  • Hello! I am an AI chatbot trained to assist you with the H3C S12508-AC Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
H3C S12500 Routing Switch Series
Installation Guide
Hangzhou H3C Technologies Co., Ltd.
http://www.h3c.com
Document version: 6W170-20111114
Copyright © 2008-2011, Hangzhou H3C Technologies Co., Ltd. and its licensors
All rights reserved
No part of this manual may be reproduced or transmitted in any form or by any means without prior
written consent of Hangzhou H3C Technologies Co., Ltd.
Trademarks
H3C,
, Aolynk, , H
3
Care,
, TOP G, , IRF, NetPilot, Neocean, NeoVTL,
SecPro, SecPoint, SecEngine, SecPath, Comware, Secware, Storware, NQA, VVG, V
2
G, V
n
G, PSPT,
XGbus, N-Bus, TiGem, InnoVision and HUASAN are trademarks of Hangzhou H3C Technologies Co.,
Ltd.
All other trademarks that may be mentioned in this manual are the property of their respective owners
Notice
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute the warranty of any kind, express or implied.
Environmental protection
This product has been designed to comply with the environmental protection requirements. The storage,
use, and disposal of this product must meet the applicable national laws and regulations.
Preface
The H3C S12500 Routing Switch Series Installation Guide describes how to install the H3C S12500
switches.
This preface includes:
Audience
Conventions
About the H3C S12500 documentation set
Obtaining documentation
Technical support
Documentation feedback
Audience
This documentation is intended for:
Network planners
Field technical support and servicing engineers
Network administrators working with the S12500 switches
Conventions
This section describes the conventions used in this documentation set.
Command conventions
Convention Description
Boldface Bold text represents commands and keywords that you enter literally as shown.
Italic Italic text represents arguments that you replace with actual values.
[ ] Square brackets enclose syntax choices (keywords or arguments) that are optional.
{ x | y | ... }
Braces enclose a set of required syntax choices separated by vertical bars, from which
you select one.
[ x | y | ... ]
Square brackets enclose a set of optional syntax choices separated by vertical bars, from
which you select one or none.
{ x | y | ... } *
Asterisk marked braces enclose a set of required syntax choices separated by vertical
bars, from which you select at least one.
[ x | y | ... ] *
Asterisk marked square brackets enclose optional syntax choices separated by vertical
bars, from which you select one choice, multiple choices, or none.
&<1-n>
The argument or keyword and argument combination before the ampersand (&) sign can
be entered 1 to n times.
# A line that starts with a pound (#) sign is comments.
GUI conventions
Convention Description
Boldface
Window names, button names, field names, and menu items are in Boldface. For
example, the New User window appears; click OK.
> Multi-level menus are separated by angle brackets. For example, File > Create > Folder.
Symbols
Convention Description
WARNING
An alert that calls attention to important information that if not understood or followed can
result in personal injury.
CAUTION
An alert that calls attention to important information that if not understood or followed can
result in data loss, data corruption, or damage to hardware or software.
IMPORTANT
An alert that calls attention to essential information.
NOTE
An alert that contains additional or supplementary information.
TIP
An alert that provides helpful information.
Network topology icons
Represents a generic network device, such as a router, switch, or firewall.
Represents a routing-capable device, such as a router or Layer 3 switch.
Represents a generic switch, such as a Layer 2 or Layer 3 switch, or a router that supports
Layer 2 forwarding and other Layer 2 features.
Port numbering in examples
The port numbers in this document are for illustration only and might be unavailable on your device.
About the H3C S12500 documentation set
The H3C S12500 documentation set includes:
Category Documents Purposes
Marketing brochures Describe product specifications and benefits.
Technology white papers
Provide an in-depth description of software features
and technologies.
Product description and
specifications
Card datasheets
Describe card specifications, features, and
standards.
Category Documents Purposes
Regulatory compliance
and safety information
Provides regulatory information and the safety
instructions that must be followed during installation.
Installation guide
Provides a complete guide to hardware installation
and hardware specifications.
H3C N68 Cabinet
Installation and Remodel
Introduction
Guides you through installing and remodeling H3C
N68 cabinets.
H3C Pluggable SFP
[SFP+][XFP] Transceiver
Modules Installation
Guide
Guides you through installing SFP/SFP+/XFP
transceiver modules.
Adjustable Slider Rail
Installation Guide
Guides you through installing adjustable slider rails
to a rack.
Hardware specifications
and installation
H3C High-End Network
Products Hot-Swappable
Module Manual
Describes the hot-swappable modules available for
the H3C high-end network products, their external
views, and specifications.
Configuration guides
Describe software features and configuration
procedures.
Command references
Provide a quick reference to all available
commands.
Software configuration
Configuration examples
Describe typical network scenarios and provide
configuration examples and instructions.
System log messages Explains the system log messages.
Trap messages Explains the trap messages.
MIB Companion Describes the MIBs for the software release.
Operations and
maintenance
Release notes
Provide information about the product release,
including the version history, hardware and software
compatibility matrix, version upgrade information,
technical support information, and software
upgrading.
Obtaining documentation
You can access the most up-to-date H3C product documentation on the World Wide Web at
http://www.h3c.com
.
Click the links on the top navigation bar to obtain different categories of product documentation:
[Technical Support & Documents > Technical Documents]
– Provides hardware installation, software
upgrading, and software feature configuration and maintenance documentation.
[Products & Solutions]
Provides information about products and technologies, as well as solutions.
[Technical Support & Documents > Software Download]
– Provides the documentation released with the
software version.
Technical support
http://www.h3c.com
Documentation feedback
You can e-mail your comments about product documentation to info@h3c.com.
We appreciate your comments.
i
Contents
Product overview··························································································································································1
Physical architecture ·························································································································································1
Backplane ··········································································································································································7
Fan tray ··············································································································································································7
Power supply system······················································································································································ 11
AC power supply ·················································································································································· 11
DC power supply··················································································································································· 14
Preparing for installation ···········································································································································17
Safety recommendations ··············································································································································· 17
General safety recommendations························································································································ 17
Electricity safety ····················································································································································· 17
ESD prevention ······················································································································································ 17
Switch moving ······················································································································································· 18
Laser safety····························································································································································· 18
Examining the installation site ······································································································································ 19
Weight support······················································································································································ 19
Temperature ··························································································································································· 19
Humidity ································································································································································· 19
Cleanness······························································································································································· 20
EMI·········································································································································································· 20
Grounding······························································································································································ 20
Power supply·························································································································································· 21
Space······································································································································································ 21
Rack-mounting ································································································································································ 21
Installation tools······························································································································································ 23
Installing the switch····················································································································································24
Check before installation··············································································································································· 24
Installing the switch in a rack········································································································································ 25
Installation preparation········································································································································· 25
Installing slide rails and cage nuts to the rack ··································································································· 25
Installing the mounting brackets··························································································································· 27
Installing an air deflector (optional) ···················································································································· 28
Installing a chassis air filter (optional)················································································································· 29
Mounting the switch in the rack··························································································································· 31
Verifying the installation ······································································································································· 32
Installing the switch on a workbench··························································································································· 32
Installation preparation········································································································································· 32
Installation procedures·········································································································································· 32
Grounding the switch ···················································································································································· 34
Installing the power system ··········································································································································· 35
Installation preparation········································································································································· 35
Installing a DC power module ····························································································································· 35
Installing an AC power module ··························································································································· 36
Installing a fan tray ························································································································································ 37
Installing a card······························································································································································ 38
Installation preparation········································································································································· 39
Installation procedure············································································································································ 39
Connecting power cords··············································································································································· 41
ii
Prerequisites ··························································································································································· 41
Connecting an AC power cord ··························································································································· 41
Connecting a DC power cord······························································································································ 42
Verifying the installation················································································································································ 44
Connecting the switch to the network·······················································································································45
Logging in to the switch················································································································································· 45
Connecting the console cable······························································································································ 45
Setting up a configuration environment·············································································································· 46
Powering on the switch·················································································································································· 49
Verification before power-on ······························································································································· 49
Powering on the switch········································································································································· 49
Verification after power-on··································································································································· 51
Connecting the switch to the network ·························································································································· 52
Connecting the switch to the network through the AUX port············································································ 52
Connecting the switch to the network through a copper Ethernet port ··························································· 52
Connecting the switch to the network through a fiber Ethernet port································································ 53
Cable routing recommendations ·································································································································· 56
Hardware management·············································································································································57
Displaying the electrical label information of your switch························································································· 57
Displaying the card information of your switch·········································································································· 58
Rebooting your switch ··················································································································································· 59
Managing the power supply system ···························································································································· 60
Displaying the electrical label information of the power monitoring module················································· 60
Enabling power supply management·················································································································· 61
Configuring the number of redundant power modules ····················································································· 61
Manually starting or stopping power supply to a card····················································································· 62
Allocating IDs for AC power modules················································································································· 63
Displaying the power supply system information of your switch ····································································· 64
Configuring temperature alarm thresholds for a card································································································ 70
Configuring temperature alarm thresholds for a card······················································································· 70
Displaying the temperature information of your switch····················································································· 70
Isolating a card and locating card faults····················································································································· 71
Configuring in-service hardware failure diagnosis and failure protection ······························································ 73
Displaying the operating state of fans························································································································· 75
Displaying the alarming information of a card··········································································································· 76
Displaying transceiver information and alarming information·················································································· 77
Introduction to transceivers··································································································································· 77
Displaying transceiver information······················································································································ 77
Displaying the alarming information or fault detection parameters of a transceiver····································· 79
Troubleshooting··························································································································································82
Configuration terminal problems·································································································································· 82
No terminal display ·············································································································································· 82
Garbled terminal display······································································································································ 82
Power supply system failure·········································································································································· 83
Power monitoring module····································································································································· 83
Power modules ······················································································································································ 83
Fan failure······································································································································································· 85
MPU failure····································································································································································· 85
LPU failure······································································································································································· 86
Switching fabric module failure··························································································································· 86
Interface failure······························································································································································· 87
Technical support ··························································································································································· 88
iii
Replacement procedures ···········································································································································89
Removing, cleaning, and installing the air filters········································································································ 89
Removing, cleaning, and installing the chassis air filters for an S12508 ······················································ 89
Removing, cleaning, and installing the chassis air filter for an S12518························································ 90
Removing, cleaning, and installing a power module air filter ········································································· 91
Replacing a power module··········································································································································· 91
Preparing for the replacement ····························································································································· 91
Replacing a power module ·································································································································· 92
Replacing a PEM (applicable to only an AC power module) ·········································································· 93
Replacing a card···························································································································································· 94
Preparing for the replacement ····························································································································· 94
Replacement procedure········································································································································ 95
Replacing a fan tray ······················································································································································ 96
Preparing for the replacement ····························································································································· 96
Replacement procedure········································································································································ 97
Replacing a CF card······················································································································································ 97
Replacing a transceiver module ··································································································································· 99
Regulatory Compliance and Safety Information··································································································· 101
Regulatory Compliance Information···························································································································101
Regulatory Compliance Standards····················································································································101
European Directives Compliance·······················································································································102
USA Regulatory Compliance ·····························································································································102
Canada Regulatory Compliance ·······················································································································103
Japan Regulatory Compliance···························································································································103
CISPR 22 Compliance ········································································································································103
Safety Information Sicherheits informationen安全信息 ····························································································103
Overview Überblick 概述 ···································································································································103
Electricity Safety Elektrische Sicherheit 用电安全 ····························································································107
Lithium Battery Lithiumbatterie 锂电池···············································································································109
Fuse Sicherung保险丝·········································································································································110
Laser Laser激光辐射············································································································································110
Appendix A Technical specifications····················································································································· 111
Environment requirements ···········································································································································111
Power consumption/weight/dimensions···················································································································111
Switches································································································································································111
Cards ····································································································································································112
Fan trays·······························································································································································113
Power components ··············································································································································113
Switch ordering guide ·················································································································································114
Card ordering guide····················································································································································114
MPUs·····································································································································································116
Switching fabric modules ···································································································································117
Ethernet interface card specifications················································································································117
OAA cards···························································································································································118
Power components ordering guide ····························································································································119
Appendix B LEDs····················································································································································· 124
Power system LEDs ·······················································································································································124
Monitoring module LEDs·····································································································································124
Power module LEDs·············································································································································124
Fan LEDs········································································································································································125
MPU LEDs······································································································································································125
CF card status LED···············································································································································126
iv
Network management port LEDs ·······················································································································126
Switching fabric module LED ·····························································································································126
LPU status LED ······················································································································································126
Fan status LED ······················································································································································127
Power status LED··················································································································································127
MPU LEDs ·····························································································································································127
Line card LEDs ······························································································································································127
Interface LEDs·······················································································································································128
RUN LED·······························································································································································129
Switching fabric module LEDs·····································································································································129
Appendix C Transceiver modules·························································································································· 130
10-GE XFP transceiver modules··································································································································130
10-GE SFP+ transceiver modules ·······························································································································130
10-GE SFP+ cables ······················································································································································131
100/1000 Mbps SFP transceiver modules···············································································································131
Appendix D Lightning protection··························································································································· 133
Connecting the AC power supply to a power strip with lightning protection ·······················································133
Installing a lightning protector for a network port····································································································134
Appendix E Cable management···························································································································· 136
Prerequisites··································································································································································136
Cable management guidelines···································································································································136
Appendix F Engineering labels for cables ············································································································ 139
Introduction to labels ···················································································································································139
Material································································································································································139
Type and shape···················································································································································139
Printing labels ······················································································································································141
Writing labels ······················································································································································142
Affixing labels······················································································································································143
Information carried on labels·····························································································································145
Remarks ································································································································································146
Engineering labels for Ethernet cables·······················································································································146
Engineering labels for optical fibers ··························································································································147
Labels for the fiber that connects two devices··································································································147
Labels for the fiber that connects the device and the ODF ·············································································148
Engineering labels for power cords···························································································································149
Labels for DC power cords·································································································································149
Labels for AC power cords·································································································································151
Index ········································································································································································ 153
1
Product overview
The H3C S12500 Routing Switch Series includes the models in Table 1.
Table 1 S12500 models
Model MPU slots Line card slots Switching fabric module slots
S12508-AC 2 8 9
S12508-DC 2 8 9
S12518-AC 2 18 9
S12518-DC 2 18 9
NOTE:
The “AC” suffix in a chassis model represents AC powered and the “DC” suffix in a chassis model
represents DC powered.
The line card slots are for both Ethernet interface cards and OAA cards. For card specifications, see
Appendix A Technical specifications.
Unless otherwise stated, the configuration and installation procedures in this document apply to all
S12500 switches.
Physical architecture
NOTE:
The DC-powered model and the AC-powered model of a chassis look the same.
The diagrams in this guide are for illustration only.
2
S12508 chassis views
Figure 1 S12508 front view
1
2
3
4
5
2
4
6
7
(1) Power frame cover (2) Upper cabling rack (3) MPU slots (slots 0 and 1)
(4) Lower cabling rack (5) System air intake vents (6) ESD-preventive wrist strap port
(7) Line card slots (slots 2 to 9)
3
NOTE:
The power frame cover protects the power module air filter and the power frame slot. See “Power supply
syst
em.”
Figure 2 S12508 rear view
1
2
3
4
5
6
8
7
9
(1) Power entry module (PEM) (2) Upper fan tray
4
(3) Lower fan tray (4) Ventilation panel
(5) Grounding screw (6) ESD-preventive wrist strap port
(7) Switching fabric module slots (slots 10 to 18) (8) System air exhaust vents
(9) Power air exhaust vents
The S12508 chassis has the following slots and components:
Two MPU slots and eight line card slots at the front, and nine switching fabric module slots at the
rear.
One power frame, at the top of the chassis, can accommodate up to six power modules.
Two horizontally oriented fan trays at the rear of the chassis. For the ventilation inside the chassis,
see Figure 7.
5
S12518 chassis views
Figure 3 Front view of the S12518
1
22
3
55
7
6
4
4
(1) Power frame cover (2) Upper cabling rack (3) MPU slots (slots 0 and 1)
(4) Line card slots (slots 2 to 19) (5) Lower cabling rack (6) System air intake vents
(7) ESD-preventive wrist strap port
6
Figure 4 S12518 rear view
1
2
3
4
5
6
7
8
9
(1) Power entry module (PEM) (2) Upper fan tray
(3) Switching fabric module slots (slots 20 to 28)
(4) Lower fan tray
(5) Ventilation panel (6) Grounding screw
(7) ESD-preventive wrist strap port (8) System air exhaust vents
(9) Power air exhaust vents
7
The S12518 chassis has the following slots and components:
Two MPU slots and 18 line card slots at the front, and nine switching fabric module slots at the rear.
Two power frames at the top, and each power frame can accommodate up to six power modules.
Two horizontally oriented fan trays at the rear. For the ventilation inside the chassis, see Figure 7.
Backplane
The backplane of an S12500 switch is located inside the chassis. It provides high-speed data switching
between switching fabric modules and line cards, and exchanges management and control signals
between MPUs and line cards/switching fabric modules. The backplane provides the following
capabilities:
Provides communication channels for signal exchange between cards.
Supports hot-swapping of cards.
Identifies card type.
Supplies power to MPUs, line cards, switching fabric modules, fan trays, and power modules when
connected to the power frame.
Provides monitoring channels to monitor power module status.
Fan tray
A fan tray contains fan units. The dimension of each fan unit is 120 × 120 × 38 mm (4.72 × 4.72 ×1.50
in).
Both the S12508 and the S12518 use an upper fan tray at the top and a lower fan tray at the bottom.
Each fan tray comprises 12 fan units and one fan monitoring board.
S12500 fan trays provide the following functions:
Effective heat dissipation and single-point of failure protection.
Status monitoring, including fan rotation speed monitoring and fault alarming.
Fan speed can be controlled by the MPU or automatically adjusted based on temperature. The
S12508 and S12518 have four groups of fans. Speed adjustment is done on a per-group basis to
decrease noise and improve energy efficiency.
Each fan tray has two LEDs on the front panel to show its operating status.
Hot swappable. The fans receive DC power from the backplane, and are hot swappable.
CAUTION:
The S12508 and S12518 use different fan trays, and do not support the intermixing of fan trays.
Figure 5 shows the S12508 fan tray. The physical view of the S12518 fan tray is similar.
8
Figure 5 S12508 fan tray
Table 2 Fan LED description
LED Color Status Description
Off
The fan tray has failed.
RUN Green
Flashing
The fan tray is operating properly.
Off
The fan tray is in a normal state.
Flashing
The fan tray is faulty.
ALM Red
On The fan tray is faulty.
Figure 6 and Figure 7 show the ventilation inside the chassis of the S12508 and S12518.
9
Figure 6 Ventilation inside an S12508 chassis
1
1
2
3
3
4
1
(1) System air intake direction (2) System air exhaust direction
(3) Power module air intake direction (4) Power module air exhaust direction
10
Figure 7 Ventilation inside an S12518 chassis
1
1
1
3
3
2
4
(1) System air intake direction (2) System air exhaust direction
(3) Power module air intake direction (4) Power module air exhaust direction
/