Digital Monitoring Products XF6 Installation & Programming Guides

Type
Installation & Programming Guides
DIGITAL MONITORING PRODUCTS, INC.
INSTALLATION AND PROGRAMMING GUIDE
FIELD TEST
B XF6 SERIES INSTALLATION AND PROGRAMMING GUIDE | DIGITAL MONITORING PRODUCTS
FIELD TEST
MODEL XF6 SERIES
Contains installation and programming Instructions for use with the
Model XF6 Series Fire Control Panels.
When using the XF6 Series panel for any listing organization’s approved methods, refer to the Compliance
Listing Guide (LT-2779). This document outlines the installation and programming requirements of all
applications for which XF6 Series control panels are approved.
© 2023 Digital Monitoring Products, Inc.
Information furnished by DMP is believed to be accurate and reliable.
This information is subject to change without notice.
XF6 INSTALLATION AND PROGRAMMING GUIDE | DIGITAL MONITORING PRODUCTS I
FIELD TEST
FIELD TEST
ABOUT THE PANEL ................................1
Zone Expansion ................................................................... 1
Output Expansion ............................................................... 1
SPECIFICATIONS SUMMARY ................2
Power Supply ........................................................................ 2
Communication .................................................................... 2
Panel Zones ........................................................................... 2
Keypad Bus ............................................................................ 2
LX-Bus ..................................................................................... 2
Outputs ................................................................................... 2
SYSTEM COMPONENTS .........................3
Lightning Protection .......................................................... 3
INSTALL THE PANEL ..............................4
Mount the Enclosure .......................................................... 4
Fire Command LCD Keypad ........................................... 5
Mounting Additional Keypads, Zone Expanders, and
Modules ................................................................................... 5
WIRE THE PANEL ...................................6
Wiring Specifications ......................................................... 6
Wire the Transformer ......................................................... 6
Wire the Batteries ............................................................... 6
Power Requirements .......................................................... 7
Standby Battery Selection ............................................... 8
LX-Bus Expansion ............................................................... 10
Wireless Bus Expansion .................................................... 10
Ethernet Connection .......................................................... 10
RESET and TAMPER Headers ......................................... 10
Bell Output ............................................................................. 11
Keypad Bus ............................................................................ 11
Smoke Output ...................................................................... 11
Dry Contact Relay Outputs ............................................. 13
Annunciator Outputs ......................................................... 13
ORDERING INFORMATION ...................14
Accessories ............................................................................ 14
PROGRAMMING ......................................17
XF6 Programming Information ...................................... 17
Getting Started .................................................................... 17
Accessing the user menu ................................................. 17
Programmer Operation ..................................................... 17
Reset Timeout ...................................................................... 18
Keypads .................................................................................. 18
Special Keys........................................................................... 18
Entering Alpha Characters .............................................. 19
Entering Non-Alpha Characters .................................... 19
Keypad Displays Current Programming ..................... 19
INITIALIZATION ......................................20
Initialization ........................................................................... 20
Clear All Memory ................................................................. 20
Clear All Codes ..................................................................... 20
Clear Display Events Memory ......................................... 20
Clear Zone Information ..................................................... 20
Clear Output Information ................................................. 20
Clear Communication and Remote Options ............. 20
Set to Factory Defaults ..................................................... 20
COMMUNICATION ..................................21
Communication .................................................................... 21
Account Number ................................................................. 21
Communication Path ......................................................... 21
Communication Type ......................................................... 21
Test Report ............................................................................ 21
Test Time ................................................................................. 21
Check In .................................................................................. 21
Fail Time .................................................................................. 22
Receiver IP ............................................................................. 22
Receiver Port ........................................................................ 22
Fail Test Hours ...................................................................... 22
Protocol ................................................................................... 22
II XF6 SERIES INSTALLATION AND PROGRAMMING GUIDE | DIGITAL MONITORING PRODUCTS
FIELD TEST
Retry Seconds ...................................................................... 22
Duplicate Alarms ................................................................. 22
Send Path Information ...................................................... 22
NETWORK OPTIONS .............................. 23
DHCP ........................................................................................ 23
Local IP Address ................................................................. 23
Gateway Address ................................................................ 23
Subnet Mask .......................................................................... 23
DNS Server............................................................................. 23
DEVICE SETUP ........................................24
Device Setup ......................................................................... 24
Device Number .................................................................... 24
Device Name ......................................................................... 24
Device Type ........................................................................... 24
REMOTE OPTIONS .................................25
Remote Options ................................................................... 25
Cell APN .................................................................................. 25
Entré Connection ................................................................ 25
Entré Incoming TCP Port.................................................. 25
Entré IP Address .................................................................. 25
Entré Outbound TCP Port ................................................ 25
Entré Backup Connection ................................................ 25
Entré Backup TCP Port ..................................................... 25
Entre Reports ........................................................................ 25
User Command Reports ................................................... 26
Supervisory Reports .......................................................... 26
Entré Passphrase ................................................................. 26
Integrator Connection ....................................................... 26
Integrator Incoming TCP Port ........................................ 26
Integrator IP Address ......................................................... 26
Integrator Outbound TCP Port ...................................... 26
Integrator Backup Connection ....................................... 26
Integrator Backup TCP Port ............................................ 26
Integrator Reports .............................................................. 26
Zone Reports ........................................................................ 27
User Command Reports ................................................... 27
Supervisory Reports .......................................................... 27
Integrator Passphrase ........................................................ 27
App Key .................................................................................. 27
SYSTEM OPTIONS ..................................28
System Options .................................................................... 28
Cross Zone Time .................................................................. 28
Zone Retard Delay .............................................................. 28
Power Fail Delay .................................................................. 28
Swinger Bypass Trips ......................................................... 28
Time Changes ....................................................................... 28
Latch Supervisory Zones.................................................. 29
Programming Menu Language....................................... 29
Detect Wireless Jamming ................................................ 29
Wireless Encryption ........................................................... 30
Enter Passphrase ................................................................. 30
Trouble Audible Annunciation ....................................... 30
Bell Options ........................................................................... 31
Bell Options ........................................................................... 31
Bell Cuto Time ................................................................... 31
NAC 1 Sync Protocol .......................................................... 31
NAC 2 Sync Protocol ......................................................... 31
Selective Silence .................................................................. 31
Bell Output ............................................................................. 31
Bell Action .............................................................................. 31
Fire Bell Action ..................................................................... 31
Supervisory Bell Action .................................................... 31
Carbon Monoxide (CO) ..................................................... 31
OUTPUT OPTIONS ..................................32
Output Options .................................................................... 32
Cuto Output ....................................................................... 32
Output Cuto Time ............................................................ 32
Communication Trouble Output ................................... 32
Fire Alarm Output ............................................................... 32
Fire Trouble Output ............................................................ 32
XF6 INSTALLATION AND PROGRAMMING GUIDE | DIGITAL MONITORING PRODUCTS III
FIELD TEST
FIELD TEST
Device Fail Output .............................................................. 32
Sensor Reset Output ......................................................... 33
Supervisory Alarm Output .............................................. 33
AC Fail Output ...................................................................... 33
Carbon Monoxide Alarm Output ................................... 33
Output Information ............................................................ 34
Output Number .................................................................... 34
Output Name ........................................................................ 34
Output Real-Time Status .................................................. 34
Output Groups ..................................................................... 35
Group Number...................................................................... 35
Group Name .......................................................................... 35
Output Number .................................................................... 35
ZONE INFORMATION .............................36
Zone Information ................................................................. 36
Zone Number ........................................................................ 36
Zone Name ............................................................................ 36
Fire Bell Output .................................................................... 37
Expander Serial Number .................................................. 37
Next Zone ............................................................................... 37
Wireless ................................................................................... 37
Serial Number Entry ........................................................... 37
Contact .................................................................................... 37
Supervision Time ................................................................. 38
Alarm Action ......................................................................... 38
Output Number .................................................................... 38
Output Action ....................................................................... 38
Swinger Bypass .................................................................... 39
Zone Retard Delay .............................................................. 39
Presignal Keypad Addresses .......................................... 39
Fast Response ...................................................................... 39
Fire Panel Slave Input ........................................................ 39
STOP .........................................................40
Stop .......................................................................................... 40
SET LOCKOUT CODE .............................41
Set Lockout Code ............................................................... 41
APPENDIX................................................42
Diagnostics Function ......................................................... 42
Using the Walk Test ............................................................ 44
Walk Test ................................................................................ 44
Zone Types ............................................................................ 44
Trip Counter For Walk Test .............................................. 44
Trip Counter For DMP Wireless Check-in Test (WLS)
45
Test End Warning ................................................................ 45
Keypad Speaker Operation ............................................. 45
Wireless Check-in and Supervision Definitions ....... 46
Zone Type Descriptions .................................................... 46
Common Keypad Messages ............................................ 47
FCC INFORMATION ................................48
Part15 ...................................................................................... 48
XF6 Series Installation and Programming Guide Digital Monitoring Products
1
FIELD TEST
ABOUT THE PANEL
The DMP XF6 Series system consists of an alarm panel with a built-in communicator, an enclosure with built-in Graphic
Fire Command keypad, and a 24 VDC 130 VAC transformer. A complete system can provide:
142 or 574 programmable inputs and outputs for commercial and industrial fire alarm service
Six onboard grounded zones, 2 NAC circuits
The powered zones have a reset capability to provide for2-wire smoke detectors, relays, or other latching devices.
Addressable smoke detectors and input modules round out the XF6 Series Series panel to deliver a truly flexible and
expansive fire detection and notification system. The Fire Alarm Control Panel is shipped pre-wired in a red steel
enclosure.
ZONE EXPANSION
Up to574additional zones are available on the XF6 Series Series panel using DMP LCD keypad remote zone capability
and zone expansion modules. The panel keypad data bus supports up to fifteen supervised device addresses with each
address supporting up to four programmable expansion zones.
Up to500zones are available using the on board LX-Bus connections, along with any combination of single, four, eight,
or sixteen-zone expansion modules and single-zone LX-Bus detectors.
OUTPUT EXPANSION
In addition to the two SPDT relays and four programmable open collector outputs on the panel, you can also connect up
to25programmable Model716Output Expansion Modules to each LX-Bus. These modules can provide an additional 100
or 500 programmable SPDT relays.
SPECIFICATIONS SUMMARY
For a full list of compatible panel accessories, refer to "Ordering Information".
POWER SUPPLY
Transformer Input—Primary input: 130VAC 60Hz; Primary Output: 24 VDC
Standby Battery—24VDC (Two 12V batteries wired in series), XXAmps Max. charging current
Smoke and Auxiliary—24VDC output at 0.5Amp Max (not shared)
NAC Circuit  and NAC Circuit —24VDC at 0.7Amp Max
The combined Auxiliary and Bell outputs total cannot exceedXXAmps. All circuits are power limited except the red
battery wire and AC terminal.
COMMUNICATION
Built-in network communication to SCS-1R and SCS-VR Receivers
Optional cellular communication to SCS-1R and SCS-VR Receivers
Can operate as a local panel
PANEL ZONES
Six3.3k Ohm EOL powered zones with reset (1-6).
KEYPAD BUS
You can connect the following supervised keypads and expansion modules to the Keypad Bus:
Alphanumeric keypads
Sixteen, eight, four, and single-zone expansion modules
Single zone detectors
LX-BUS
You can connect the following devices to the LX-Bus connections provided on the panel. See Accessory Devices for
information about specific connections.
Sixteen, eight, four, and single-zone expansion modules
Relay output expansion modules
Smoke Detectors
OUTPUTS
The XF6 Series Series panel provides two Single Pole, Double Throw (SPDT) relay outputs which require the installation
of two Model305relays, each rated1Amp at30VDC resistive (power limited sources only). A Model431Output
Harness is required to use these outputs.
The panel also provides four open collector outputs rated for50mA each. The open collector outputs provide ground
connection for a positive voltage source. A Model300Output Harness is required to use these outputs.
Digital Monitoring Products XF6 Series Installation and Programming Guide
2
PRELIMINARY
XF6 Series Installation and Programming Guide Digital Monitoring Products
3
FIELD TEST
SYSTEM COMPONENTS
The diagram below shows some of the accessory modules you can connect for use in various applications. A brief
description of each module follows in the Accessory Devices section.
LIGHTNING PROTECTION
Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on panel input and output
circuits. Additional surge protection is available with Model370or370RJ Lightning Suppressors. For more information,
refer to the 370/370RJ Installation Sheet (LT-0181).
XF6 Series Wiring Diagram
WARNING: Incorrect connections
may cause damage to the unit.
Listed Resistors
1k Ohm - DMP Model 308
3.3k Ohm - DMP Model 309
Use Listed Power Supervision Relay
rated at 12 VDC.
Smoke
Detector
Zone Expander
Model 715
7 mA @ 12 VDC
Models 715-8, 715-16
20 mA @ 12 VDC
1k Ohm
S
= Supervised Circuit
Zone
5
Zone
6
22 gauge minimum
22 gauge minimum
22 gauge minimum
22 gauge minimum
RED
YELLOW
GREEN
BLACK
Zone Expander
Model 714
7 mA @ 12 VDC
Models 714-8, 714-16
20 mA @ 12 VDC
RED
YELLOW
GREEN
BLACK
ss
s s s s
ss
S S S S S S S S
S S S S
S S
S SS SS S
Zone
Expander
Model 711
or 711S
7mA @ 12
VDC
J1
Ethernet
AUXILIARY/SMOKE POWER
AUXILIARY/SMOKE GROUND
1k Ohm 1k Ohm 1k Ohm 1k Ohm
RED
BLACK
Zone
1
S S
Zone
2
S S
Zone
3
S S
Zone
4
S S
All zones use 3.3k Ohm Resistors
All zones use 3.3k Ohm Resistors
AC AC B+ B- AUX GND RED YEL GRN BLK SMK GND NAC1+ NAC1- NAC2+ NAC2- Z1+ Z1- Z2+ Z2- Z3+ Z3- Z4+ Z4- Z5+ Z5- Z6+ Z6-
Cell Module
Ethernet
RESET
LOAD
PROG LX600 LX700 LX800 LX900
LX500
BAT T STAR T
TAMPER
OUTPUT 1 OUTPUT 2
XBUS
EXP
XF6 Series Panel
To pre-installed 130 VA power
supply
24 VDC Connections
12 VDC Connections
The XF6-100 only
contains one
LX-Bus connection
3.3k Ohm EOL
CAUTION: DO NOT USE LOOPED WIRE UNDER
TERMINALS. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
Using verification
delays is optional. Use
the delays marked on
the smoke detectors.
Intended Installation Environment - Indoor/Dry
All Circuits:
Impedance value for testing at
which open circuit faults, short
circuit faults, and ground faults
prevent normal operation.
Open - Infinite
Shorts - 0.1 Ohms
Ground - 0.1 Ohms
The maximum voltage
drop between the panel
Bell Output and the Model
308 EOL is 1 VDC when a
separate power supply is
not used.
7830F Keypad
130 VA 24 VAC wire-in
transformer
NAC Circuit:
Supervised, Regulated, Power
Limited Battery Backup
Maximum output current:
XXXXXXX
Smoke Power:
Supervised, Power Limited
Battery Backup
24 VDC nominal rated voltage
XXXXXXX
Battery Circuit:
XXXXXXX
XXXXXXX
Form C Relays
Programmable
3.0 VDC, 1 A, 0.35 power
factor, Resistive, Power
Limited
The relay contacts must be
connected to devices located
within the same room as the
panel.
All circuits are inherent Power
Limited except the red battery
wire and AC terminal.
Recommended panel
enclosure mounting:
Allow approx. 3 feet for door
clearance.
Top of panel enclosure should
be a minimum of 5 feet from
floor
Digital Monitoring Products XF6 Series Installation and Programming Guide
4
FIELD TEST
INSTALL THE PANEL
MOUNT THE ENCLOSURE
The XF6 Series Series panel enclosure must be mounted using the four mounting holes shown in the image below.
Mount the enclosure in a secure, dry place to protect the panel from damage from tampering or the elements. It is not
necessary to remove the panel PCB when installing the enclosure.
The enclosure dimensions are13.44” H X17.1” W X4.8” D.
Note When using the XF Series Series panel for listed applications use the Model  orS enclosure for
standby batteries
Battery shelf holds up to two batteries. Maintain
minimum spacing of 1/4” between the batteries
and any modules mounted in enclosure.
A
B
C
Panel
Transformer
Enclosure Mounting Holes
D
E
Dual 1-3/4” and 1-3/8” Knockouts
Module Mounting Holes
FBattery Shelf
E
E
E
DD
C C
C C
A
F
B
GGround
G
XF6 Series Installation and Programming Guide Digital Monitoring Products
5
FIELD TEST
FIRE COMMAND LCD KEYPAD
A 7830F Fire Command Keypad is factory installed on the panel enclosure door. The display and keyboard are factory
pre-wired to the PROG header. For standby battery calculations, the LCD display drawsXXmA of current in normal,
standby, or alarm condition. For more information, refer to "Power Requirements".
Additional 7830F keypads can be added as needed.
MOUNTING ADDITIONAL KEYPADS, ZONE EXPANDERS, AND MODULES
All DMP keypad housings are designed to install on any 4” square box, 3-gang switch box, compatible backboxes, or
directly on a flat surface.
The DMP711, 714, 715, and 716 zone expanders are each contained in molded plastic housings with removable covers. The
base provides you with mounting holes for installing the unit to a wall, switch plate, or other surface.
Mount any additional modules in the panel enclosure using the standard 3-hole mounting pattern. Refer to the
appropriate product guides for installation instructions.













7830F Fire Command Keypad
Digital Monitoring Products XF6 Series Installation and Programming Guide
6
FIELD TEST
WIRE THE PANEL
WIRING SPECIFICATIONS
DMP recommends using 18 or 22 AWG for all LX-Bus and Keypad Bus connections. The maximum wire distance between
any module and the DMP Keypad Bus or LX-Bus circuit is 1,000 feet. To increase the wiring distance, install an auxiliary
power supply, such as a DMP Model 505-12. Maximum voltage drop between a panel or auxiliary power supply and any
device is 2.0 VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of
the circuit.
To maintain auxiliary power integrity when using 22-gauge wire on Keypad Bus circuits, do not exceed 500 feet. When
using 18-gauge wire, do not exceed 1,000 feet. Maximum distance for any bus circuit is 2,500 feet regardless of wire
gauge. Each 2,500 foot bus circuit supports a maximum of 40 LX-Bus devices. To increase the wire length or to add
devices, install an additional power supply that is listed for Fire Protective Signaling, power limited, and regulated
(12VDC nominal) with battery backup.
For additional information refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031) and the 710 Bus Splitter/
Repeater Module Installation Guide (LT-0310).
WIRE THE TRANSFORMER
The XF6 Series Series panel comes with a24 VDC 130VA transformer. Thetransformer must be wired to a dedicated,
unswitched120VAC60Hz circuit with at least 0.87Amps available.
Caution Never share the Fire Alarm Control Panel circuit with any other equipment. Always ground the panel before
applying power to any devices and use  AWG or larger for all power connections
WIRE THE BATTERIES
DMP recommends replacing batteries every3to5years under normal use. Connect the black battery lead to the
negative battery terminal. Connect the red battery lead to the battery positive terminal. The batteries will need to be
wired in series, meaning the black and red leads will be connected to dierent batteries with a wire in between
connecting the two.
Caution The XF6 Series panel requires two 12 V backup batteries wired in series It cannot be powered by a single
 V backup battery
For listed installations, batteries can be installed in a DMP Model349, 350or352S enclosure and all wiring shall run
through conduit. The enclosure shall be installed to the left of the panel enclosure to ensure Battery and AC wire
separation.
Caution Use sealed lead-acid batteries only. Batteries supplied by DMP have been tested to ensure proper charging
with DMP products. Do not use gel cell batteries.
Battery Only Restart
When powering up the XF6 Series Series
panel without AC power, briefly short the
battery start pads to pull in the battery cuto
relay. Once the relay has been pulled in, the
battery voltage holds it in that condition.
If the panel is powered up with an AC
transformer, the battery cuto relay is pulled
in automatically.
Discharge/Recharge
The XF6 Series Series panel battery charging
circuit float charges at13.9VDC at a
maximum current of1.0Amps using a56VA
transformer. Battery voltage level conditions
are determined by the following voltage
ranges:
AC
1 2 3 4
+BAC –B
Battery
Start
Red
Blue
Battery Battery
Red
5 6
AUX GND
To AC
XF6
Panel
To Bell
Circuit
To Earth
Ground
XF6 Series Installation and Programming Guide Digital Monitoring Products
7
FIELD TEST
Battery Trouble—Below11.9VDC
Battery Cuto—Below10.2VDC
Battery RestoredAbove12.6VDC
Battery Supervision
The panel tests the battery when AC power is present. The test is done every three minutes and lasts for five seconds.
During the test, the panel places a load on the battery. If the battery voltage falls below11.9VDC a low battery is
detected. If AC power is not present, a low battery is detected any time the battery voltage falls below11.9VDC. When
battery voltage drops below10.2VDC, the panel performs a battery cuto to prevent deep discharge damage.
If a low battery is detected with AC power present, the test repeats every two minutes until the battery charges
above12.6VDC. If a weak battery is replaced with a fully charged battery, the restored battery will not be detected until
the next test is completed.
POWER REQUIREMENTS
During AC power failure, the XF6 Series panel and all connected auxiliary devices draw their power from the battery. All
devices must be taken into consideration when calculating the battery standby capacity. The following table lists the
XF6 Series panel power requirements. You must add the additional current draw of keypads, zone expansion modules,
smoke detector output, and any other auxiliary devices used in the system for the total current required. The total is then
multiplied by the number of standby hours required to calculate the total ampere-hours required.
Standby Battery Power Calculations Standby Current Alarm Current
XF6 Series Fire Control Panel
Relay Outputs (ON)
Switch Grounds (ON)
Active Zones
Active Zones
2-Wire Smoke Detectors
Panel Bell Output
Qty 1
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
x mA
mA
mA
mA
mA
mA
mA
______
______
______
______
______
Qty 1
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
x mA
mA
mA
mA*
mA
mA
mA
mA
______
______
______
______
______
______mA
263LTE Cellular Communicator
Qty _______ x 13mA ______ Qty _______ x 13mA ______
1100X Wireless Receiver Qty _______ x 46mA ______ Qty _______ x 46mA ______
1100XH Wireless High Power Receiver Qty _______ x 160mA ______ Qty _______ x 160mA ______
860 Relay Output Module (one relay active)
All four relays active
Qty _______ x 34mA
138mA
______
______
Qty _______ x 34mA
138mA
______
______
865 Style Y or Z Notification Module Qty _______ x 26mA ______ Qty _______ x 85mA ______
866 Style W Notification Module Qty _______ x 45mA ______ Qty _______ x 76mA ______
867 LX-Bus Style W Notification Module Qty _______ x 30mA ______ Qty _______ x 86mA ______
869 Dual Style D Initiating Module Qty _______ x 25mA ______ Qty _______ x 75mA ______
7830F Fire Command Keypad Qty _______ x 85mA
1.6mA
______
______
Qty _______
Qty _______
x
x
100mA
2mA*
______
______
630F Remote Fire Command Center Qty _______ x 63mA ______ Qty _______ x 92mA ______
7070/7170 Thinline/7070A Aqualite Keypad
Active Zones (EOL Installed)
Qty _______ x 72mA
1.6mA
______
______
Qty _______
Qty _______
x
x
87mA
2mA*
______
______
7073/7173 Thinline/7073A Aqualite Keypad
Active Zones (EOL Installed)
Qty _______ x 85mA
1.6mA
______
______
Qty _______
Qty _______
x
x
100mA
2mA*
______
______
Copy Sub-Totals to next page Sub-Total Standby ______ mA Sub-Total Alarm
______ mA
*Based on 10% of active zones in alarm.
Digital Monitoring Products XF6 Series Installation and Programming Guide
8
FIELD TEST
Standby Battery Power Calculations Standby Current Alarm Current
736P POPIT Interface Module
Radionics Popex, POPITs, OctoPOPITs
Qty _______
Qty _______
x
x
25 mA
___mA
______
______
Qty _______
Qty _______
x
x
25 mA
___mA
______
______
710 Bus Splitter/Repeater Module Qty _______ x 32 mA ______ Qty _______ x 32 mA ______
711/711S Zone Expansion Module
Active Zone (EOL Installed)
Qty _______
Qty _______
x
x
11 mA
1.6 mA
______
______
Qty _______
Qty _______
x
x
11 mA
2 mA*
______
______
714 Zone Expansion Module
Active Zones (EOL Installed)
Qty _______
Qty _______
x
x
7 mA
1.6 mA
______
______
Qty _______
Qty _______
x
x
7 mA
2 mA*
______
______
714-8, 714-16 Zone Expansion Module
Active Zones (EOL Installed)
Qty _______
Qty _______
x
x
20 mA
1.6mA
______
______
Qty _______
Qty _______
x
x
20 mA
2 mA*
______
______
715 Zone Expansion Module
Active Zones (EOL Installed)
2-Wire Smokes
Qty _______
Qty _______
Qty _______
x
x
x
7 mA
4 mA
.1 mA
______
______
______
Qty _______
Qty _______
Qty _______
x
x
x
7 mA
30 mA*
.1 mA
______
______
______
715-8, 715-16 Zone Expansion Modules
Active Zones (EOL Installed)
2-Wire Smokes
Qty _______
Qty _______
Qty _______
x
x
x
20 mA
4 mA
.1 mA
______
______
______
Qty _______
Qty _______
Qty _______
x
x
x
20 mA
30 mA*
.1 mA
______
______
______
716 Output Expansion Module
Active Form C Relays
Qty _______ x 7 mA ______ Qty _______
Qty _______
x
x
7 mA
28 mA
______
______
2W-BLX, 2WT-BLX Smoke Detectors Qty _______ x 11 mA ______ Qty _______ x 31 mA* ______
COSMOD2W Module Qty _______ x 45 mA ______ Qty _______ x 174mA*# ______
COSMO-2W Smoke and CO Detectors Qty _______ x 1 mA ______ Qty _______ x 50 mA*# ______
572 Indicator LED Qty _______ x 20 mA ______ Qty _______ x 20 mA ______
Aux. Powered Devices on Terminals 7 and 11
Other than Keypads and LX-Bus Modules
______mA ______mA
Sub-Totals this page Sub-Total Standby ______ mA Sub-Total Alarm ______mA
Sub-Totals from previous page Sub-Total Standby ______ mA Sub-Total Alarm ______mA
*Based on 10% of active zones in alarm Total Standby ______ mA Total Alarm ______mA
# For systems that are not Central Station monitored, multiply alarm current by 12.
Total Standby ______ mA x number of Standby Hours needed _____= _____ mA-hours
ULC S559 requires 24 hours of standby.
Total Alarm ______ mA x number of Alarm Hours needed _____ = _____ mA-hours
UL 864 requires 5 minutes (.0833 hours) in Alarm Total _____ mA-hours
ULC S559 requires 30 minutes (.5 hours) in Alarm X .001
Add 10% for battery derating = _____ Amp-hrs Required
Based on10% of active zones in alarm.
2 For systems that are not central station monitored, multiply alarm current by12.
1 Based on10% of active zones in alarm.
2 For systems that are not central station monitored, multiply alarm current by12.
* Where h = hours of alarm. For example, a 15 minute alarm = 0.25 h.
STANDBY BATTERY SELECTION
To choose the type and number of batteries needed for 24, 60, or 72 hours of standby power based on the Amp Hours
Required calculation, perform the following:
Select the desired standby hours required from the table below: 24, 60, or 72 hours
Select the desired battery size: Model 368 (12 VDC 5.0 Ah), Model 369 (12 VDC 7 Ah), Model 365 (12 VDC 9 Ah),
Model 366 (12 VDC 18 Ah),
Select a Max. Ah Available number that is just greater than the number calculated in Amp Hours Required.
Install the number of batteries shown in the corresponding No. of Batteries required column.
XF6 Series Installation and Programming Guide Digital Monitoring Products
9
FIELD TEST
For listed installations, batteries can be installed in a DMP Model 349, 350 or 352S enclosure and all wiring shall run
through conduit. The enclosure shall be installed to the left of the XF6 Series enclosure to ensure Battery and AC wire
separation.
24 HOURS OF STANDBY POWER
5.0 Ah Batteries 7 Ah Batteries 7.7 Ah Batteries 9 Ah Batteries 18 Ah Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
8 2 6 1 6 1 8 1 16 1
12 3 12 2 13 2 16 2 32 2
16 4 18 3 20 3 24 3 48 3
20 5 24 427 4 32 4
24 6 31 5 34 5 40 5
28 7 37 641 6
32 8 43 7
36 9 48 hours is the typical battery recharge time for any of the Number of Batteries shown in this section.
40 10
60 HOURS OF STANDBY POWER
7 Ah Batteries 7.7 Ah Batteries 9 Ah Batteries 18 Ah Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
13 2 14 2 17 2 17 1
20 3 22 3 26 3 34 2
27 4 29 4 34 4 52 3
33 5 37 5 43 5 69 4
40 6 44 6 52 6
47 752 761 7 48 hours is the typical battery recharge time for
any of the Number of Batteries shown in this
section.
54 8 59 869 8
60 9 67 9
67 10
72 HOURS OF STANDBY POWER
9 Ah Batteries 18 Ah Batteries
Max. Ah
Available
No. of
Batteries
Max. Ah
Available
No. of
Batteries
16 2 16 1
25 3 33 2
33 4 50 3
42 5 67 4
50 6
59 7 72 hours is the typical battery recharge time required for any of the Number of Batteries shown in this
section.
67 8
If the Amp Hours Required calculation is greater than any Max. Ah Available number shown on a table, then add power
supply(s) to power some system devices allowing the Amp Hours Required calculation to be reduced. See the 710 Bus
Splitter/Repeater Installation Guide (LT-0310).
Digital Monitoring Products XF6 Series Installation and Programming Guide
10
FIELD TEST
LX-BUS EXPANSION
There are five 12 VDC LX-Bus headers near the bottom of the panel:
LX500 provides zones500-599 (XF6 Series)
LX600 provides zones600-699 (XF6-500 Series only)
LX700 provides zones700-799 (XF6-500 Series only)
LX800 provides zones800-899 (XF6-500 Series only)
LX900 provides zones900-999 (XF6-500 Series only)
WIRELESS BUS EXPANSION
The Wireless Bus (XBUS) header provides connection for the1100X or1100XH Wireless Receiver. The XBUS provides up
to500wireless zones numbered500-999. Refer to the1100X Wireless Receiver Install Guide (LT-1822) or the1100XH
Wireless Receiver Install Guide (LT-1823) for complete information.
XF6-100provides up to100zones.
XF6-500provides up to500zones.
Wireless Bus LEDs
The two LEDs, located above the XBUS header, indicate data transmission and receipt. The left LED flashes green to
indicate the panel is transmitting data. The right LED flashes yellow to indicate the panel is receiving data.
ETHERNET CONNECTION
Description
The ETHERNET connector on the XF6 Series Series panel allows you to connect directly to an Ethernet network using a
standard Cat 5 cable. The ETHERNET connector supports100Mbps full duplex operation and the maximum impedance
is100Ohms.
Ethernet LEDs
The two LEDs located on the top edge of the connector indicate network connection. The right Link LED (green) lights
to indicate a valid receive connection from the host network. The Activity LED (yellow) lights when connected to a 100
Mbps network and is o when connected to a 10 Mbps network connection.
RESET AND TAMPER HEADERS
RESET Header
The RESET header is used to reset the panel. To reset the panel when installing the system, place the jumper across both
RESET pins before applying power to the panel. After connecting the AC and battery, remove the reset jumper.
To reset the panel while the system is operational,
install the reset jumper without powering down the
system. Remove the reset jumper after one or two
seconds.
After resetting the panel, begin programming
within30minutes. Otherwise, you must reset the
panel again to enter the PROG menu.
TAMPER Header
The TAMPER header is designed to connect to a
tamper switch with a tamper harness. One or more
tamper switches can be mounted inside the panel
enclosure to supervise unauthorized removal or opening of an enclosure. Refer to the wiring diagram on the enclosure
door for correct tamper switch wiring.
XF6 Series Panel Showing the RESET Jumper and Tamper
RESET
LOAD
PROG LX600 LX700 LX800 LX900
LX500
TAMPER
OUTPUT 1 OUTPUT 2
EXP
XF6 Series Panel
XF6 Series Installation and Programming Guide Digital Monitoring Products
11
FIELD TEST
BELL OUTPUT
Terminals5and6
Supplies positive24VDC to power alarm bells or horns. This output can be steady, pulsed, or temporal, depending on
the Bell Action specified in Bell Options. Terminal6is the ground reference for the bell circuit. This supervised output
reads resistance of3.3kOhms or less as normal. The indicating appliance can supply this resistance. If using a horn or
siren, install the included3.3kOhm0.5W resistor across the bell circuit to provide supervision. See the Notification
Appliance section in the Compliance Listing Guide (LT-2779) for wiring diagrams and a list of approved notification
appliances.
KEYPAD BUS
Description
The panel Keypad Bus includes Terminals7, 8, 9, and10. You can connect up to fifteen supervised keypads and multiple
unsupervised keypads to the panel. In addition to DMP keypads, you can also connect any combination of zone
expansion modules. Refer to the specific device installation sheet for the maximum number of Keypad Bus devices. Refer
to the LX-Bus section for more information about LX-Bus expansion.
Terminal7 - RED
Supplies positive and regulated12VDC to power DMP LCD keypads and zone expansion modules. Terminal7also
supplies power for any auxiliary device. The ground reference for Terminal7is Terminal10.
The output current is shared with the smoke power output on Terminal11and zones9and10. Current draw for all
connected devices must not exceed the panel maximum current rating. See Power Supply in the Compliance Listing
Guide (LT-1330) for maximum current in a fire listed application.
Terminal8 - YELLOW
Receives data from keypads and zone expansion modules. It cannot be used for any other purpose.
Terminal9 - GREEN
Transmits data to keypads and zone expansion modules. It cannot be used for any other purpose.
Terminal10 - BLACK
The ground reference for DMP keypads, zone expansion modules, and all auxiliary devices being powered by Terminal7.
Programming (PROG) Connection
A 7830F Fire Command Keypad come pre-installed and is connected to the Programming header of the XF6 Series
panel.
OVC LEDs
The Overcurrent LED (OVC) lights red when the devices connected to the Keypad Bus and LX-Bus draw current that
exceeds the panel rating.
The LEDs turn a steady red when lit. When the OVC LEDs light red, the LX-Buses and Keypad Bus are shut down.
SMOKE OUTPUT
Terminals11and12
Supplies positive and regulated24VDC to power4-wire smoke detectors and other powered devices. This output can
be turned o by the user for5seconds using the Sensor Reset User Menu option to allow latched devices to reset.
Terminal12is the ground reference for Terminal11.
Current Rating
The Output current from Terminal11is shared with Terminals7, 25, and27.
The total current draw of all devices powered from the panel must be included with Terminal11calculations and must not
exceed the maximum output rating.Protection zones
Terminals13-16
Supplies two 1.5 Amp Class B Style Y NAC circuits. Requires 3.3k Ohm EOL resistor.
Terminals17-28
Zones1to6 (Terminals17to28) on the panel are powered zones. For programming purposes, the zone numbers
are1through6. Panel Terminals25through28provide two resettable Class B, Style A, 2-wire powered zones. For
programming purposes the zone numbers are9and10. See the Compliance Listing Guide LT-1330for a list of the
compatible2-wire smoke detectors. Do not mix detectors from dierent manufacturers on the same zone.
Caution Performing a Sensor Reset momentarily drops power to the devices on zones 9 and 10. The panel views
these zones as Open while power is absent.
When wiring powered zones for 2-wire smoke detectors, refer to the following specifications:
Maximum wire length—3000feet (18AWG) or1000feet (22AWG)
Maximum voltage—14VDC
Maximum normal standby current1.25mA DC
Maximum line impedance100Ohms
Maximum short circuit current—56mA
The voltage sensing Terminal measures the voltage across a3.3k Ohm EOL resistor to ground. Use Model309 3.3k Ohm
resistors. Dry contact sensing devices can be used in series (normally-closed) or in parallel (normally-open) with any of
the burglary protection zones.
Operational Parameters
Each protection zone detects three conditions: Open, Normal, and Short.
Zone Response Time
A condition must be present on a zone for500milliseconds before it is detected by the panel. Ensure detection devices
used on the protec tion zones are rated for use with this delay. Zones1-6can also be programmed for a fast response
delay of160milliseconds.
Terminal 13-24 Specifications
Terminal Function Terminal Function
17 Zone1positive 23 Zone4 positive
18 Zone 1 negative 24 Zone 4 negative
19 Zone2positive 25 Zone5 positive
20 Zone2 negative 26 Zone5 negative
21 Zone 3 positive 27 Zone 6 positive
22 Zone3 negative 28 Zone6 negative
Protection Zone Parameters
Condition Resistance on zone Voltage on positive terminal
Open Over1300ohms Over2.0VDC
Normal 600to1300ohms 1.2to2.0VDC
Short Under600ohms Under1.2VDC
Model 431 Output Wiring
Output 1 Output 2
Contact Color Contact Color
Normally Closed Violet Normally Closed Violet with white stripe
Common Gray Common White with gray stripe
Normally Open Orange Normally Open Orange with white stripe
Digital Monitoring Products XF6 Series Installation and Programming Guide
12
PRELIMINARY
XF6 Series Installation and Programming Guide Digital Monitoring Products
13
FIELD TEST
DRY CONTACT RELAY OUTPUTS
The panel provides two programmable auxiliary SPDT relays when equipped with two DMP Model305relays in sockets
OUTPUT1and OUTPUT2and a Model431Output Harness on the OUT1-OUT2 6-pin header. Each relay provides one
SPDT set of contacts that can be operated by any of the functions listed below:
Activation by zone condition—Steady, Pulsing, Momentary, and Follow
Manual activation from the DMP LCD keypad menu
Communication failure
Fire Alarm, Fire Trouble, or Supervisory
Contact Rating
The Model305relay contacts are rated for1Amp at30VDC (allows 0.35power factor). You can connect auxiliary power
to the Relay Output1common terminal by installing the gray harness wire to Terminal7. Current draw for all connected
devices must not exceed the panel maximum current rating.
Model431Output Harness Wiring
The relay contacts are accessible by installing the DMP431Output Harness on the6-pin OUT1 OUT2header.
OUTPUT2uses the top three prongs, and OUTPUT1uses the bottom three prongs. The relay contacts must be
connected to devices located within the same room as the panel. The wire harness colors and contact locations are
shown below:
ANNUNCIATOR OUTPUTS
The four programmable annunciator outputs can be programmed to indicate the activity of the panel zones or
conditions occurring on the system. Annunciator outputs do not provide voltage. Instead, they switch voltage from
another source to ground. The outputs can respond to any of the conditions listed in Dry Contact Relays. Maximum
voltage is30VDC at50mA.
Model300Harness Wiring
Access the open collector outputs by installing DMP300Harness on the4-pin OUTPUTS header. The output locations
are shown below. For listed applications, devices connected to the outputs must be located within the same room as the
panel.
Model860Relay Module
Connect a Model860Relay Module to the OUTPUTS header on the panel to provide relays for outputs3-6. Use these
relays for electrical isolation between the alarm panel and other systems or for switching voltage to control various
functions. Power is supplied to the relay coils from a single wire connected to the panel auxiliary power Terminal7.
The module includes one relay and provides three additional sockets for expansion of up to four relays. Mount
the860inside the panel enclosure using the3-hole pattern and plastic standos. Refer to the860Module Install Sheet
(LT-0484) as needed. Relay Contact Rating is 1Amp at30VDC (allows 0.35power factor).
Digital Monitoring Products XF6 Series Installation and Programming Guide
14
FIELD TEST
ORDERING INFORMATION
Panels
XF6-100 XF6-100Fire Control Panel with Network and Cell
XF6-500 XF6-500Fire Control Panel with Network and Cell
ACCESSORIES
Keypads
7830F-R Fire Command Keypad 32-character touchscreen Fire Command keypad.
ORDER: 7830F-R
630F LCD Remote Fire Command 32-character LCD Fire keypad with keyswitch.
ORDER: 630F-R
Power Supplies
505-12 Power Supply A power-limited, switching power supply that meets UL, CSFM, NFPA and FCC
compliance standards. The 505-12is rated for 12VDC at 5amps maximum.
ORDER: 505-12-R
505-12LX Power Supply A power-limited, switching power supply that meets UL, CSFM, NFPA and FCC
compliance standards. 505-12LX is rated for 12VDC at 5amps maximum. Provides
two independent Class B NAC outputs. Each power supply includes a transformer,
battery leads and a metal enclosure.
ORDER: 505-12LX-G, 505-12LX-R
Batteries and Battery Accessories
Batteries 365 9.0 Ah 12 VDC (ORDER: 365)
366 18.0 Ah 12 VDC (ORDER: 366)
368 5.0 Ah 12 VDC (ORDER: 368)
369 7.0 Ah 12 VDC (ORDER: 369)
349 Medium Enclosure Medium panel enclosure with dual-size knockouts, lock and key, and module
mounting holes. Dimensions: 13.5" W × 11.66" H × 3.55" D
ORDER: 349-G
350 Large Enclosure Holds three 7.7 Ah batteries or two 18.0 Ah batteries and module mounting holes.
Dimensions: 17.5" W × 13.5" H × 3.5" D
ORDER: 350-G, 350-R
352S Extra Large Battery
Enclosure
Features five adjustable shelves to hold batteries for standby power.
Dimensions: 14.5" x 32" x 4" (lid adds 0.5" on each side)
ORDER: 352S-G
Battery Harnesses 318 Standard battery leads (ORDER: 318)
318R Ring-style battery leads (ORDER: 318R)
318T Terminal-style battery leads (ORDER: 318T)
318EXT 48" Battery lead extension (ORDER: 318EXT)
Cellular Communicators
263LTE-V LTE Verizon Cellular
Communicator
Provides wireless communication for XF6 Series panels.
ORDER: 263LTE-V, 263LTE-V/381-2
263LTE-A LTE AT&T Cellular
Communicator
Provides wireless communication for XF6 Series Panels.
ORDER: 263LTE-A, 263LTE-A/381-2
263LTE-FN FirstNet Cellular
Communicator
Provides wireless communication for XF6 Series Panels over the FirstNet network.
ORDER: 263LTE-FN
Expansion Modules
710Bus Splitter/Repeater Expands the number of devices and length of wire on the LX-Bus or keypad bus.
Also provides wire connections for up to three additional LX-Bus circuits.
ORDER: 710
711Single Zone Expander Single-zone expander with screw terminal connections. Includes EOL resistors.
ORDER: 711
711S Single Zone Expander Single-zone expander with flying lead connections. Includes EOL resistor.
ORDER: 711S
XF6 Series Installation and Programming Guide Digital Monitoring Products
15
FIELD TEST
714 Zone Expansion Module Expander with four 5VDC Class B zones and rotary-switch addressing. Includes
EOL resistors and 12-wire harness.
ORDER: 714
714-8 Zone Expander Terminal block installation for eight burglary or Class B non-powered fire devices.
Includes enclosure with lock and key plus EOL resistors.
ORDER: 714-8 , 714-8-R, 714-8L-G, 714-8L-R, 714-8PCB
714-16 Zone Expander Terminal block installation for 16burglary or Class B non-powered fire devices.
Includes enclosure with lock and key plus EOL resistors.
ORDER: 714-16 , 714-16-R, 714-16L-G, 714-16L-R, 714-16PCB
715 Zone Expansion Module Provides 4 Class B zones (12VDC) for two-wire smoke detectors and other
powered or non-powered devices. Includes 3.3k EOL resistors and 12-wire harness.
ORDER: 715
715-8 Zone Expander Provides eight powered zones (12VDC) supporting two-wire smoke detectors or
other fire alarm initiating devices. Includes red 340 enclosure and EOL resistors.
ORDER: 715-8, 715-8PCB, 715-16PCB
715-16 Zone Expander Provides 16 powered zones (12VDC) supporting two-wire smoke detectors or
other fire alarm initiating devices. Includes red 340 enclosure and EOL resistors.
ORDER: 715-16
716Output Expander Provides 4 programmable Form C (SPDT) relays and four open collector
annunciator outputs. Use the outputs for remote zone and system annunciation or
environmental control applications. Harness included.
ORDER: 716
Auxiliary Modules
860Relay Output Module Provides electrical isolation between the alarm panel and other systems or for
switching voltage to control various functions.
ORDER: 860
865Style W/X Notification
Circuit Module
Provides supervision for ground faults, opens and shorts on notification appliance
circuits. Suitable for use with style W or X 12or 24VDC circuits.
ORDER: 865
866Style W Notification Circuit
Module
Supervises one Style W Notification circuit that supervises opens, shorts and
ground faults. Capable of switching 12VDC internal or 24VDC external power
supply.
ORDER: 866
867LX-Bus Notification Circuit
Module
Provides one supervised Style W circuit for 12 VDCor 24VDC notification devices.
The 867connects to the LX-Bus and supervises Ground Fault, Open and Short
conditions on the notification circuit.
ORDER: 867
869Style D Class A Initiating
Circuit Module
Provides two Style D initiating 4-wire circuits for waterflow switches and
nonpowered burglary and fire devices. Supervises both zones for Opens, Shorts
and Ground Fault conditions.
ORDER: 869
Pull Stations
850Series Pull Stations Single or dual action pull stations with gold-plated SPST contacts and terminal
strip connections.
ORDER: 850D, 850D/711, 850D/711S, 850S, 850S/711, 850S/711S
Smoke/Heat Detectors
2W-BLX Conventional Smoke
Detector
A photoelectric detector that includes an addressable single point module for
connection to the LX-Bus of the XF6 Series panels.
ORDER: 2W-BLX
2WT-BLX Conventional Smoke/
Heat Detector
A photoelectric detector that includes an addressable single point module with a
restorable, built-in fixed temperature thermal detector and is capable of sensing a
temperature higher than 135 °F.
ORDER: 2WT-BLX
Miscellaneous Accessories
335Intrusion Siren Oers dual tones, steady and warble, is load-tested to four hours, is indoor surface-
mounted and is made out of UV-resistant, high-impact ABS plastic. 105dB.
ORDER: 335
370Lightning Suppressor Provides lightning supression for any DMP or other manufacturer’s panel.
ORDER: 370, 370RJ
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55

Digital Monitoring Products XF6 Installation & Programming Guides

Type
Installation & Programming Guides

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI