SBC PCD3-WAC Owner's manual

Type
Owner's manual
Document PP26-862; Edition EN06 │ 2014-11-04
Manual
PCD3 WAC
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Content
0-1
0
0 Content
0.1 Document History ............................................................................................... 0-3
0.2 Brands and trademarks ..................................................................................... 0-3
1 Orientation guide
1.1 Introduction ......................................................................................................... 1-1
1.2 Instructions for connecting Saia-PCD
®
controllers to the internet....................... 1-1
1.3 Starting up check list ......................................................................................... 1-2
1.3.1 General .......................................................................................................... 1-2
1.3.2 GPRSandPPPconguration ........................................................................ 1-4
1.4 PCD3.WAC as GPRS S-Bus client station ........................................................ 1-5
1.5 Planning an application ...................................................................................... 1-6
1.6 I/O Extension ...................................................................................................... 1-7
1.7 Mounting rules .................................................................................................... 1-8
1.7.1 Airow ............................................................................................................. 1-8
1.7.2 Mounting ......................................................................................................... 1-8
1.7.3 Earthing and connection plan ......................................................................... 1-9
1.8 General technical details .................................................................................... 1-10
2 PCD3.M2x30 WAC CPUs
2.1 Supported WAN communication technologies ................................................... 2-1
2.2 Wired Wide Area Automation .............................................................................. 2-1
2.2.1 PSTN modem ................................................................................................. 2-1
2.2.2 ISDN modem .................................................................................................. 2-1
2.2.3 WACwithEthernetport................................................................................... 2-2
2.3 WideAreaAutomationwithwirelessconnection ................................................ 2-2
2.4 WACversionswithGSM/GPRSmodem ............................................................ 2-2
2.4.1 Wirelessnetworkconnection .......................................................................... 2-2
2.4.2 DifferencebetweenGSM(CSD)andGPRS(PSD) ........................................ 2-3
2.5 GeneralOverview ............................................................................................... 2-4
2.5.1 Characteristics ................................................................................................ 2-4
2.6 Dimensions ......................................................................................................... 2-5
2.7 Memory ............................................................................................................... 2-6
2.8 Connections of the CPU ..................................................................................... 2-7
2.9 Description of the LEDs for the Flash card and communication ......................... 2-7
2.10 I/O Connections .................................................................................................. 2-8
2.10.1AnalogueInputs(TerminalblockX0) .............................................................. 2-9
2.10.2DigitalInputs(TerminalblockX1) ................................................................... 2-11
2.10.4Terminalblockwith“PushIn”systemandLED(optional) ............................... 2-12
3 Communication interfaces
3.1 Ethernet .............................................................................................................. 3-1
3.2 USB .................................................................................................................... 3-1
3.3 Onboard Serial ports .......................................................................................... 3-1
3.4 CommunicationportswithsocketA .................................................................... 3-2
3.4.1 Possible F-Modules Serie PCD7.F1xx ............................................................ 3-2
3.4.2 PossibleF-ModulesnewseriePCD7.F1xxS .................................................. 3-4
3.5 Modem(Port131) ............................................................................................... 3-8
3.5.1 General ........................................................................................................... 3-8
3.5.2 GSM/GPRS Modem ........................................................................................ 3-8
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Content
0-2
0
3.5.3 PSTN Modem ................................................................................................. 3-10
3.5.4 ISDN Modem .................................................................................................. 3-10
3.6 Life check and modem reset .............................................................................. 3-11
3.6.1 Check Internet connection via GPRS ............................................................. 3-11
3.6.2 GPRS diagnosis .............................................................................................. 3-11
3.6.3 Using modem reset ......................................................................................... 3-12
3.6.4 Modem connection via ISDN or PSTN ............................................................ 3-12
3.7 Modem LED functionality .................................................................................... 3-13
4 WAN,possibilitiesofconguration
4.1 Defaultgateway/RoutingwithPPPcommunication ............................................ 4-1
4.2 Use Modem communication as backup to Ethernet ........................................... 4-2
4.3 Dyn DNS for PCD3.WAC .................................................................................... 4-3
4.4 Modem 18 library and PPP communication ....................................................... 4-4
5 Input/output (I/O) modules
6 Conguration
6.1 General ............................................................................................................... 6-1
6.2 DeviceCongurator ............................................................................................ 6-1
6.3 Digital Inputs ....................................................................................................... 6-2
6.4 Digital Outputs .................................................................................................... 6-2
6.5 Analogue Inputs .................................................................................................. 6-3
7 Maintenance
7.1 Changing the battery .......................................................................................... 7-1
A Appendix
A.1 Icons ................................................................................................................... A-1
A.2 Denitionsofserialinterfaces ............................................................................. A-2
A.2.1 RS-232 ............................................................................................................ A-2
A.2.2 RS-485/422 ..................................................................................................... A-3
A.3 Order details ....................................................................................................... A-4
A.4 Contact .............................................................................................................. A-5
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Document History | Brands and trademarks
Content
0-3
0
0.1 Document History
Date Version Changes Remarks
pEN01 2009-02-15 - Newedition
EN02 2009-03-15 2009-05-15 Modications
EN03 2010-05-15
2010-08-08
2010-09-02
2010-06-05
2010-08-11
2010-09-02
WAN possibilities
ReworkedchapterCh01
ChapterCh03:Denitionoftheambienttem-
peratur for the PCD7.F150
EN04 2012-12-08 - NewPCD7.F1xxSmodulesinCh03
EN05 2014-04-09 - Change of Logo
EN06 2014-11-04 Chapter 1.3.1 : Connection of the «+24VDC»
and «GND» inverted
0.2 Brands and trademarks
Saia PCD
®
and Saia PG5
®
are registered trademarks of Saia-Burgess Controls AG.
Technicalmodicationsarebasedonthecurrentstate-of-the-arttechnology.
Saia-Burgess Controls AG, 2009
©
All rights reserved.
PublishedinSwitzerland
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Introduction | Starting up check list
Orientation guide
1-1
1
1 Orientation guide
1.1 Introduction
ThismanualcoversthetechnicalaspectsofthePCD3.M2x30A4Tx.Thefollowing
terms are used frequently:
● CPU Centralprocessingunit:theheartoftheSaiaPCD
®
● LIOs LocalI/Os:theseareconnectedtotheCPUviatheI/Obus
● Modules Input/outputelements,mountedinahousing,matchedtothe
PCD3 system
● Moduleholder CPU,RIOorLIO,towhichmodulesmaybeattached
● WAC WideAreaController
The aim of this section is to present the essentials of planning and installing control
systemswithPCD3components.
1.2 Instructions for connecting Saia-PCD
®
controllers to the internet
When Saia PCD controllers are connected directly to the internet, they are also
a potential target of cyber attacks. For secure operation, appropriate protective
measuresmustalwaysbetaken.
PCDcontrollersincludesimple,built-inprotectionfeatures.However,secureop-
erationontheinternetisonlyensuredifexternalroutersareusedwitharewall
and encrypted VPN connections.
For more information, please refer to our support site:
www.sbc-support.com/security
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Starting up check list
Orientation guide
1-2
1
1.3 Starting up check list
1.3.1 General
1. Cabling of PCD3.WAC (Only PCD3.M2x30A4T5)
8
9
+24 VDC
GND
For a proper operation of the GSM modem of a PCD3 Wide Area Controller
(PCD3.M2230A4T5andPCD3.M2330A4T5),themodemneedstobeconnectedtothe
24VDCpowersupplyonterminalblockX0!
ThisadditionalpowerconnectionisnotrequiredforWACwithanalogueorISDN
Modem(PCD3.M2330A4T1andPCD3.M2330A4T3)
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Starting up check list
Orientation guide
1-3
1
2 Insert SIM card (Only PCD3.M2x30A4T5)
DisablethePINcodecheck(→Canbedonewitha
mobilephone)andinsertSIMcard.
SIM-card-
Karte
3 Connect GSM/GPRS antenna (Only PCD3.M2x30A4T5)
Placetheantennaatleast50cmawayfromtheWAC
device.
> 50 cm
4 Power on equipment
Withoutanyconguration,themodemwillnotconnect
totheGPRSnetwork.
5 Use SD ash card
TheSDashcardisaccessiblewiththename
SL2Flash.
Thefactorydefaultpositionoftherotaryswitchis0for
readingandwritingtoashmemory
→Worksonlyifthecoverisclosed.
→Iftheswitchisputonposition4,theSDashcard
canbeusedwithoutcover.Thismodeisrecom-
mended for test only.
6 Conguration with Device Congurator
In the Saia PG5
®
DeviceConguratorchoosetheright
deviceforconguration.
Thesection„OnboardModem“includesallmodem
parameters.
Modemconguration
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
PCD3.WAC as GPRS S-Bus client station
Orientation guide
1-4
1
1.3.2 GPRSandPPPconguration
1 Starts Saia PG5
®
Device Congurator
OnboardModemconguration
2 Activate PPP
Change PPP Enable to Yes
3 Enter GPRS access data (APN)
InSkriptModem,Line5replaceTagGPRS_APNwith
the data of your provider.
e.g: GPRS_APN => ProviderData.GPRS
Some GPRS access data includes a user name and a
password.
4 Automatic restart of PPP
BydefaultthePPPcommunicationwillbesetupau-
tomatically after every disconnection. This means that
afteramodemresetthePPPconnectionwillbeinitial-
isedandthesystemwillgetanewIPaddressfromthe
GPRS provider.
WithautomaticrestartofPPP,theSTOPcommandcannotbeusedwithintheuser
programme.
5 DNS conguration
For a name resolution the right DNS server
corresponding to the providers APN must
be selected.
DNS Time out must be set to 8000.
6 Transfer conguration to the controller
Ifallparametersarecorrect,thecongurationcanbe
downloadedtothecontroller.
Download Configuration
7 Place Diagnose Saia PG5
®
FBoxen
TocheckthecongurationtheWAAFBoxesshouldbe
placed.
PPP Status: E.g. to check the received IP address.
GPRSStatus:E.g.toviewtheGPRSsignalquality.
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Planning an application | I/O Extension
Orientation guide
1-5
1
8 Check the Internet connection
Once the GPRS connection is established the con-
nectiontotheInternetcanbecheckedwithLifeCheck
FBox
For GPRS communication the Timeout should be set
8000!
9 Modem Reset
In Error cases the controller is able to reset the modem
toreinitializeaconnection.
For preventive reasons this can be done once a day.
10 Work with modem 18 library and PPP Stanby mode
This FBox should only be place if the modem 18 func-
tions are used.
Chose the right PCD3.WAC modem type and select
port131fortheserialcommunicationwiththemodem.
To execute PPP and modem 18 functions one after the
other, PPP must be selected as Standby mode.
EverytimethePPPcommunicationisreinitializedthesystemgetsanewIPaddress
(e.g.fromthelocalprovider)
1.4 PCD3.WAC as GPRS S-Bus client station
TotransmitdateusingS-BusonGPRSthefollowingcongurationshouldbeused:
1 S-Bus conguration for GPRS
Select Channel 9 and Timeout 15’000 in the S-Bus
congurations-FBox.
2 S-Bus Station Indirect
For the reference of the communication F-Boxes, the
„Node“and„Station“mustcorrespond.
3 Data exchange
The communication F-Boxes control the automatic
data exchange.
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
I/O Extension
Orientation guide
1-6
1
1.5 Planning an application
ThefollowingaspectsshouldbeconsideredwhenplanningPCD3applications:
● It’s only one module holderallowed
PCD3.C200 or PCD3.C110(ConnectionwithcablePCD3.K106/K116)
■ PCD3.C200Z09orPCD3.C110Z09(ConnectionwithconnectorPCD3.K010)
● TheinternalloadcurrenttakenbytheI/Omodulesfromthe+5VandV+supply
mustnotexceedthemaximumsupplycurrentspeciedfortheCPUsorthe
LIO PCD3.C110/C110Z09
When planning an application, we recommend the following procedure:
Select the I/O modules according to your requirements. Where possible, use
PCD3I/Omoduleswith16connections;thesehave16redLEDs.
PCD3 M2230A4T5 M2330A4T1 M2330A4T3 M2330A4T5
I/O bus connection for expansion units Yes
Numberofinputs/outputswiththeoneI/O
moduleholder(PCD3.C200)
78
1)
1)UsingdigitalI/OmodulesPCD3.E16xorA46xwith16I/Oseach
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Mounting rules
Orientation guide
1-7
1
1.6 I/O Extension
OnlyoneextensionPCD3.C200orPCD3.C110canbeconnected!
TheadditionalI/Oscanbemappedwiththedevice
congurator.
TherstI/Oaddressontheextensionmoduleis64.
No SPI communication on the extension.
WithPro-S-Netonport2orEthernettheSystemcanalsobeextendedwithPCD3.
RIO(PCD3.T760orPCD3.T660)modules.
PCD3.C110
PCD3.C200
PCD3.K010
For connecting the former extension modules to the Saia PCD
®
,usethefollowing
cables:
PCD3.K106 0.7 m or
PCD3.K116 1.2 m
WiththenewextensionmodulesPCD3.C110Z09andPCD3.C200Z09theconnector
PCD3.K010 can be used.
PCD3.C110Z09
PCD3.C200Z09
PCD3.K010
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Mounting rules
Orientation guide
1-8
1
1.7 Mounting rules
1.7.1 Airow
Thecontrollermustbemountedinaverticalwaysothatcoolingisgivenbythermic
airowfromdowntotheuppersideoftheshape.
1.7.2 Mounting
ThePCD3.WACwillbemountedona35mmtophatrailDINEN60715.
Mounting:
Press the top of the housing onto the mounting surface
Pressdownwardsagainstthetophatrail
Press the bottom of the housing against the mounting
surface and snap into place.
Remove:
Pushdownwardsthetwoholdingelementsandpullout.
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
General technical details
Orientation guide
1-9
1
1.7.3 Earthing and connection plan
0V
2.5 mm
2
In the bottom part of the PCD3.WAC there is a shielding and earthing plate.
Thezero-potential(Minuspole)ofthe24VsupplyisconnectedtotheMinusterminal
ofthesupply.Thisshouldbeconnectedtotheearthingbarwiththeshortestpossible
wire(<25cm)of1.5mm
2
.
Any shielding of analogue signals or communication cables should also be brought to
the same earth potential, either via a Minus terminal or via the earthing bar.
All Minus connections are linked internally. For problem-free operation, these
connectionsshouldbereinforcedexternallywithshortwiresof1.5mm
2
.
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
General technical details
Orientation guide
1-10
1
1.8 General technical details
Supply (external and internal)
Supply voltage 24VDC±+25%smoothedor19VAC±15%full-waverectied(18VDC)
Powerconsumption
1)
typ. 250 mA at 24 V
400mAmax.peakconsumptionwithPCD7.F1xxxmoduleorexternal
I/OmodulesupportPCD3.C110andGSM/GPRScommunication(bad
reception)
Capacity of internal
5 V bus
2)
600 mA
Capacity of internal
+Vbus(16...24V)
2)
The capacity of the +V bus depends on the capacity of the 5V bus,
asfollows(themorepreciselythe24Varemaintained,thehigherthe
possiblecapacity):
24 V
- 25 %
: 100 [mA]
+30 %
24 V
- 20 %
: 150
-
I
5 V Bus
[mA]
+25
% 15
24 V
- 10 %
: 260
-
I
5 V Bus
[mA]
+10
% 4.8
1)Theloadshandledbytheoutputsandotherconsumersaregenerallymoreimportantforsizingthesupplythan
theinternalpowerleakageofthecontrol
2)WhenplanningPCD3systems,itisessentialtocheckthatthetwointernalsuppliesarenotoverloaded.This
checkisespeciallyimportantwhenusinganalogue,counterandpositioningmodules,asthesemayhaveavery
largepowerconsumption.
Atmospheric conditions
Ambient temperature Whenmountedonverticalsurfacewithverticallyalignedterminals:
0...+55 °C
In all other mounting positions, a reduced temperature range of 0..+40 °C
applies
Storage temperature -20...+85 °C
Relative humidity 10...95%withoutcondensation
Vibration resistance
Vibration according to EN/IEC 61131-2:
5...13.2Hzconstantamplitude(1.42mm)
13.2...150Hz,constantacceleration(1G)
Electrical safety
Protection type IP 20 according to EN60529
Air/leakage paths accordingtoEN61131-2andEN50178:betweencircuitsandbodiesand
betweenelectricallyisolatedcircuits:surgecategoryII,foulinglevel2
Electromagnetic compatibility
Electrostatic discharge according to EN61000-4-2: 8 kV: contact discharge
Electromagneticelds accordingtoEN61000-4-3:eldintensity10V/m,80...1000MHz
Bursts according to EN61000-4-4: 4 kV on DC supply lines, 4 kV on I/O signal
lines, 1 kV on interface lines
Noise emission accordingtoEN61000-4-6:ClassA(forindustrialareas)
Noise immunity acc. to EN61000-6-4
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
General technical details
Orientation guide
1-11
1
Mechanism and mounting
Housing material Module holder: PC/ABS, light grey, RAL7035
I/O modules: PC, transparent blue
Clips: PAM, orange, RAL2003
Fibre optics: PC, crystal-clear
Mounting rail Top-hatrailaccordingtoEN50022-35(35mm)
Electromagnetic compatibility
Electrostatic discharge according to EN61000-4-2: 8 kV: contact discharge
Electromagneticelds accordingtoEN61000-4-3:eldintensity10V/m,80...1000MHz
Bursts according to EN61000-4-4: 4 kV on DC supply lines, 4 kV on I/O signal
lines, 1 kV on interface lines
Noise emission accordingtoEN61000-4-6:ClassA(forindustrialareas)
Noise immunity acc. to EN61000-6-4
Mechanism and mounting
Housing material Module holder: PC/ABS, light grey, RAL7035
I/O modules: PC, transparent blue
Clips: PAM, orange, RAL2003
Fibre optics: PC, crystal-clear
Mounting rail Top-hatrailaccordingtoEN50022-35(35mm)
Connections
Terminal
blocks
Spring
terminals
10-pole,
4-pole
Screw
terminals
10-pole
Spring
terminals
14-pole,
12-pole,
8-pole
Spring
terminals
24-pole,
6-pole
Earth
terminal
Terminal
2-pole
supply
Section
stranded
singlewire
0.5...2.5 mm²
0.5...2.5 mm²
0.5...2.5 mm²
0.5...2.5 mm²
0.5...1.5 mm²
0.5...1.5 mm²
0.5...1.0 mm²
0.5...1.0 mm²
0.08...
2.5 mm²
0.5...
1.5 mm²
The terminal blocks may only be plugged onto 20 times. They must then be replaced, to guarantee a
reliable contact
Length of
insulation
7 mm 7 mm 7 mm 7 mm 5...6 mm 7 mm
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
WAN communication technologies
PCD3.M2x30 WAC CPUs
2-1
2
2 PCD3.M2x30 WAC CPUs
2.1 Supported WAN communication technologies
Four different types of PCD3 Wide Area Controller are available. Every model has an
integratedmodemwithwhichWANconnectionscanbeestablishedoveraprovider’s
telecommunicationsnetwork.
PCD3.M2230A4T5 GSM/GPRS modem
PCD3.M2330A4T1 Ethernet, PSTN modem
PCD3.M2330A4T3 Ethernet, ISDN modem
PCD3.M2330A4T5 Ethernet, GSM/GPRS modem
2.2 Wired Wide Area Automation
Wherewiredcommunicationwithatelecommunicationsproviderisavailableata
location,thistechnologyshouldbepreferredtowirelessconnectionsbecausethe
connection quality is better.
YoumayalsowishtouseGSMtooptimisecosts;however,youwillthenhavetoac-
ceptcertainrestrictionsinthequalityofcommunication.Forapplicationswherethe
availabilityoftheconnectionisveryimportant,awiredconnectionshouldbeprovided
asthenormalcommunicationchannelwithaGSM/GPRSchannelasabackup.
2.2.1 PSTN modem
TheWACwithintegratedPSTNmodem(PSTNstandsforPublicSwitchedTel-
ecommunicationsNetwork)canberunoveranormaltelephoneline.Dependingon
whetherthedeviceisattachedtoatrunklineoran(internal)PBX(PrivateBranchEx-
change),thefunctionalitymaybemoreorlessrestricted.Itmaybethatnoincoming
callswillbeaccepted,oroutgoingcallsmaybewhollyorpartlyblocked.Thereare
also(internal)exchangesthathavetobespeciallyconguredinordertorunmodems
and fax machines. A dedicated trunk line has the advantage that the behaviour and
capabilitiesofsuchalinearewellknown,whichisnotalwaysthecasewithcon-
nectionsthroughaPBX.Wherethereliabilityofthealarmfunctionisakeycriterion,
youshoulduseaseparateline,asthe(internal)exchangeisanadditionallinkinthe
chain that could restrict the function.
TheWACmodelwiththeintegratedPSTNmodemisthePCD3.M2330A4T1
2.2.2 ISDN modem
WiththeWACwithISDNmodem,theproblemissimilartothePSTNversion.
ISDNstandsforIntegratedServicesDigitalNetwork.WhenanISDNlinehasbeen
ordered,theproviderusuallysuppliesadevicewhichisneededtooperateamodem
orISDNtelephone.ThisdeviceiscalledaNetworkTerminationforISDNBasicRate
Access(NTBA)(inSwitzerland,NT2ab).ItispossibletoconnectmultipleISDNde-
vices and 2 analogue devices to this adapter. ISDN connections offer approximately
twicethespeedofanaloguepoint-to-pointconnections.Withanaloguepoint-to-point
connections,youarelimitedtoaspeedof33600bit/s,whileISDNpoint-to-pointcon-
nectionsusingaBchannelcanreachaspeedof64kBit/s.Inprinciple,thetwoexist-
ing B channels can be combined to 128 kBit/s. If you have to transmit larger volumes
of data, ISDN is an advantage.
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Wireless connection | GSM/GPRS modem
PCD3.M2x30 WAC CPUs
2-2
2
For connections to the Internet provider’s digital modems, there is only a small differ-
enceinspeedbetweenanalogue(56kBit/s)andISDNconnections(64kBit/s).The
advantages of ISDN are particularly the fast connection setup and better quality.
TheWACmodelwiththeintegratedISDNmodemisthePCD3.M2330A4T3.
2.2.3 WACwithEthernetport
Anotheralternativewithwiredconnectionsisabroadbandline,e.g.withxDSL.With
this technology, the existing transfer capacity of normal copper cable trunk lines is
muchbetterutilised.ThesearealwaysInternetconnections.ByconnectinganxDSL
router to the Ethernet port of a WAC, you can achieve much higher transfer rates
thanwithanalogueorISDNmodems.Asyouonlyhavetopayaxedamountper
month,communicationcostsareeasiertocalculate.AdrawbackofxDSLthatisoften
overlooked is that, in contrast to a modem connection, you no longer have a pass-
word-protectedprivatecommunicationchannelasstandard.Youhavetocreatesuch
channelsyourselfusingVPNs(VirtualPrivateNetworks).Thisgenerallyrequiresad-
ditionalhardware,whichisnotnormallyincludedinthexDSLpackage.Theuseofa
modemwithanintegratedrewalloranadditionalexternalrewallisstronglyrecom-
mended.
ThefollowingWACmodelshaveanEthernetport:PCD3.M2330A4T1,
PCD3.M2330A4T3 and PCD3.M2330A4T5.
2.3 WideAreaAutomationwithwirelessconnection
Whereacommunicationconnectionoverwiresisnotpossiblebecausetheunitisto
beplacedinanareathatisnotservedbythexednetwork,youshouldusetheWAC
withGSM/GPRSmodems.WACswithGSM/GPRSarealsowellsuitedforuseas
a communication backup.
2.4 WACversionswithGSM/GPRSmodem
2.4.1 Wirelessnetworkconnection
ThefollowingtypesinthePCD3WideAreaControllerseries:
PCD3.M2330A4T5 and PCD3.M2230A4T5 can use the functions of the GSM mobile
communicationnetwork.
TheGSMversionsoftheWideAreaControllercanbeusedinlocationswherethere
isreceptionfromaGSMnetwork.IfyoucanusemobilephoneswiththeGSMstand-
ard,andthesignalstrengthissufcient,youshouldalsobeabletouseaPCD3Wide
Area Controller.
GSM(GlobalSystemforMobileCommunications)isthebest-knownstandardformo-
bile communication. Its share of the global mobile communications market is about
80%.GSMisnowavailableinaround200countries.
The PCD3.M2330A4T5 and PCD3.M2230A4T5 have an integrated quadband GSM/
GPRSmodem.Thefollowingfrequenciesaresupported:
850MHz,900MHz,1800MHz,1900MHz.ItshouldbepossibletousetheminEu-
ropewithoutanyrestrictions.ItisadvisabletocheckthatthereisgoodGSMrecep-
tion at the desired location. If the devices are to be used in America, Asia, Africa or
Australia,youshouldcheckbeforehandwhatfrequenciesareavailableandwhether
you need to apply for additional licenses.
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
GSM/GPRS modem
PCD3.M2x30 WAC CPUs
2-3
2
ThePCD3WACcanusethefollowingservicesprovidedbyGSMmobilenetwork
providers:
SMS Short Message Service
CSD CircuitSwitchedData
GPRS General Packet Radio Service
In order to operate the PCD3.M2330A4T5 and PCD3.M2230A4T5 devices, you need
aSIMcardfromamobilenetworkprovider.Dependingonthecommunicationservice
thatyouwanttouse,youshouldaskfortheappropriatesubscriptionfromthepro-
vider. There are subscriptions that support SMS, CSD and GPRS. Voice may also
besupported,butthereisnobenetinthis,asitisnotsupportedbytheWAC.There
are subscriptions that only support CSD and SMS, and others that only support SMS.
Ifyoulimityourselftoafewservices,thepriceofthesubscriptionshouldbequite
affordable.Manyoperatorsofferattractiveframeworkcontractsforsufcientlyhigh
volumes.
2.4.2 DifferencebetweenGSM(CSD)andGPRS(PSD)
WithCSD(CircuitSwitchedDataService)a“channel”isestablishedtemporarily.The
baud rate over this channel is 9600 baud. By using other coding schemes and bun-
dlingchannels(high-speedCSD,orHSCSD),ahigherbaudratecanbeprovidedfor
datacommunication.Thismustbesupportedbythehardwareandtheoperator.A
channelisestablishedfromAtoB.Thetwodevicesareaddressedbytheirtelephone
numbers,asisusualwithxedlinecommunication.
Thecostsarecalculatedpertimeunit;theexactformulamayvaryaccordingtothe
operator. For example, there may be a cost element per call + a time element in sec-
ondsorminutes(rounded).
WithPSD(PacketSwitchedDataService),IPpacketsaretransmitted.
GSMnetworkscanofferthefollowingPSDservices:GPRSandEDGE.Notall
providers have expanded their infrastructure to include EDGE. No transparent data
channelsareestablishedaswithCSD.Itisnotpossiblesimplytoexchangedata
betweentwoterminals.
Operators usually bill the communication costs for PSD by data volume and not by
timeaswithCSD.
WithGPRStransmission,youarenotallocatedaconstantbandwidthaswithCSD
communication.Acertainnumberofchannelsineachwirelesscellarereservedfor
thewholeIPpackettrafctoandfromallsigned-onGPRSterminals.Themorede-
vicesarecommunicatingviathesamewirelesscell,thesmallerthebandwidthavail-
able to any individual device.
Foroperators,voicecommunicationalwayshasthehighestpriorityforcommercial
reasons. The GSM system has not been optimised for data transfer.
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
GeneralOverview
PCD3.M2x30 WAC CPUs
2-4
2
2.5 GeneralOverview
The CPU is similar to the PCD3.M3xxx.
ThismanualspeciesonlythedifferencestoaPCD3.PleaserefertothePCD3Hard-
waremanualforthewholefeatureset,alsorefertothePCD3.WACyer.
Telecom port
ISDN, PSTN
GSM, GPRS
SIM card holder
SD Flash card
Status LED’s
IO connector
Ethernet
USB
Sockets for F-
Modules
Battery
SD card
protection
Terminal block X1
10...19
Terminal block X0
0...9
Terminal block X3
30...39
Terminal block XF
0...9
CPU connector
1...9
Functions for
SD flash card
Analogue Inputs
Power supply for
GSM/GPRS
modem
up to 1024 MB
2.5.1 Characteristics
● Compactsize:130×140×75mm(W×H×D)
User program memory: 512 KByte RAM
Flash onboard for user program backup: 512 KByte
● Flashonboardforlesystem:1MB
USB, RS-485, 2 interrupts onboard and integrated Web server
● EthernetTCP/IP(PCD3.M2230A4T5 not)
● Dataprotectionwithremovablelithiumbattery:1-3years
● 14DatapointswithcompactI/OBoard:
○ 8DigitalInputs(DI):15...30VDC,0.8ms“ON“-Delay.
2 Relais-outputs: 24 VDC, 0.5 A, change over
○ 4AnalogueInputs(AI):13Bit+/-10V;12Bit0...10V,0...20mA,
0...2500Ohm, Pt/Ni1000
● 1Port(socketA)forPCD7.F1xx
● 1TelecomportforPSTN,ISDNorGSM/GPRS
● Adequatepluggablescrewterminalblocksincluded*
Options: Pluggable“Push-in”terminalblockwithLED(10poles-1xplus,
1xground,8xI/Osignals)(onlyforX1)
Pluggable“Push-in”terminalblockwithLED(3x10poles,
3wireconnection)(onlyforX1)
Saia-Burgess Controls AG
Hardware Manual for the PCD3 WAC Document PP26-862 EN06 │ 2014-11-04
Dimensions
PCD3.M2x30 WAC CPUs
2-5
2
2.6 Dimensions
74
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54

SBC PCD3-WAC Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI