High voltage warning
The voltage of the frequency converter is
dangerous whenever the converter is con-
nected to mains. Incorrect fitting of the
motor or frequency converter may cause
damage to the equipment, serious injury
or death. Consequently, it is essential to
comply with the instructions in this manual
as well as local and national rules and
safety regulations.
The Protective Extra Low Voltage (PELV)
requirements stated in IEC 61800-5-1 are
not fulfilled at altitudes above 2000 m
(6562 ft.). For 200V frequency converters
the requirements are not fulfilled at alti-
tudes above 5000 m (16 404 ft.). Please
contact Danfoss Drives for further infor-
mation.
These rules concern your safety.
1. The adjustable frequency drive must be dis-
connected from AC line if repair work is to be
carried out. Ensure that the line supply has
been disconnected and that the prescribed
time has passed before removing motor and
AC line plugs.
2. The [STOP/RESET] key on the control panel
of the adjustable frequency drive
does not
disconnect the equipment from line power
and is therefore not to be used as a safety
switch.
3. The unit must be properly grounded, the user
must be protected against the supply voltage,
and the motor must be protected against
overloading in accordance with prevailing na-
tional and local regulations.
4. The ground leakage currents are higher than
3.5 mA.
5. Protection against motor overload is not in-
cluded in the factory setting. If this function is
required, set parameter 128 Motor thermal
protection to data value ETR trip or data value
ETR warning. For the North American market:
The ETR functions provide overload protec-
tion of the motor, class 20, in accordance with
NEC.
6. Do
not remove either the plugs for the motor
or line supply while the adjustable frequency
drive is connected to line power. Ensure that
the line supply has been disconnected and
that the prescribed time has passed before
removing motor and AC line plugs.
7. Note that the adjustable frequency drive has
more voltage inputs than L1, L2 and L3 when
the DC bus terminals are used. Check that all
voltage inputs are disconnected and that the
prescribed time has passed before repair
work is commenced.
Warning against unintended start
1. The motor can be brought to a stop by means
of digital commands, bus commands, refer-
ences or a local stop, while the frequency
converter is connected to mains. If personal
safety considerations make it necessary to
ensure that no unintended start occurs,
these
stop functions are not sufficient.
2. While parameters are being changed, the
motor may start. Consequently,
the stop key
[STOP/RESET] must always be activated,
following which data can be modified.
3. A motor that has been stopped may start if
faults occur in the electronics of the frequen-
cy converter, or if a temporary overload or a
fault in the supply mains or the motor con-
nection ceases.
VLT
®
2800 Series
4 MG.27.A2.22 - VLT
®
is a registered Danfoss trademark