ABB RIO600 Configuration manual

Type
Configuration manual
Remote I/O
RIO600
Configuration Manual
Document ID: 1MRS757489
Issued: 2011-12-23
Revision: A
Product version: 1.0
© Copyright 2011 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Section 1 Introduction.......................................................................3
This manual........................................................................................3
Intended audience..............................................................................3
Product documentation.......................................................................3
Product documentation set............................................................3
Document revision history.............................................................3
Related documentation..................................................................4
Symbols and conventions...................................................................4
Symbols.........................................................................................4
Document conventions..................................................................4
Section 2 RIO600 overview..............................................................7
Overview.............................................................................................7
Module configuration.....................................................................8
Configuration and engineering tool for RIO600..................................9
PCM600 and RIO600 connectivity package version.....................9
Hardware and software requirements................................................9
RIO600 engineering flow..................................................................10
Section 3 Setting up a project........................................................11
Handling connectivity packages.......................................................11
Uninstalling connectivity packages .............................................11
Installing connectivity packages..................................................11
Activating connectivity packages ................................................14
Creating a new project......................................................................15
Building the plant structure...............................................................16
Inserting IEDs...................................................................................17
Inserting an IED in offline mode..................................................18
Inserting an IED in online mode..................................................24
Setting the technical key...................................................................32
Editing object properties...................................................................35
Section 4 Using the Parameter Setting tool...................................37
Viewing parameters..........................................................................37
Reading parameters from the device...............................................38
Setting communication and synchronization parameters ................39
Writing parameters to the device .....................................................40
Section 5 Using the Signal Matrix tool............................................43
Starting the Signal Matrix tool...........................................................43
Table of contents
RIO600 1
Configuration Manual
Exporting SCD files..........................................................................44
Importing SCD files...........................................................................46
Section 6 Common Read/Write (CRW)..........................................51
Starting Read/Write .........................................................................51
Section 7 Using the Composition Update tool................................55
Configuring the device offline...........................................................55
Configuring the device online...........................................................59
Section 8 GOOSE engineering......................................................65
Creating a project.............................................................................65
Importing an SCL file in IET600........................................................66
Creating GOOSE datasets ..............................................................68
Defining data attributes................................................................70
Configuring GOOSE control blocks..................................................70
Configuring a GOOSE Subscriber ...................................................72
Exporting SCD files in IET600..........................................................72
Section 9 Troubleshooting..............................................................75
Troubleshooting the technical key in online mode............................75
Troubleshooting the reading and writing of parameters...................76
Section 10 Glossary.........................................................................79
Table of contents
2 RIO600
Configuration Manual
Section 1 Introduction
1.1 This manual
The configuration manual contains information on how to engineer the device
using the different tools in PCM600. The manual provides information for IEC
61850 engineering with PCM600 and IET600. For more details on tool usage, see
the PCM600 documentation.
1.2 Intended audience
This manual addresses system and project engineers involved in the engineering
process of a project.
1.3 Product documentation
1.3.1 Product documentation set
The installation and commissioning manual contains information on how to install
and commission the device. The manual provides an introduction to engineering
tasks and a description of the basic operations.
The configuration manual contains information on how to engineer the device
using the different tools in PCM600. The manual provides information for IEC
61850 engineering with PCM600 and IET600. For more details on tool usage, see
the PCM600 documentation.
The user manual (online help) contains instructions on how to use the RIO600
Configuration Wizard. The Configuration Wizard helps configure RIO600 for
different system products and tools with the help of the connectivity package. See
the product documentation for more information on handling the connectivity
packages in different system products and tools.
1.3.2 Document revision history
Document revision/date
Product version History
A/2011-12-23 1.0 First release
1MRS757489 A Section 1
Introduction
RIO600 3
Configuration Manual
1.3.3 Related documentation
Name of the document Document ID
RIO600 Installation and Commissioning Manual 1MRS757488
Specific Communication Service Mapping (SCSM) – Mappings to
MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-8-1
Download the latest documents from the ABB Web site
http://www.abb.com/substationautomation.
1.4 Symbols and conventions
1.4.1 Symbols
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2 Document conventions
A particular convention may not be used in this manual.
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
HMI menu paths are presented in bold.
Select Main menu/Settings.
WHMI menu names are presented in bold.
Section 1 1MRS757489 A
Introduction
4 RIO600
Configuration Manual
Click Information in the WHMI menu structure.
Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
1MRS757489 A Section 1
Introduction
RIO600 5
Configuration Manual
6
Section 2 RIO600 overview
2.1 Overview
RIO600 is a modular I/O designed to expand the digital I/O of ABB’s Relion
®
product family IEDs and to provide I/O for Station Automation device COM600
used in power generation plants, utility substations and industrial power systems.
GUID-10936B8E-CD69-425B-A212-BBACE48211EC V1 EN
Figure 1: RIO600
RIO600 is designed to function with ABB IEDs and also with other RIO600 units
to exchange binary I/O information over Ethernet.
1MRS757489 A Section 2
RIO600 overview
RIO600 7
Configuration Manual
IEC 61850-8-1
IEC 60870-5-104
ABB
MicroSCADA
RET615 RET615 RIO600 REF630
IEC 61850-8-1
COM600
Web HMI
COM600
Web HMI
PCM600
Ethernet switch
COM600
RIO600 RED615 RED615
RIO600
RIO600 REF615
COM600
Binary signal
transfer
PCM600
Ethernet switch
Line differential
communication
GUID-F03EF024-C321-473D-B753-D7D490D99282 V1 EN
Figure 2: Conceptual picture of a typical system setup
Understanding the communication properties of the IED is a prerequisite before
making any mechanical or electrical connections to RIO600. The connection
details of the IED are available in the respective manuals.
2.1.1 Module configuration
RIO600 is designed using a modular architecture, where the I/O control
functionality is built on modules. The RIO600 modules can be stacked on a
standard DIN rail to achieve the required configuration. The minimum
configuration required for RIO600 is PSM_H-LECM-DIM8_H or PSM_H-LECM-
DOM.
RIO600 consists of four module types.
Power Supply Module (PSM_H)
Communication Module (LECM)
Digital Input Module (DIM8_H)
Digital Output Module (DOM)
RIO600 can be configured to operate a maximum of 20 binary I/O signals using
one PSM_H module and up to 40 binary I/O signals using two PSM _H modules.
Section 2 1MRS757489 A
RIO600 overview
8 RIO600
Configuration Manual
2.2 Configuration and engineering tool for RIO600
PCM600 with the RIO600 connectivity package is used for configuring RIO600.
Configuring RIO600 in online and offline mode
Setting the operating parameters for the modules using PST
Performing the I/O mapping across the modules using SMT
Reading and writing the configuration and the parameter file to RIO600
CCT600 or IET600 are used to establish the GOOSE communication between the
IEDs configured in PCM600.
2.2.1 PCM600 and RIO600 connectivity package version
Protection and Control IED Manager PCM600 Ver. 2.3 or later
RIO600 Connectivity Package Ver. 1.0 or later
2.3 Hardware and software requirements
Table 1: Requirements
Description
Requirements
Hardware Pentium III, 800 MHz or higher
128 RAM or higher
40 MB free disk space
Software Operating SystemWindows 98 / XP / VISTA / Windows 7
Microsoft .NET Framework 2.0
PCM600 Ver.2.3 or later
IET600
1MRS757489 A Section 2
RIO600 overview
RIO600 9
Configuration Manual
2.4 RIO600 engineering flow
Create the RIO600 in PCM600, use the
RIO600 Connpack and select online or
offline configuration
Online mode
Select and assign
the HW slot
RIO600 ConnPack scans the ‘powered up’
RIO600 and ascertains the hardware
configuration
Set the parameters of
RIO600 modules
RIO600 ConnPack automatically instantiates one LN GGIO
for every BI module, comprising DOs equaling number of
channels and also creates the datasets comprising all the
BI channel status and health information
Export the SCD file to the
IET600 tool
Enter the GoCB parameters for RIO600
and do subscriber mapping
Export the SCD file to
PCM600
Map the I/O using SMT
in PCM600
Select the write operation and download
the configuration into RIO600
Use the Web client to view parameter
settings and other operational data of the
RIO600 device
No
Yes
GUID-4185D81E-9E1B-4CDF-A04B-BA33C2AA0582 V1 EN
Figure 3: Basic steps in RIO600 GOOSE engineering
Section 2 1MRS757489 A
RIO600 overview
10 RIO600
Configuration Manual
Section 3 Setting up a project
3.1 Handling connectivity packages
Uninstall the old RIO600 connectivity package before installing a new version. The
product code has changed in the latest release.
3.1.1 Uninstalling connectivity packages
1. To uninstall a connectivity package version, click Start, click Control Panel.
2. In the Control Panel, double-click Add or Remove Programs.
3. Select the connectivity package and click Remove.
GUID-A10FAF3F-F32A-4E5F-99EC-B6EFAC770898 V1 EN
Figure 4: Selecting the RIO600 connectivity package
4. In the Add or Remove Programs dialog box, click Yes to confirm the
uninstallation.
3.1.2 Installing connectivity packages
Install Microsoft .NET Framework 2.0 and PCM600 Version 2.4
Production Build before installing the RIO600 connectivity package.
1. Run the ABB RIO600 Connectivity Package Ver. n.msi installer from the
RIO600 connectivity package installation package. (n = version number)
2. In the connectivity package setup, click Next.
1MRS757489 A Section 3
Setting up a project
RIO600 11
Configuration Manual
GUID-77C5FCFB-F605-4904-9605-E8B0F7170B00 V1 EN
Figure 5: Running RIO600 installation wizard
2.1. Click Cancel to exit the installation.
2.2. Click Resume to revert back to the installation or Exit Setup to confirm
the cancellation.
3. Select I accept the license agreement and click Next.
GUID-A6406B4A-C038-4BE8-A6E6-4CB6A23E817A V1 EN
Figure 6: Accepting the License Agreement before installation
4. Click Browse select the file destination and click Next.
Section 3 1MRS757489 A
Setting up a project
12 RIO600
Configuration Manual
GUID-9A3AF6D3-8133-424A-A7AF-BC48E868A65E V1 EN
Figure 7: Selecting the folder for installation
5. Click Next to start the installation.
GUID-AF3833E9-54FB-41C1-B70B-98CE07D1AA9F V1 EN
Figure 8: Installation progress
6. After the installation is complete, click Finish to exit the setup program.
1MRS757489 A Section 3
Setting up a project
RIO600 13
Configuration Manual
GUID-F5EA0C8E-4DFC-4534-BB76-74B74D268E34 V1 EN
Figure 9: Completing the installation
3.1.3 Activating connectivity packages
The connectivity package has to be installed before it can be activated.
1. Double-click the Update Manager icon on Windows desktop to activate the
appropriate connectivity package.
The Update Manager shows the connectivity packages that are compatible
with the installed PCM600 version.
2. Select the ABB RIO600 Connectivity Package Ver. n (n = version number).
Always use the latest version of the connectivity package.
Section 3 1MRS757489 A
Setting up a project
14 RIO600
Configuration Manual
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80