OK]: For selecting a parameter and for accepting
changes to parameter settings.
D. OPERATION KEYS AND INDICATOR LIGHTS (LEDS)
13
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTICE!
Terminal 27 Digital Input (5-12 Terminal 27 Digital Input) has
coast inverse as default setting. This means that [Hand
On] not starts the motor if there is no 24 V to terminal
27. Connect terminal 12 to terminal 27.
14 [Off/Reset]: Stops the motor (Off). If in alarm mode the
alarm will be reset.
15 [Auto On]: frequency converter is controlled either via
control terminals or serial communication.
Menu
On
Com.
Back
OK
Alarm
Hand
On
Off
Reset
Auto
On
Warn.
1-20 Motor Power
[5] 0.37kW - 0.5 HP
Setup 1
Status Quick
Menu
Main
Menu
A
B
C
D
6
10
7
8
9
13
5
1
2
3
4
11
12
11
11
14 15
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
10
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
13. OPERATING PANEL FC102
Operating panel is standard in frequency converter FC102.
A. DISPLAY AREA
The display area is activated when the frequency converter
receives power from mains voltage, a DC bus terminal, or an
external 24 V DC supply.
The information displayed on the LCP can be customized for user
application. Select options in the Quick Menu Q3-13 Display Settings.
Display Parameter number Default setting
10-20 Reference %
2 0-21 Motor current
3 0-22 Power [kW]
4 0-23 Frequency
5 0-24 kWh counter
Auto
on Reset
Hand
on
Status Quick
Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
Status 1(1)
0.00 kW
0.0Hz
On
Alarm
Warn.
A
0.00 A
0.0 %
B
C
D
2605 kWh
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18 19 20 21
Indicator Light Function
15 ON Green
The ON light activates when the frequency
converter receives power from mains volt-
age, a DC bus terminal, or an external 24
V supply.
16 WARN Yellow
When warning conditions are met, the
yellow WARN light comes on and text
appears in the display area identifying the
problem.
17 ALARM Red A fault condition causes the red alarm light
to flash and an alarm text is displayed.
D. OPERATION KEYS AND RESET
Operation keys are located at the bottom of the LCP.
Key Function
18 Hand On
Starts the frequency converter in local control.
• An external stop signal by control input or
serial communication overrides the local hand on
9Off Stops the motor but does not remove power to
the frequency converter.
20 Auto On
Puts the system in remote operational mode.
• Responds to an external start command by con-
trol terminals or serial communication
21 Reset Resets the frequency converter manually after
a fault has been cleared.
C. NAVIGATION KEYS AND INDICATOR LIGHTS (LEDS)
Navigation keys are used for programming functions and moving
the display cursor. The navigation keys also provide speed control
in local (hand) operation. There are also 3 frequency converter
status indicator lights in this area.
Key Function
10 Back Reverts to the previous step or list in the menu
structure.
11 Cancel Cancels the last change or command as long as
the display mode has not changed.
12 Info Press for a definition of the function being dis-
played.
13 Navigation
Keys
Use the 4 navigation keys to move between items
in the menu.
14 OK Use to access parameter groups or to enable a
choice.
B. DISPLAY MENU KEYS
Menu keys are used for menu access for parameter set-up,
toggling through status display modes during normal
operation, and viewing fault log data.
Key Function
6Status Shows operational information.
7Quick Menu
Allows access to programming parameters for
initial set-up instructions and many detailed appli-
cation instructions.
8Main Menu Allows access to all programming parameters.
9 Alarm Log Displays a list of current warnings, the last 10
alarms, and the maintenance log.
FC101 and FC102 frequency converters for plug fan GMPM -
Quick Guide
11
FläktGroup DC_10035GB_20180514_R0
Specifications are subject to change without further notice
14. ALARMS AND WARNINGS
If alarm or warning messages appear, consult the frequency con-
verter operating manual for fault messages and troubleshooting.
Warning! Frequency converter tries to restart the motor after alarm so
the fan may start automatically.
PROTECTION AND FEATURES:
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the
frequency converter trips if the temperature is too high.
The frequency converter is protected against short-circuits on
motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or
issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the
frequency converter trips if the intermediate circuit voltage is
too low or too high.
The frequency converter is protected against earth faults on
motor terminals U, V, W.
If the frequency converter can’t find rotor position, Locked Ro-
tor alarm is generated.
Motor is stopped if motor back voltage is too high.
Motor is stopped if 24V supply is too low.
Motor is stopped if motor phase is missing.
Motor is stopped if inverter overloaded too long.
FG_DC-10053GB_
Frequency controllers FC101 and FC102
_QG_180514_R0 © Copyright 2018 FläktGroup
WWW.FLAKTGROUP.FI GMPM FC101-FC102
» Learn more on www.flaktgroup.com
or contact one of our offices
A HISTORY OF INNOVATION
AND RELIABILITY
With more than a century of accumulated industry experience, FläktGroup is in
a unique position to deliver energy efficient components and solutions for inte-
grated performance, reliability and quality. With modern manufacturing techno-
logies, precise deliveries and technical support, FläktGroup is your partner –
fulfilling and surpassing industry standards and certifications.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

FläktGroup CentriFlow 3D GMPM FC101_FC102 Quick start guide

Type
Quick start guide

FläktGroup CentriFlow 3D GMPM FC101_FC102 is a frequency converter for controlling and adjusting the speed of plug fans, ranging from 0.8 kW to 15 kW. With high efficiency (IE4) due to permanent magnets in the rotor, it offers better part load efficiency compared to asynchronous motors. Featuring a special algorithm for PM motors, it optimizes motor performance and enhances operational efficiency.