Danfoss ECL Comfort 210/296/310, A217/A317 Operating instructions

Category
Thermostats
Type
Operating instructions
OperatingGuide
ECLComfort210/296/310,applicationA217/A317
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................11
2.3Mounting...........................................................12
2.4Placingthetemperaturesensors................................16
2.5Electricalconnections.............................................18
2.6InsertingtheECLApplicationKey..............................26
2.7Checklist............................................................32
2.8Navigation,ECLApplicationKeyA217/A317................33
3.0Dailyuse.........................................................39
3.1Howtonavigate...................................................39
3.2Understandingthecontrollerdisplay..........................40
3.3Ageneraloverview:Whatdothesymbolsmean?...........42
3.4Monitoringtemperaturesandsystem
components........................................................43
3.5Influenceoverview................................................44
3.6Manualcontrol.....................................................45
3.7Schedule............................................................46
4.0Settingsoverview............................................47
5.0Settings...........................................................49
5.1IntroductiontoSettings..........................................49
5.2Tanktemperature..................................................50
5.3Flowtemperature..................................................54
5.4Returnlimit.........................................................55
5.5Flow/powerlimit.................................................60
5.6Controlparameters................................................63
5.7Application.........................................................69
5.8Anti-bacteria........................................................76
5.9Alarm................................................................78
5.10Alarmoverview....................................................81
6.0Commoncontrollersettings..............................82
6.1IntroductiontoCommoncontrollersettings’................82
6.2Time&Date.........................................................83
6.3Holiday..............................................................84
6.4Inputoverview.....................................................86
6.5Log...................................................................87
6.6Outputoverride....................................................88
6.7Keyfunctions.......................................................89
6.8System...............................................................91
7.0Miscellaneous..................................................98
7.1Severalcontrollersinthesamesystem........................98
7.2Frequentlyaskedquestions....................................101
7.3Definitions........................................................103
7.4Type(ID6001),overview.......................................106
7.5ParameterIDoverview..........................................107
©Danfoss|2018.03VI.LG.U3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA217
(ordercodeno.087H3807).
TheA217Keycontainstwosetsofapplications:oneset(A217.1/
A217.2/A217.3)andanotherset(A317.1/A317.2).
Thefunctionscanberealizedin:
ECLComfort210(A217)forsimplesolutionsor
ECLComfort310(A217/A317)foradvancedsolutions,e.g.M-bus,
ModbusandEthernet(Internet)communication.
TheapplicationsA217/A317complywithECLComfortcontrollers
210/310asofsoftwareversion1.11(visibleatstart-upofthe
controllerandinCommoncontrollersettingsin‘System’).
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
2|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
1
2
174
-
Circuit2Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
VI.LG.U3.02
©Danfoss|2018.03|3
OperatingGuideECLComfort210/296/310,applicationA217/A317
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.0Installation
2.1Beforeyoustart
Thetwoapplications,A217.1/A317.1arealmostidentical.
However,A317.1hassomeextrafunctionswhicharedescribed
separately.
TheapplicationsA217.1/A317.1areveryflexible.Thesearethe
basicprinciples:
DomesticHotWater(DHW):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS6).
Theheating/chargingtemperaturesensorS3isthemost
importantsensor.
IfthemeasuredDHWtemperature(S6)getslowerthanthedesired
DHWtemperature,theDHWheating/chargingpump(P1)is
switchedON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain
theheating/chargingtemperatureatS3.Thistemperatureis
typically5–10degreeshigherthanthedesiredDHWtemperature.
Amax.valuecanbeset.
DHWtankwith1temperaturesensor(S6):
IfthemeasuredDHWtemperature(S6)getshigherthanthe
desiredDHWtemperature,theDHWheating/chargingpump(P1)
isswitchedOFF.Thepost-runtimecanbeset.
DHWtankwith2temperaturesensors(S6andS8):
IfthemeasuredDHWtemperature(S6)getshigherthanthedesired
DHWtemperatureandthelowertemperature(atS8)getshigher
thanthecut-outtemperature,theDHWheating/chargingpump
(P1)isswitchedOFF.Thepost-runtimecanbeset.
InchargingapplicationstheDHWcirculationcanbethrough
theDHWtank(connectionA)orthroughtheheat-exchanger
(connectionB).
ThesolutionwithconnectionAresultsinclosingofthemotorized
controlvalveaftertheDHWtankchargingprocedure.
ThesolutionwithconnectionBisusedtocompensateforthe
heatlossintheDHWcirculationpipe.Furthermore,afterDHW
tankcharging,thecirculationtemperature(atS3)iscontrolled
accordingtothedesiredDHWtemperature.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredchargingtemperaturecanbe
adjusted(typicallytoalowervalue),thusresultinginagradual
closingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thesupplytemperature,S2,isusedforadjustingtheproportional
band(Xp)inordertogiveastabletemperaturecontrol.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periodsperday.
TypicalA217.1./A317.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
Chargingtemperaturesensor
S5Returntemperaturesensor
S6
DHWtanktemperaturesensor,upper
S8
DHWtanktemperaturesensor,lower
P1
DHWchargingpump(DHWheatingpump)
P3
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
VI.LG.U3.02
©Danfoss|2018.03|5
OperatingGuideECLComfort210/296/310,applicationA217/A317
ApplicationA217.1(usedinECLComfort210)/A317.1(usedin
ECLComfort310)ingeneral:
ARemoteControlUnit,theECA30,canbeconnectedinorderto
controltheECLcontrollerremotely.
Aconnectedfloworenergymeter(inECLComfort210itisbased
onpulsesignalsandinECLComfort310basedonM-bussignal)
canlimitthefloworenergytoasetmaximum.
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In
ECLComfort310theM-busdatacanfurthermorebetransferred
totheModbuscommunication.
Alarmrelay(inECLComfort210itisR4andinECLComfort310R6)
canbeactivatediftheactualflowtemperatureatS3differsfrom
thedesiredDHWchargingtemperature.
A217.1/A317.1examplea:
A217.1/A317.1exampleb:
A217.1/A317.1examplec:
A217.1/A317.1exampled:
A217.1/A317.1examplee:
6|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Thetwoapplications,A217.2/A317.2arealmostidentical.
However,A317.2hassomeextrafunctionswhicharedescribed
separately.
TheapplicationsA217.2/A317.2areveryflexible.Thesearethe
basicprinciples:
DomesticHotWater(DHW):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS6).
TheDHWheatingtemperaturesensorS3andthecharging
temperaturesensorS4arethemostimportantsensors.
IfthemeasuredDHWtemperature(S6)getslowerthanthedesired
DHWtemperature,theDHWheatingpump(P1)isswitchedON.The
motorizedcontrolvalve(M1)iscontrolledinordertomaintainthe
DHWheatingtemperatureatS3.TheDHWheatingtemperatureis
determinedbythedesiredDHWchargingtemperatureatS4.
WhentheDHWheatingtemperatureisreached,theDHWcharging
pumpP2isswitchedON.
IftheDHWchargingtemperatureatS4cannotbereached,the
ECLcontrollergraduallyincreasesthedesiredDHWheating
temperatureatS3inordertoobtainthechargingtemperature.
Amax.valuecanbeset.
TheDHWchargingtemperatureatS4istypically5–10degrees
higherthanthedesiredDHWtemperature.
DHWtankwith1temperaturesensor(S6):
IfthemeasuredDHWtemperature(S6)getshigherthanthedesired
DHWtemperature,theDHWheatingpump(P1)andtheDHW
chargingpump(P2)areswitchedOFF.Thepost-runtimecanbeset.
DHWtankwith2temperaturesensors(S6andS8):
IfthemeasuredDHWtemperature(S6)getshigherthanthe
desiredDHWtemperatureandthelowertemperature(atS8)gets
higherthanthecut-outtemperature,theDHWheatingpump(P1)
andtheDHWchargingpump(P2)areswitchedOFF.Thepost-run
timecanbeset.
InchargingapplicationstheDHWcirculationcanbethrough
theDHWtank(connectionA)orthroughtheheat-exchanger
(connectionB).
ThesolutionwithconnectionAresultsinclosingofthemotorized
controlvalveaftertheDHWtankchargingprocedure.
ThesolutionwithconnectionBisusedtocompensatefortheheat
lossintheDHWcirculationpipe.
Furthermore,afterDHWtankcharging,thecirculationtemperature
(atS4)iscontrolledaccordingtothedesiredDHWtemperature.
TypicalA217.2./A317.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
DHWheatingtemperaturesensor
S4
DHWchargingtemperaturesensor
S5Returntemperaturesensor
S6
DHWtanktemperaturesensor,upper
S8
DHWtanktemperaturesensor,lower
P1
DHWheatingpump
P2
DHWchargingpump
P3
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
VI.LG.U3.02
©Danfoss|2018.03|7
OperatingGuideECLComfort210/296/310,applicationA217/A317
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredchargingtemperaturecanbe
adjusted(typicallytoalowervalue),thusresultinginagradual
closingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thesupplytemperature,S2,isusedforadjustingtheproportional
band(Xp)inordertogiveastabletemperaturecontrol.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periodsperday.
ApplicationA217.2(usedinECLComfort210)/A317.2(usedin
ECLComfort310)ingeneral:
ARemoteControlUnit,theECA30,canbeconnectedinorderto
controltheECLcontrollerremotely.
Aconnectedfloworenergymeter(inECLComfort210itisbased
onpulsesignalsandinECLComfort310basedonM-bussignal)
canlimitthefloworenergytoasetmaximum.
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In
ECLComfort310theM-busdatacanfurthermorebetransferred
totheModbuscommunication.
Alarmrelay(inECLComfort210itisR4andinECLComfort310R6)
canbeactivatediftheactualflowtemperatureatS3differsfrom
thedesiredDHWheatingtemperature.
A217.2/A317.2examplea:
A217.2/A317.2exampleb:
8|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
TheapplicationA217.3isveryflexible.Thesearethebasic
principles:
DomesticHotWater(DHW),examplea:
Bymeansofaweekschedulee(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS3).The
DHWtemperaturesensorS3isthemostimportantsensor.
IfthemeasuredDHWtemperature(S3)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue)thusresultinginagradualclosingofthe
motorizedcontrolvalve,i.e.thereturntemperaturewilldecrease.
Thecirculationpump,P1,iscontrolledbymeansofaseparateweek
schedule(upto3‘Comfortperiods/day).
IfasupplytemperaturesensorS2isconnected,theproportional
bandXpisadaptedtotheactualsupplytemperatureinorderto
avoidcontrolinstability.
TypicalA217.3application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
DHWsupplytemperaturesensor
S5Returntemperaturesensor
S8
(Flowswitchexamplesb,c,d)
P1
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
VI.LG.U3.02
©Danfoss|2018.03|9
OperatingGuideECLComfort210/296/310,applicationA217/A317
Exampleb:
Aflowswitchsignal(S8)canbeappliedinordertoheattheDHW
ondemand(DHWtapping/DHWdraw-off).Anidletemperature
forthesupplytemperature(atS2)canbemaintainedtominimize
theheat-uptimefortheDHW.
Examplec:
Aflowswitchsignal(S8)canbeappliedinordertoheattheDHW
ondemand(DHWtapping/DHWdraw-off).Thetemperatureat
S3ismaintainedduringthecomforttimesofthecirculationpump
P1.Anidletemperatureforthesupplytemperature(atS2)canbe
maintainedtominimizetheheat-uptimefortheDHW.
Exampled:
TheDHWtankisdirectlyheated.Thesettingofthereturn
temperaturelimitation(atS5)canavoidatoohighflowinthe
heatingcoil.Anidletemperatureforthesupplytemperature(at
S2)canbemaintainedtominimizetheheat-uptimefortheDHW.
A217.3examplea:
A217.3exampleb:
A217.3examplec:
A217.3exampled:
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
10|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
VI.LG.U3.02
©Danfoss|2018.03|11
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
12|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
VI.LG.U3.02
©Danfoss|2018.03|13
OperatingGuideECLComfort210/296/310,applicationA217/A317
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
14|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
VI.LG.U3.02
©Danfoss|2018.03|15
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturers
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturers
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
16|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
VI.LG.U3.02
©Danfoss|2018.03|17
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
18|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
relay)terminals
0,2A/230Va.c.
VI.LG.U3.02
©Danfoss|2018.03|19
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/24Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
relay)terminals
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power
suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230
Va.c.from24Va.c.
20|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110

Danfoss ECL Comfort 210/296/310, A217/A317 Operating instructions

Category
Thermostats
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI