Danfoss ECL Comfort 210/296/310, A217/A317 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 210/296/310, A217/A317 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort210/296/310,applicationA217/A317
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................11
2.3Mounting...........................................................12
2.4Placingthetemperaturesensors................................16
2.5Electricalconnections.............................................18
2.6InsertingtheECLApplicationKey..............................26
2.7Checklist............................................................32
2.8Navigation,ECLApplicationKeyA217/A317................33
3.0Dailyuse.........................................................39
3.1Howtonavigate...................................................39
3.2Understandingthecontrollerdisplay..........................40
3.3Ageneraloverview:Whatdothesymbolsmean?...........42
3.4Monitoringtemperaturesandsystem
components........................................................43
3.5Influenceoverview................................................44
3.6Manualcontrol.....................................................45
3.7Schedule............................................................46
4.0Settingsoverview............................................47
5.0Settings...........................................................49
5.1IntroductiontoSettings..........................................49
5.2Tanktemperature..................................................50
5.3Flowtemperature..................................................54
5.4Returnlimit.........................................................55
5.5Flow/powerlimit.................................................60
5.6Controlparameters................................................63
5.7Application.........................................................69
5.8Anti-bacteria........................................................76
5.9Alarm................................................................78
5.10Alarmoverview....................................................81
6.0Commoncontrollersettings..............................82
6.1IntroductiontoCommoncontrollersettings’................82
6.2Time&Date.........................................................83
6.3Holiday..............................................................84
6.4Inputoverview.....................................................86
6.5Log...................................................................87
6.6Outputoverride....................................................88
6.7Keyfunctions.......................................................89
6.8System...............................................................91
7.0Miscellaneous..................................................98
7.1Severalcontrollersinthesamesystem........................98
7.2Frequentlyaskedquestions....................................101
7.3Definitions........................................................103
7.4Type(ID6001),overview.......................................106
7.5ParameterIDoverview..........................................107
©Danfoss|2018.03VI.LG.U3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA217
(ordercodeno.087H3807).
TheA217Keycontainstwosetsofapplications:oneset(A217.1/
A217.2/A217.3)andanotherset(A317.1/A317.2).
Thefunctionscanberealizedin:
ECLComfort210(A217)forsimplesolutionsor
ECLComfort310(A217/A317)foradvancedsolutions,e.g.M-bus,
ModbusandEthernet(Internet)communication.
TheapplicationsA217/A317complywithECLComfortcontrollers
210/310asofsoftwareversion1.11(visibleatstart-upofthe
controllerandinCommoncontrollersettingsin‘System’).
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
2|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
1
2
174
-
Circuit2Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
VI.LG.U3.02
©Danfoss|2018.03|3
OperatingGuideECLComfort210/296/310,applicationA217/A317
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.0Installation
2.1Beforeyoustart
Thetwoapplications,A217.1/A317.1arealmostidentical.
However,A317.1hassomeextrafunctionswhicharedescribed
separately.
TheapplicationsA217.1/A317.1areveryflexible.Thesearethe
basicprinciples:
DomesticHotWater(DHW):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS6).
Theheating/chargingtemperaturesensorS3isthemost
importantsensor.
IfthemeasuredDHWtemperature(S6)getslowerthanthedesired
DHWtemperature,theDHWheating/chargingpump(P1)is
switchedON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain
theheating/chargingtemperatureatS3.Thistemperatureis
typically5–10degreeshigherthanthedesiredDHWtemperature.
Amax.valuecanbeset.
DHWtankwith1temperaturesensor(S6):
IfthemeasuredDHWtemperature(S6)getshigherthanthe
desiredDHWtemperature,theDHWheating/chargingpump(P1)
isswitchedOFF.Thepost-runtimecanbeset.
DHWtankwith2temperaturesensors(S6andS8):
IfthemeasuredDHWtemperature(S6)getshigherthanthedesired
DHWtemperatureandthelowertemperature(atS8)getshigher
thanthecut-outtemperature,theDHWheating/chargingpump
(P1)isswitchedOFF.Thepost-runtimecanbeset.
InchargingapplicationstheDHWcirculationcanbethrough
theDHWtank(connectionA)orthroughtheheat-exchanger
(connectionB).
ThesolutionwithconnectionAresultsinclosingofthemotorized
controlvalveaftertheDHWtankchargingprocedure.
ThesolutionwithconnectionBisusedtocompensateforthe
heatlossintheDHWcirculationpipe.Furthermore,afterDHW
tankcharging,thecirculationtemperature(atS3)iscontrolled
accordingtothedesiredDHWtemperature.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredchargingtemperaturecanbe
adjusted(typicallytoalowervalue),thusresultinginagradual
closingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thesupplytemperature,S2,isusedforadjustingtheproportional
band(Xp)inordertogiveastabletemperaturecontrol.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periodsperday.
TypicalA217.1./A317.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
Chargingtemperaturesensor
S5Returntemperaturesensor
S6
DHWtanktemperaturesensor,upper
S8
DHWtanktemperaturesensor,lower
P1
DHWchargingpump(DHWheatingpump)
P3
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
VI.LG.U3.02
©Danfoss|2018.03|5
OperatingGuideECLComfort210/296/310,applicationA217/A317
ApplicationA217.1(usedinECLComfort210)/A317.1(usedin
ECLComfort310)ingeneral:
ARemoteControlUnit,theECA30,canbeconnectedinorderto
controltheECLcontrollerremotely.
Aconnectedfloworenergymeter(inECLComfort210itisbased
onpulsesignalsandinECLComfort310basedonM-bussignal)
canlimitthefloworenergytoasetmaximum.
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In
ECLComfort310theM-busdatacanfurthermorebetransferred
totheModbuscommunication.
Alarmrelay(inECLComfort210itisR4andinECLComfort310R6)
canbeactivatediftheactualflowtemperatureatS3differsfrom
thedesiredDHWchargingtemperature.
A217.1/A317.1examplea:
A217.1/A317.1exampleb:
A217.1/A317.1examplec:
A217.1/A317.1exampled:
A217.1/A317.1examplee:
6|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Thetwoapplications,A217.2/A317.2arealmostidentical.
However,A317.2hassomeextrafunctionswhicharedescribed
separately.
TheapplicationsA217.2/A317.2areveryflexible.Thesearethe
basicprinciples:
DomesticHotWater(DHW):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS6).
TheDHWheatingtemperaturesensorS3andthecharging
temperaturesensorS4arethemostimportantsensors.
IfthemeasuredDHWtemperature(S6)getslowerthanthedesired
DHWtemperature,theDHWheatingpump(P1)isswitchedON.The
motorizedcontrolvalve(M1)iscontrolledinordertomaintainthe
DHWheatingtemperatureatS3.TheDHWheatingtemperatureis
determinedbythedesiredDHWchargingtemperatureatS4.
WhentheDHWheatingtemperatureisreached,theDHWcharging
pumpP2isswitchedON.
IftheDHWchargingtemperatureatS4cannotbereached,the
ECLcontrollergraduallyincreasesthedesiredDHWheating
temperatureatS3inordertoobtainthechargingtemperature.
Amax.valuecanbeset.
TheDHWchargingtemperatureatS4istypically5–10degrees
higherthanthedesiredDHWtemperature.
DHWtankwith1temperaturesensor(S6):
IfthemeasuredDHWtemperature(S6)getshigherthanthedesired
DHWtemperature,theDHWheatingpump(P1)andtheDHW
chargingpump(P2)areswitchedOFF.Thepost-runtimecanbeset.
DHWtankwith2temperaturesensors(S6andS8):
IfthemeasuredDHWtemperature(S6)getshigherthanthe
desiredDHWtemperatureandthelowertemperature(atS8)gets
higherthanthecut-outtemperature,theDHWheatingpump(P1)
andtheDHWchargingpump(P2)areswitchedOFF.Thepost-run
timecanbeset.
InchargingapplicationstheDHWcirculationcanbethrough
theDHWtank(connectionA)orthroughtheheat-exchanger
(connectionB).
ThesolutionwithconnectionAresultsinclosingofthemotorized
controlvalveaftertheDHWtankchargingprocedure.
ThesolutionwithconnectionBisusedtocompensatefortheheat
lossintheDHWcirculationpipe.
Furthermore,afterDHWtankcharging,thecirculationtemperature
(atS4)iscontrolledaccordingtothedesiredDHWtemperature.
TypicalA217.2./A317.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
DHWheatingtemperaturesensor
S4
DHWchargingtemperaturesensor
S5Returntemperaturesensor
S6
DHWtanktemperaturesensor,upper
S8
DHWtanktemperaturesensor,lower
P1
DHWheatingpump
P2
DHWchargingpump
P3
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
VI.LG.U3.02
©Danfoss|2018.03|7
OperatingGuideECLComfort210/296/310,applicationA217/A317
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredchargingtemperaturecanbe
adjusted(typicallytoalowervalue),thusresultinginagradual
closingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thesupplytemperature,S2,isusedforadjustingtheproportional
band(Xp)inordertogiveastabletemperaturecontrol.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periodsperday.
ApplicationA217.2(usedinECLComfort210)/A317.2(usedin
ECLComfort310)ingeneral:
ARemoteControlUnit,theECA30,canbeconnectedinorderto
controltheECLcontrollerremotely.
Aconnectedfloworenergymeter(inECLComfort210itisbased
onpulsesignalsandinECLComfort310basedonM-bussignal)
canlimitthefloworenergytoasetmaximum.
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In
ECLComfort310theM-busdatacanfurthermorebetransferred
totheModbuscommunication.
Alarmrelay(inECLComfort210itisR4andinECLComfort310R6)
canbeactivatediftheactualflowtemperatureatS3differsfrom
thedesiredDHWheatingtemperature.
A217.2/A317.2examplea:
A217.2/A317.2exampleb:
8|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
TheapplicationA217.3isveryflexible.Thesearethebasic
principles:
DomesticHotWater(DHW),examplea:
Bymeansofaweekschedulee(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS3).The
DHWtemperaturesensorS3isthemostimportantsensor.
IfthemeasuredDHWtemperature(S3)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue)thusresultinginagradualclosingofthe
motorizedcontrolvalve,i.e.thereturntemperaturewilldecrease.
Thecirculationpump,P1,iscontrolledbymeansofaseparateweek
schedule(upto3‘Comfortperiods/day).
IfasupplytemperaturesensorS2isconnected,theproportional
bandXpisadaptedtotheactualsupplytemperatureinorderto
avoidcontrolinstability.
TypicalA217.3application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
DHWsupplytemperaturesensor
S5Returntemperaturesensor
S8
(Flowswitchexamplesb,c,d)
P1
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
VI.LG.U3.02
©Danfoss|2018.03|9
OperatingGuideECLComfort210/296/310,applicationA217/A317
Exampleb:
Aflowswitchsignal(S8)canbeappliedinordertoheattheDHW
ondemand(DHWtapping/DHWdraw-off).Anidletemperature
forthesupplytemperature(atS2)canbemaintainedtominimize
theheat-uptimefortheDHW.
Examplec:
Aflowswitchsignal(S8)canbeappliedinordertoheattheDHW
ondemand(DHWtapping/DHWdraw-off).Thetemperatureat
S3ismaintainedduringthecomforttimesofthecirculationpump
P1.Anidletemperatureforthesupplytemperature(atS2)canbe
maintainedtominimizetheheat-uptimefortheDHW.
Exampled:
TheDHWtankisdirectlyheated.Thesettingofthereturn
temperaturelimitation(atS5)canavoidatoohighflowinthe
heatingcoil.Anidletemperatureforthesupplytemperature(at
S2)canbemaintainedtominimizetheheat-uptimefortheDHW.
A217.3examplea:
A217.3exampleb:
A217.3examplec:
A217.3exampled:
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
10|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
VI.LG.U3.02
©Danfoss|2018.03|11
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
12|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
VI.LG.U3.02
©Danfoss|2018.03|13
OperatingGuideECLComfort210/296/310,applicationA217/A317
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
14|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
VI.LG.U3.02
©Danfoss|2018.03|15
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturers
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturers
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
16|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
VI.LG.U3.02
©Danfoss|2018.03|17
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
18|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
relay)terminals
0,2A/230Va.c.
VI.LG.U3.02
©Danfoss|2018.03|19
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/24Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
relay)terminals
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power
suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230
Va.c.from24Va.c.
20|©Danfoss|2018.03
VI.LG.U3.02
OperatingGuideECLComfort210/296/310,applicationA217/A317
/