9/19/02 REL356 Addendum to IB 40-226 (Dated January 2001)
1) This document has additional data to those at Page 1-6:
1.1) Below 56/64kbps Digital Communication, it is added:
The maximum channel delay time for correct operation of REL356 is 24 milliseconds for relays
with Catalogue # MC _ _ _ _ (D,H,E,M,L)_ _ _.”
1.2) Below 9600bps Audio Tone Communication Interface, it is added:
“The maximum channel delay time for correct operation of the REL356 is 24 milliseconds for
relays with Catalogue # MC _ _ _ _ (T,B)_ _ _ and 15 milliseconds for relays with Catalogue # MC_
_ _ _ (A,B)_ _ _.”
2) Addition to page xi under REL356 Revision History:
Version 1.31 (08/29/02)
“This version includes the following changes from V 1.21:
The addition of a settable timer (by setting) for the channel alarm contact,
New setting parameter: CHAT = 0.0-10.0 sec, step 0.1 sec,
The addition of a selectable (by setting) Transfer Trip Alarm contact,
New setting parameter GSAL = GS/TTRP,
New Voltage Transformer ratio setting. The setting range for VTR 300 - 7000 has been
changed to 200 – 7000".
3) Correction at page 5-7:
“Test Conditions: Case 2 – C0=0, C1=0.1, C2=0.7, OTH=0.50 (OTH=0.70 for V1.15 or lower) should
be changed with Test Conditions: Case 2 – C0=1, C1=0.1, C2=0.7, OTH=0.50 (OTH=0.70 for V1.15
or lower)”
4) Correction at page 5-9:
Figure below Dual Unit Back to Back Test – Internal faults:
“TB6-6, TB6-6, TB6-8, TB6-8, TB6-10, TB6-10 should be changed with TB6-5, TB6-6, TB6-7, TB6-8,
TB6-9, TB6-10”.
ABB
ABB REL 356 Current Differential Protection
Instruction Booklet
REL356
January 2001 (IB 40-226)
ABB Automation Inc.
Substation Automation and Protection Division
7036 Snowdrift Road
Allentown, PA 18106
USA
Tel: (610) 395-7333
Fax: (610) 395-1055
This Instruction Book is applicable to the REL 356 Versions 1.21 and all previous versions.
ABB REL 356 Current Differential Protection
Page ii
Table of Contents
Table of Contents .....................................................................................................................ii
Guide to Figures ......................................................................................................................ix
Guide to Tables.........................................................................................................................x
Introduction .............................................................................................................................xi
REL 356 Revision History.......................................................................................................xi
Section 1 Product Overview and Specifications
Application...................................................................................................................................................... 1-1
REL 356 System Operation ............................................................................................................................ 1-1
Standard Features .......................................................................................................................................... 1-2
Communication Channel Options .................................................................................................................... 1-2
Optional Features ........................................................................................................................................... 1-3
Platform Overview .......................................................................................................................................... 1-3
REL 356 Modules ........................................................................................................................................... 1-4
Hardware Structure ......................................................................................................................................... 1-4
Specifications ................................................................................................................................................. 1-5
Ratings .................................................................................................................................................... 1-5
External Connections ............................................................................................................................... 1-5
Contact Data ............................................................................................................................................ 1-5
Binary (Voltage) Input Circuits .................................................................................................................. 1-6
9600 bps Audio Tone Communication Interface ....................................................................................... 1-6
56/64 kbps Digital Communication ........................................................................................................... 1-6
Optional Computer/Network Interface ....................................................................................................... 1-7
Chassis Dimensions and Weight .............................................................................................................. 1-7
Environmental Data .................................................................................................................................. 1-7
CT Requirements for REL 356 Current Differential Protection ......................................................................... 1-7
Catalog Information ........................................................................................................................................ 1-9
Section 2 Installation, Operation and Maintenance
Introduction .................................................................................................................................................... 2-1
REL 356 Construction ..................................................................................................................................... 2-1
REL 356 Modules ........................................................................................................................................... 2-1
Backplane Module .......................................................................................................................................... 2-2
Interconnect Module ....................................................................................................................................... 2-2
Relay Output Module ...................................................................................................................................... 2-3
Contact Input Module ..................................................................................................................................... 2-3
Microprocessor Module................................................................................................................................... 2-3
Display Module ............................................................................................................................................... 2-4
Power Supply Module ..................................................................................................................................... 2-4
Analog Input Module ....................................................................................................................................... 2-5
Modem Module (9600 bps Audio Tone Option) ............................................................................................... 2-5
CODEC (56/64 kbps Digital Communication Option) ....................................................................................... 2-5
Digital Communication Interface DCI (56/64 kbps Digital Communication Option) ........................................... 2-6
Self-Checking Software .................................................................................................................................. 2-6
Table of Contents
ABB REL 356 Current Differential Protection
Page iii
Table of Contents
Unique Remote Communication (WRELCOM) Program .................................................................................. 2-6
Separating the Inner and Outer Chassis ......................................................................................................... 2-7
Test Plugs and FT-14 Switches ...................................................................................................................... 2-7
External Wiring ............................................................................................................................................... 2-7
REL 356 Front Panel Display .......................................................................................................................... 2-8
Vacuum Fluorescent Display .......................................................................................................................... 2-8
Indicators ....................................................................................................................................................... 2-8
Key Switches ................................................................................................................................................. 2-8
Front Panel Operation ..................................................................................................................................... 2-9
Settings Mode ................................................................................................................................................ 2-9
Metering (Volts/Amps/Angle) Mode ................................................................................................................ 2-9
Target (LAST and PREVIOUS FAULT) Mode ................................................................................................. 2-9
Test Mode Function...................................................................................................................................... 2-10
Contact Input Test ........................................................................................................................................ 2-10
Relay Output Test ........................................................................................................................................ 2-11
Self Check.................................................................................................................................................... 2-12
Test Enable .................................................................................................................................................. 2-13
Standing Relay Trip ...................................................................................................................................... 2-13
Network Interface ......................................................................................................................................... 2-13
Digital Fault Recording.................................................................................................................................. 2-14
REL 356 Settings ......................................................................................................................................... 2-14
Monitoring Functions .................................................................................................................................... 2-14
Target (Fault Data) Information ..................................................................................................................... 2-18
Communication Channel Testing .................................................................................................................. 2-18
9600 bps Audio Tone Option Only ................................................................................................................ 2-18
56/64 kbps Option Only ................................................................................................................................ 2-18
Communication Channel Interface ................................................................................................................ 2-18
Receiver Status ............................................................................................................................................ 2-18
Transmitter Status ........................................................................................................................................ 2-18
Routine Visual Inspection ............................................................................................................................. 2-19
Acceptance Testing...................................................................................................................................... 2-19
Normal Precautions ...................................................................................................................................... 2-19
Disassembly Procedures .............................................................................................................................. 2-19
System Diagrams ......................................................................................................................................... 2-19
Section 3 Settings and Application
Introduction .................................................................................................................................................... 3-1
Relay System Setup....................................................................................................................................... 3-4
Firmware Version (VERS) ........................................................................................................................ 3-4
System Frequency (FREQ) ...................................................................................................................... 3-4
Readout in Primary Values (RP) ............................................................................................................... 3-4
Current Transformer Type (CTYP) ............................................................................................................ 3-4
Current Transformer Ratio (CTR) .............................................................................................................. 3-4
Voltage Transformer Ratio (VTR) ............................................................................................................. 3-4
Digital Fault Recording Information ................................................................................................................. 3-4
Trigger for Storing Oscillographic Data (OSC) .......................................................................................... 3-5
Trigger for Storing Fault Records (FDAT) ................................................................................................. 3-5
Ground Trigger Pick Up Level (TRGG) ..................................................................................................... 3-5
Phase Trigger Pick Up Level (TRGP) ....................................................................................................... 3-5
Protection System Settings ............................................................................................................................ 3-5
Change Detector (CD) .............................................................................................................................. 3-5
Dedicated Direct Transfer Trip (DDTT) ..................................................................................................... 3-5
Low Set Current Supervision (ILTS) ......................................................................................................... 3-6
ABB REL 356 Current Differential Protection
Page iv
Table of Contents
Reclose Block Enable (RBEN) ................................................................................................................. 3-6
Stub/Open Breaker Timer (SOBT) ............................................................................................................ 3-6
Open Breaker (OPBR) .............................................................................................................................. 3-6
Very Low Set Phase Current Unit (IE) ...................................................................................................... 3-7
Low Set Phase Unit (IPL) ......................................................................................................................... 3-7
High Set Phase Overcurrent Unit (IPH) .................................................................................................... 3-7
Low Set Ground Unit (IGL) ....................................................................................................................... 3-7
High Set Ground Overcurrent Unit (IGH) ................................................................................................... 3-7
Current Differential System Settings ............................................................................................................... 3-8
Trip Desensitizing (TDES) ........................................................................................................................ 3-8
Operating Threshold (OTH) ...................................................................................................................... 3-8
Sequence Coefficients (C0, C1, C2) ......................................................................................................... 3-9
Automatic Channel Delay Measurement (ALDT)..................................................................................... 3-11
Lead/Follow Mode (LDFL) ....................................................................................................................... 3-11
Local Delay Timer (LDT)......................................................................................................................... 3-11
Unit Identification (UNID) ........................................................................................................................ 3-11
Communication Speed Selection (KBPS) - 56/64 kbps versions only ..................................................... 3-12
Transfer Trip (TTRP) .............................................................................................................................. 3-12
Transmit Clock Source (XCLK) - 56/64 kbps versions only .................................................................... 3-12
Loopback (LPBK) ................................................................................................................................... 3-12
Transmitter Level (XMTR) - Audiotone version only................................................................................ 3-12
Receiver Level Signal Detector (RLSD) - Audiotone version only ........................................................... 3-12
Fault Locator and Distance System Common Settings ................................................................................. 3-12
Ohms Per Unit Distance (XPUD)............................................................................................................ 3-12
Distance Unit Type (DTYP) .................................................................................................................... 3-12
Positive Sequence Impedance Angle (PANG) ........................................................................................ 3-13
Zero Sequence Impedance Angle (GANG) ............................................................................................. 3-13
Zero Sequence to Positive Sequence Impedance Ratio (ZR) ................................................................. 3-13
Backup System Settings - Version with Distance Option only ...................................................................... 3-13
Backup System Enable (BKUP) ............................................................................................................. 3-13
Loss of Potential Block (LOPB).............................................................................................................. 3-13
Directional Units Settings ............................................................................................................................. 3-13
Forward Directional Phase Unit (FDOP) ................................................................................................. 3-13
Forward Directional Ground unit (FDOG) ................................................................................................ 3-13
Ground Directional Unit Polarization (DIRU)............................................................................................ 3-14
Ground Backup Unit Settings - Version with Distance Option only ................................................................ 3-14
Medium Set Ground Overcurrent Unit (IOM) ........................................................................................... 3-14
Ground Overcurrent Timer (TOG) ........................................................................................................... 3-14
Zone 2 and Zone 3 Settings - Versions with Distance Option only ................................................................ 3-14
Zone 2 Phase Reach (Z2P) .................................................................................................................... 3-15
Zone 2 Phase Timer (T2P) ..................................................................................................................... 3-15
Zone 2 Forward Ground Reach (Z2GF) ................................................................................................... 3-15
Zone 2 Reverse Ground Reach (Z2GR) .................................................................................................. 3-15
Zone 2 Ground Timer (Z2G) ................................................................................................................... 3-15
Zone 3 Phase Reach (Z3P) .................................................................................................................... 3-15
Zone 3 Phase Timer (T3P) ..................................................................................................................... 3-15
Zone 3 Forward Ground Reach (Z3GF) ................................................................................................... 3-15
Zone 3 Reverse Ground Reach (Z3GR) .................................................................................................. 3-15
Zone 3 Ground Timer (T3G) ................................................................................................................... 3-15
Out of Step Settings - Versions with Distance Option only ........................................................................... 3-15
Out of Step Trip (OST) ........................................................................................................................... 3-16
Out of Step Block (OSB) ........................................................................................................................ 3-16
Inner Blinder (RT) ................................................................................................................................... 3-16
ABB REL 356 Current Differential Protection
Page v
Table of Contents
Outer Blinder (RU) .................................................................................................................................. 3-16
Out of Step Detection Timer (OST1) ...................................................................................................... 3-16
Out of Step Trip Way In Timer (OST2) ................................................................................................... 3-16
Out of Step Trip Way Out Timer (OST3) ................................................................................................ 3-16
Out of Step Trip Override Timer (OSOT) ................................................................................................ 3-17
Remote Setting and Time Settings ............................................................................................................... 3-17
Remote Setting (SETR).......................................................................................................................... 3-17
Time Settings (TIME, YEAR, MONTH, DAY, WDAY, HOUR, MIN) ........................................................ 3-17
Settings for Tapped Load Applications.......................................................................................................... 3-17
Introduction ............................................................................................................................................ 3-17
Settings for OTH, C0, C1 and C2 for Tapped Load Applications ............................................................. 3-18
Setting Example - General Case................................................................................................................... 3-19
Line Data ...................................................................................................................................................... 3-19
For Current Differential Measurement ..................................................................................................... 3-19
For Fault Locating and Fault Recording .................................................................................................. 3-19
For Distance Backup Protection ............................................................................................................. 3-19
Relay System Setup..................................................................................................................................... 3-19
Firmware Version (VERS) ...................................................................................................................... 3-19
System Frequency (FREQ) .................................................................................................................... 3-19
Readout in Primary Values (RP) ............................................................................................................. 3-19
Current Transformer Type (CTYP) .......................................................................................................... 3-19
Current Transformer Ratio (CTR) ............................................................................................................ 3-20
Voltage Transformer Ratio (VTR) ........................................................................................................... 3-20
Digital Fault Recording Information ............................................................................................................... 3-20
Trigger for Storing Oscillographic Data (OSC) ........................................................................................ 3-20
Trigger for Storing Fault Records (FDAT) ............................................................................................... 3-20
Ground Trigger Pick Up Level (TRGG) ................................................................................................... 3-20
Phase Trigger Pick Up Level (TRGP) ..................................................................................................... 3-21
Protection System Settings .......................................................................................................................... 3-21
Change Detector (CD) ............................................................................................................................ 3-21
Dedicated Direct Transfer Trip (DDTT) ................................................................................................... 3-21
Low Set Current Supervision (ILTS) ....................................................................................................... 3-22
Reclose Block Enable (RBEN) ............................................................................................................... 3-22
Stub/Open Breaker Timer (SOBT) .......................................................................................................... 3-22
Open Breaker (OPBR) ............................................................................................................................ 3-22
Very Low Set Phase Current Unit (IE) .................................................................................................... 3-23
Low Set Phase Unit (IPL) ....................................................................................................................... 3-23
High Set Phase Overcurrent Unit (IPH) .................................................................................................. 3-23
Low Set Ground Unit (IGL) ..................................................................................................................... 3-23
High Set Ground Overcurrent Unit (IGH) ................................................................................................. 3-24
Current Differential System Settings ............................................................................................................. 3-24
Trip Desensitizing (TDES) ...................................................................................................................... 3-24
Operating Threshold (OTH) .................................................................................................................... 3-24
Sequence Coefficients (C0, C1, C2) ....................................................................................................... 3-25
Automatic Channel Delay Measurement (ALDT)..................................................................................... 3-28
Lead/Follow Mode (LDFL) ....................................................................................................................... 3-28
Local Delay Timer (LDT)......................................................................................................................... 3-28
Unit Identification (UNID) ........................................................................................................................ 3-28
Comunication Speed Selection (KBPS) - 56/64 kbps versions only ........................................................ 3-28
Transfer Trip (TTRP) .............................................................................................................................. 3-28
Transmit Clock Source (XCLK) - 56/64 kbps versions only .................................................................... 3-28
Loopback (LPBK) ................................................................................................................................... 3-29
Transmitter Level (XMTR) - Audiotone version only................................................................................ 3-29
ABB REL 356 Current Differential Protection
Page vi
Receiver Level Signal Detector (RLSD) - Audiotone version only ........................................................... 3-29
Fault Locator and Distance System Common Settings ................................................................................. 3-29
Ohms Per Unit Distance (XPUD)............................................................................................................ 3-29
Distance Unit Type (DTYP) .................................................................................................................... 3-29
Positive Sequence Impedance Angle (PANG) ........................................................................................ 3-29
Zero Sequence Impedance Angle (GANG) ............................................................................................. 3-29
Zero Sequence to Positive Sequence Impedance Ratio (ZR) ................................................................. 3-29
Backup System Settings - Versions with Distance Option only .................................................................... 3-30
Backup System Enable (BKUP) ............................................................................................................. 3-30
Loss of Potential Block (LOPB).............................................................................................................. 3-30
Directional Units Settings ............................................................................................................................. 3-30
Forward Directional Phase Unit (FDOP) ................................................................................................. 3-30
Forward Directional Ground Unit (FDOG) ................................................................................................ 3-30
Ground Directional Unit Polarization (DIRU)............................................................................................ 3-30
Ground Backup Unit Settings - Version with Distance Option only ................................................................ 3-30
Medium Set Ground Overcurrent Unit (IOM) ........................................................................................... 3-30
Ground Overcurrent Timer (TOG) ........................................................................................................... 3-31
Zone 2 and Zone 3 Settings - Versions with Distance Option only ................................................................ 3-31
Zone 2 Phase Reach (Z2P) .................................................................................................................... 3-31
Zone 2 Phase Timer (T2P) ..................................................................................................................... 3-31
Zone 2 Forward Ground Reach (Z2GF) ................................................................................................... 3-31
Zone 2 Reverse Ground Reach (Z2GR) .................................................................................................. 3-32
Zone 2 Ground Timer (T2G) ................................................................................................................... 3-32
Zone 3 Phase Reach (Z3P) .................................................................................................................... 3-32
Zone 3 Phase Timer (T3P) ..................................................................................................................... 3-32
Zone 3 Forward Ground Reach (Z3GF) ................................................................................................... 3-32
Zone 3 Reverse Ground Reach (Z3GR) .................................................................................................. 3-32
Zone 3 Ground Timer (T3G) ................................................................................................................... 3-32
Out of Step Settings - Versions with Distance Option only ........................................................................... 3-32
Out of Step Trip (OST) ........................................................................................................................... 3-32
Out of Step Block (OSB) ........................................................................................................................ 3-33
Outer Blinder (RU) .................................................................................................................................. 3-33
Out of Step Detection Timer (OST1) ...................................................................................................... 3-33
Out of Step Trip Way In Timer (OST2) ................................................................................................... 3-33
Out of Step Trip Way Out Timer (OST3) ................................................................................................ 3-33
Out of Step Trip Override Timer (OSOT) ................................................................................................ 3-34
Remote Setting and Time Settings ............................................................................................................... 3-34
Remote Setting (SETR).......................................................................................................................... 3-34
Time Settings (TIME, YEAR, MONTH, DAY, WKDAY, HOUR, MIN) ..................................................... 3-34
Setting Example - Tapped Load Application ................................................................................................. 3-34
Line and Transformer Data ........................................................................................................................... 3-34
Settings for OTH, C0, C1 and C2 for Tapped Load Applications ................................................................... 3-35
Section 4 Measuring Elements and Operational Logic
Composite Sequence Filter............................................................................................................................. 4-1
Current Differential Algorithm .......................................................................................................................... 4-1
Communication Channel Options .................................................................................................................... 4-3
Data Communication ................................................................................................................................ 4-4
9600 bps Audiotone Interface ................................................................................................................... 4-4
56/64 kbps Digital Communication Interfaces........................................................................................... 4-4
Adaptive Communication Channel Delay Measurement ............................................................................ 4-4
Relay Functions.............................................................................................................................................. 4-5
Direct Transfer Trip .................................................................................................................................. 4-5
Table of Contents
ABB REL 356 Current Differential Protection
Page vii
Change Detector Supervision ................................................................................................................... 4-5
Open Breaker Function ............................................................................................................................ 4-5
Stub Bus Trip ........................................................................................................................................... 4-5
Weak Feed Trip........................................................................................................................................ 4-6
Reclose Initiate Logic ............................................................................................................................... 4-6
High Set Overcurrent Elements ................................................................................................................ 4-6
Fault Locator ............................................................................................................................................ 4-7
Faulted Phase Selector ............................................................................................................................ 4-7
Differential Protection Disable .................................................................................................................. 4-8
Optional Backup Functions............................................................................................................................. 4-8
Distance Protection .................................................................................................................................. 4-8
Backup Protection Disable ....................................................................................................................... 4-8
Sensitive Directional Ground Overcurrent Unit.......................................................................................... 4-8
Out of Step Trip and Out of Step Block Logic ........................................................................................ 4-12
Loss of Potential (LOPB) ....................................................................................................................... 4-13
Loss of Current Monitoring ..................................................................................................................... 4-13
Section 5 Testing
Introduction .................................................................................................................................................... 5-1
Equipment Needed ......................................................................................................................................... 5-1
Test Setup...................................................................................................................................................... 5-1
Current and Voltage Inputs ....................................................................................................................... 5-1
Analog Input and Front Panel Metering Test ................................................................................................... 5-1
Contact Input Subsystem Test ....................................................................................................................... 5-2
Relay Output Subsystem Test........................................................................................................................ 5-3
Communication Subsystem Test .................................................................................................................... 5-3
9600 bps Audio Tone Option .................................................................................................................... 5-3
56/64 kpbs Digital Communication Option ................................................................................................ 5-3
Functional Tests - Current Differential System ............................................................................................... 5-4
Single Unit Loopback Test - Internal Faults .............................................................................................. 5-5
Single Unit Loopback Test - External Faults............................................................................................. 5-8
Dual Unit Back to Back Test - External Faults ......................................................................................... 5-8
Dual Unit Back to Back Test - Internal Faults .......................................................................................... 5-9
Functional Tests - Optional Backup System ................................................................................................. 5-10
Phase to Ground Units ................................................................................................................................. 5-10
Zone 2 Phase-Ground Element Without Reverse Reach......................................................................... 5-10
Zone 2 Phase-Ground Element With Reverse Reach ............................................................................. 5-13
Zone 3 Phase-Ground Element Without Reverse Reach......................................................................... 5-16
Phase to Phase Units ............................................................................................................................ 5-18
Zone 2 Phase-Phase Element ................................................................................................................ 5-18
Zone 3 Phase-Phase Element ................................................................................................................ 5-20
3-Phase Units ........................................................................................................................................ 5-21
Zone 2 3-Phase Units............................................................................................................................. 5-22
Zone 3 3-Phase Units............................................................................................................................. 5-23
Out of Step System Functional Tests........................................................................................................... 5-24
In-Service Checks ........................................................................................................................................ 5-26
Potential and Current Circuits ....................................................................................................................... 5-26
Current Differential Checks ........................................................................................................................... 5-27
Table of Contents
ABB REL 356 Current Differential Protection
Page viii
Table of Contents
Section 6 Computer Communications
Communication Port(s) Use ............................................................................................................................ 6-1
Introduction .............................................................................................................................................. 6-1
Communication Port Options.................................................................................................................... 6-1
Personal Computer Requirements ............................................................................................................ 6-1
Connecting Cables ................................................................................................................................... 6-1
Modem Communications .......................................................................................................................... 6-2
Setting Change Permission and Relay Password ..................................................................................... 6-2
Password ................................................................................................................................................. 6-2
Troubleshooting ........................................................................................................................................ 6-3
Sixteen Fault Target Data ............................................................................................................................... 6-3
Digital Fault Recording.................................................................................................................................... 6-3
Fault Record Data Definitions ......................................................................................................................... 6-4
Analog Signals ......................................................................................................................................... 6-4
Digital Signals .......................................................................................................................................... 6-5
Section 7 Glossary
Section 8 Application Notes
Line Sectionalizing Using a PLC and ABB Protective Relays
Modem Communications to ABB Relays
ABB REL 356 Current Differential Protection
Page ix
Guide to Figures
Section 1 Product Overview and Specifications
Figure 1-1 Fault Recognition .......................................................................................................................... 1-2
Section 2 Installation, Operation and Maintenance
Figure 2-1 Backplane..................................................................................................................................... 2-2
Figure 2-2 RS232/PONI Communication Interface Device ........................................................................... 2-14
Figure 2-3 Layout of REL 356 Modules Within Inner and Outer Chassis ...................................................... 2-20
Figure 2-4 Block Diagram of REL 356 Relay ................................................................................................ 2-21
Section 3 Settings and Applications
Figure 3-1 Ratio of I
3
F
min
/I
F
Gmin
vs. C0 (C1 = 0.1, C2 - 0.7) ....................................................................... 3-10
Figure 3-2 Tapped Load Application............................................................................................................ 3-18
Figure 3-3 Setting Example-Tapped Load Application ................................................................................ 3-34
Section 4 Measuring Elements and Operational Logic
Figure 4-1 IT Filter Output for an A-G Fault ................................................................................................... 4-1
Figure 4-2 Current Differential Logic ............................................................................................................... 4-2
Figure 4-3 Operating Characteristic................................................................................................................ 4-3
Figure 4-4 Data Frame ................................................................................................................................... 4-4
Figure 4-5 Open Breaker Trip......................................................................................................................... 4-5
Figure 4-6 Stub Bus Trip................................................................................................................................ 4-6
Figure 4-7 Phase Selector ............................................................................................................................. 4-8
Figure 4-8 Mho Characteristic for Phase to Ground Faults ........................................................................... 4-10
Figure 4-9 Mho Characteristic for Three Phase Faults ................................................................................. 4-11
Figure 4-10 Mho Characteristic for Phase to Phase Faults .......................................................................... 4-11
Figure 4-11 Blinders for the Out of Step Logic ............................................................................................. 4-12
Guide to Figures
ABB REL 356 Current Differential Protection
Page x
Guide to Tables
Section 2 Installation, Operation and Maintenance
Table 2-1 Test Mode Functions .................................................................................................................. 2-10
Table 2-2 Binary-to-Hexidecimal Conversion............................................................................................... 2-11
Table 2-3 Monitoring Functions ................................................................................................................... 2-15
Table 2-4 Target (Fault Data) Information ................................................................................................... 2-16
Section 3 Settings and Applications
Table 3-1 Setting Table ................................................................................................................................ 3-1
Section 5 Testing
Table 5-1 Zone-2 Phase-Ground Forward Internal Faults: Z2GF = 4.5 Ohms Z2GR = 0.01 Ohms .............. 5-11
Table 5-2 Zone-2 Phase-Ground Forward External Faults: Z2GF = 4.5 Ohms Z2GR = 0.01 Ohms ............. 5-12
Table 5-3 Zone-2 Phase-Ground Reverse External Faults: Z2GF = 4.5 Ohms Z2GR = 0.01 Ohms ............ 5-13
Table 5-4 Zone-2 Phase-Ground Forward Internal Faults: Z2GF = 4.5 Ohms Z2GR = 4.5 Ohms ................ 5-14
Table 5-5 Zone-2 Phase-Ground Forward External Faults: Z2GF = 4.5 Ohms Z2GR = 4.5 Ohms ............... 5-15
Table 5-6 Zone-2 Phase-Ground Reverse External Faults: Z2GF = 4.5 Ohms Z2GR = 4.5 Ohms .............. 5-16
Table 5-7 Zone-3 Phase-Ground Forward Internal Faults: Z2GF = 7.0 Ohms Z2GR = 0.01 Ohms .............. 5-16
Table 5-8 Zone-3 Phase-Ground Forward External Faults: Z2GF = 7.0 Ohms Z2GR = 0.01 Ohms ............. 5-17
Table 5-9 Zone-3 Phase-Ground Reverse External Faults: Z2GF = 7.0 Ohms Z2GR = 0.01 Ohms ............ 5-17
Table 5-10 Zone-2 Phase-Phase Forward Internal Faults: Z2P = 4.5 Ohms................................................ 5-18
Table 5-11 Zone-2 Phase-Phase Forward External Faults: Z2P = 4.5 Ohms .............................................. 5-19
Table 5-12 Zone-2 Phase-Phase Reverse External Faults: Z2P = 4.5 Ohms .............................................. 5-19
Table 5-13 Zone-3 Phase-Phase Forward Internal Faults: Z3P = 7.0 Ohms................................................ 5-20
Table 5-14 Zone-3 Phase-Phase Forward External Faults: Z3P = 7.0 Ohms .............................................. 5-20
Table 5-15 Zone-3 Phase-Phase Reverse External Faults: Z3P = 7.0 Ohms .............................................. 5-21
Table 5-16 Zone-2 Three-Phase Forward Internal Faults: Z2P = 4.5 Ohms ................................................. 5-22
Table 5-17 Zone-2 Three-Phase Forward External Faults: Z2P = 4.5 Ohms ............................................... 5-22
Table 5-18 Zone-2 Three-Phase Reverse External Faults: Z2P = 4.5 Ohms ............................................... 5-22
Table 5-19 Zone-3 Three-Phase Forward Internal Faults: Z3P = 7.0 Ohms ................................................. 5-23
Table 5-20 Zone-3 Three-Phase Forward External Faults: Z3P = 7.0 Ohms ............................................... 5-23
Table 5-21 Zone-3 Three-Phase Reverse External Faults: Z3P = 7.0 Ohms ............................................... 5-23
Section 6 Computer Communications
Table 6-1 Communications Cable Requirements ............................................................................................ 6-3
Table 6-2 RS-PONI Dip Switch Settings ........................................................................................................ 6-4
Guide to Tables
ABB REL 356 Current Differential Protection
Page xi
Introduction & Revision History
Introduction
The REL 356 numerical current differential protection provides high speed protection for long and
short lines. It is particularly suitable for lines too short to be effectively protected by distance relays
and for tapped load applications. The current-only measuring principle offers advantages such as
insensitivity to power swings, mutuals and problems associated with ccvt’s. Communication inter-
faces for 9600 bps audiotone or 64 kbps direct digital or fiber optic are available. The REL 356
protection system also provides digital fault recording, fault locating and extensive target records.
Features
· numerical processing
· proven sequence filter for current differential measurement
· trip time 18 – 26 msec typical for digital communication
· 64/56 kbps digital communication for optical fiber or multiplexers
· modem version for leased telephone lines, analog microwave or metallic pilot wires
· automatic channel delay measurement
· independent Direct Transfer Trip
· directional or non-directional high set phase and ground independent trip
· built-in optional distance back-up
REL356 Revision History
Main board
Version 1.21 (10/01/00)
Same as v 1.20 except an internal code modification due to new modem design.
Version 1.20 (05/01/00)
This version includes the following changes from v 1.15:
· Added setting SOBT to allow longer reset time of the 52b contact.
· Added setting for OPBR so that the selections are OPBR=IE/52B/BOTH/OUT.
· Extended setting range for IPL and IGL
· Improved 2
nd
harmonic filtering
· Metering display of IT (composite current), OP (operating value) and RES (restraint value)
· OP and RES are now set in rms value instead of peak value
Version 1.15 (11/01/99)
Same as v 1.14 except a setting range change of TDES, trip-desensitizing feature.
Version 1.13 (03/29/99)
Same as v 1.12 except that distance back-up can be enabled.
ABB REL 356 Current Differential Protection
Page xii
Introduction & Revision History
Version 1.12 (03/23/99)
Same as v 1.11 and v 1.10 except
· Change of communication error display to FEPH (frame errors per hour).
· Added CDT, change detector supervision, of pilot trip.
· Added a 60 seconds trip limiting timer to prevent accidental overheating for standing relay trip.
Version 1.11 (10/20/98)
Same as v 1.10 but for digital communication versions.
Version 1.10 (08/27/98)
Same as v 1.00 with target display improvements. Modem version only.
Version 1.00 (08/12/97)
Initial release.
DCI, digital communication interface
Version 1.10 (10/20/98)
Improved noise immunity. Part number 1614C53G06.
Version 1.00 (08/12/97)
Initial release. Part number 1614C53G01.
CODEC, coder-decoder
Version 1.12 (10/20/98)
Improved noise immunity.
Version 1.10 (08/12/97)
Initial release.
Modem module
Version 1.10 (09/01/00)
New design due to obsolete Rockwell modem. Style number changed to “A” for channel selection.
Note that the style “A” modem is incompatible with the older style “T” modem. The modems have to
be of the same style in the two line ends.
Version 1.00 (08/12/97)
Initial release.
ABB REL 356 Current Differential Protection
1-1
Product Overview and Specifications
Product Overview
Application
The REL 356 is a dual-microprocessor based, composite sequence filter, current differential protection system. The
REL 356 operates on the principles inherited from previous successful current differential systems (LCBII); but adapted
and improved using numerical techniques.
The REL 356 is a pilot system, utilizing a communication channel with wide choice of analog and digital communication
options.
The REL 356 is a high speed relaying system and is suitable for application to any voltage level. Its principle of operation
makes it ideal for short lines and tapped lines with a power transformer, where traditional distance protection are not
practical.
The REL 356 is a current-only system and provides all benefits associated with relaying systems not needing potential
transformers such as:
· Unaffected by CCVT transients
· Unaffected by power swings
· Not affected by mutuals on parallel lines
An optional distance relaying system has been included to provide back-up for loss of communication channel. This
back-up system consists of a two zone distance unit and logic for non-pilot relaying system. Phase and ground distance
units are included.
The current differential protection is inherently immune to system swings and the relay will block the tripping. However,
if power swing trip is desired, blinders have been provided for detecting this condition. OST (Out-of-Step Trip) is included
in the optional distance back-up system.
An overcurrent tripping function is also included in the relaying system. The high set overcurrent function activates
instantaneous trip when the phase (IPH) or the ground (IGH) threshold units detect currents above the settings. These
units may be supervised by the directional units. The phase units are supervised by FDOP (Forward Directional Overcurrent
Phase) and the ground unit is supervised by FDOG (Forward Directional Overcurrent Ground). Connection of external
voltage transformers is required to activate the directional units.
The REL 356 also requires the connection to voltage transformers for out-of-step trip, distance protection, fault location,
loss-of-potential and loss-of-current detection.
Because of the setting ranges available in the relaying system, it is possible to accommodate different ct ratios at the
two terminals of the transmission line.
The REL 356 relay has the capability, through its channel modem, to accurately measure the communication channel
delay. A continuous channel delay measurement with delay compensation is provided.
REL 356 System Operation
The basic operation of the REL 356 relay system performs a true differential comparison of line current flowing through
each terminal of the protected line. A pilot channel, either fiber optic or audio tone, is used to bring in the remote terminal
signals for comparison to the local signals. The unique methods used to represent the three phase current and securely
transmit the remote signal produce the application flexibility and fidelity of the REL 356.
Current only systems, like the REL 356, compare the currents measured at the terminals of the transmission line. In a
current differential system, the phasor relationship determines whether the condition is external or internal.
ABB REL 356 Current Differential Protection
1-2
Product Overview and Specifications
For an internal fault, the currents are essentially in phase at the terminals of the transmission line. For an external fault,
the currents are 180° out of phase. Figure 1-1 illustrates the concept.
Figure 1-1. Fault Recognition
Standard Features
· Current differential protection algorithm
· Numerical processing
· Multiple microprocessor design
· Current change detectors and selectable voltage change detectors
· Direct transfer trip
· Channel independent high set phase and ground overcurrent units, directional or non-directional
· Fault locator
· High speed operation, typical 1½ cycle
· Close into fault detection
· Open breaker and stub bus trip
· Contact outputs for
· Breaker trip
· General start
· Breaker failure initiation
· Reclose initiate and block
· System failure alarm
· Channel failure alarm
· Trip alarm
· RS232C series communications port
· Adaptive protection communication channel delay compensation
· Digital fault recording
· 10 analog waveforms from local and remote measurements
· 64 digital channels
· 12 samples per cycle
· Local HMI interface
· 19” rack mounting
Communication Channel Options
REL 356 is available with eight different communication interfaces:
· 9600 bps audiotone
· British Telecom audiotone
· 56/64 kbps direct digital
· 56/64 kbps 820 nm multi-mode fiber
· 56/64 kbps 1300 nm single mode fiber, short reach
· 56/64 kbps 1300 nm single mode fiber, medium reach
· 56/64 kbps 1300 nm single mode fiber, long reach
· 56/64 kbps direct digital with G.703 interface
ABB REL 356 Current Differential Protection
1-3
Product Overview and Specifications
Optional Features
· Two zone distance back-up, phase and ground
· Directional ground back-up
· Loss of potential block
· Loss of current supervision
· Power swing block or trip
· Extended contact output with selectable transfer trip contacts
· Dual power supplies
· RS232C series communication port with IRIG-B input port
· Modbus PONI
Platform Overview
The REL 356 relay assembly consists of an outer-chassis and an inner-chassis which slides into the outer-chassis.
The REL 356 conforms to the following dimensions and weight:
· Height 7” (requires 4 rack units @ 1.75” each); 177 mm
· Width 19”; 483 mm
· Depth 13.6”; 345 mm
· Weight 38 lbs; 17.5 kg
ABB REL 356 Current Differential Protection
1-4
Product Overview and Specifications
All of the relay circuitry, with the exception of the input isolation transformers and first-line surge protection, are mounted
on the inner chassis, to which the front panel is attached. The outer chassis has a backplate, which is a receptacle for
all external connections, including the digital communication interface. Two optional FT-14 switches are mounted in the
two peripheral areas of the outer chassis. The FT-14 switches permit convenient and safe disconnection of trip, ac and
dc circuits, and provide for injection of test signals.
REL 356 Modules
The inner and outer chassis, together, contain standard modules, plus the optional relay output board. The backplane
module and digital communication interface (DCI) are connected to the backplate of the outer chassis. The remaining
modules are attached to the inner chassis:
· Interconnect module
· Relay output modules
· Contact input module
· Microprocessor module
· Display module
· Power supply module
· Analog input module
· Modem module for 9600 bps audio tone channel version
· CODEC (coder-decoder) module for 56/64 kbps digital communication
Hardware Structure
The basic hardware consists of:
· Input transformers for analog signals (currents only, or currents and voltages)
· A front-end filter, multiplexer and A/D converter of those input signal
· One CPU for analog input sampling, Fourier computations, operator interface and non-volative data storage
· One CPU for protection functions, contact input interface, control output interface and communication interface
· Status inputs for logic operations
· Output contacts for control of external devices
· EPROM for program storage
· EEPROM for settings and fault-data storage
· Modem or CODEC module for protection communication
ABB REL 356 Current Differential Protection
1-5
Product Overview and Specifications
Specifications
Ratings
Nominal ac voltage at 60 Hz 69.3 V rms
Nominal ac current (In) 1 or 5 A rms
Rated frequency 50 or 60 Hz
Maximum permissible ac voltage
Continuous 160 V rms (limited by maximum input to A/D converter)
10 seconds 240 V rms (limited by input transformer flux density)
Maximum permissible ac current
Continuous 3 x nominal current (limited by thermal characteristics)
1 second
Operational 160 A rms at 5 A, 32 A rms at 1 A
(limited by maximum input to the A/D converter)
Thermal 100 x nominal current
dc battery voltages, nominal (range) 60/48 Vdc (30 70 Vdc)
110/125 Vdc (88 - 140 Vdc)
220/250 Vdc (176 280 Vdc)
dc burdens
normal 15 W
tripping 40 W
ac burdens
volts per phase 0.02 VA at 70 Vac
current per phase 0.45 VA at 5 A
External connections
Terminal blocks located on the rear of the chassis suitable for #14 square tongue lugs. Wiring to FT-14 switches suitable
for #12 wire lugs.
Contact data
Trip contacts
make and carry
1 second 30 A
continuous 10 A
break
resistive 50 W
L/R = 45 msec 25 W
Non-trip contacts
continuous 1 A
resistive interrupt 0.1 A
Contacts meet IEC255-6A, IEC255-12, IEC255-16, BS142-1982
ABB REL 356 Current Differential Protection
1-6
Product Overview and Specifications
Binary (Voltage) Input Circuits
Jumper selectable 48, 125 or 250 Vdc
Drop-out threshold 67%
9600 bps Audio Tone Communication Interface
Operating speed 9600 bps
Standards compliance ITU V.29
Carrier frequency 1,700 Hz
Modulation QAM Quadrature Amplitude Modulation
Transmit level - 1 dBm to 15 dBm in 2 dBm steps
Receiver sensitivity - 33 dBm
Channel requirement 4 wire, unconditioned
56/64 kbps Digital Communication
Operating speed 56 or 64 kbps, selectable
Direct digital option
Electrical standard RS422/RS485
Mechanical standard RS530
Maximum distance 4000/1300 m
Fiber optic options
Connector ST
Wave length 820 nm
Cable multi-mode
Transmitter output into 50/125 mm cable - 18 dBm minimum
Receiver input - 28 dBm minimum
Reach, typical 2 miles/3.3 km
Wave length 1300 nm
Cable single-mode
Transmitter output into 9/125 mm cable
Short reach option - 20 dB minimum
Reach, typical 7.5 miles/12 km
Medium reach option - 10 dB minimum
Reach, typical 20 miles/32 km
Long reach option 0 dB minimum
Reach, typical 32 miles/52 km
Receiver input - 32 dBm minimum
- 20 dBm maximum
*
* Receiver maximum input is determined by receiver saturation and should not be exceeded. An attenuator is
delivered to facilitate back-to back testing. The received level should be adjusted to 26 dBm.
Optional G.703 Interface
The optional G.703 interface adapter complies with CCITT (ITU) G.703 co-directional, 64 kbps specification. For
details refer to IL 40-201.7
ABB REL 356 Current Differential Protection
1-7
Product Overview and Specifications
Optional Computer/Network Interface
· RS232C PONI for single point computer communications
· RS232C PONI with IRIG-B for modulated/de-modulated IRIG-B time synchronization
· Modbus PONI for DNP 3.0 network communications (requires an external MIPC card)
· INCOM PONI for local network communications using INCOM network
Chassis Dimensions and Weight
Height 7 (177.8 mm), 4 rack units
Width 19 (482.6 mm)
Depth including terminal blocks 14 (356 mm)
Weight 68 lb (17.5 kg)
Environmental Data
Ambient temperature range
Operation - 20°C to + 60°C
Storage - 40° C to + 80°C
Insulation test voltage, ANSI C37.90, IEC 255-5 2.8 kV dc, 1 minute
3.2 kV dc, 1 second
Open contacts 1400 V dc, continuous
Impulse voltage withstand, IEC 255-5 1.2/50 ms, 0.5 Joule
Surge withstand voltage, ANSI C37.90.1, IEC 255-22-1 3 kV, 1 MHz
Fast transient voltage, ANSI C37.90.1, IEC 255-22-4 4 kV, 10/100 ns
EMI field strength withstand, ANSI C37.90.2 25 MHz 1 GHz, 10 V/m
Emission tests, EN 50081-1, class A
Conducted emissions 150 kHz 30 MHz
Radiated emissions 30 MHz 1000 MHz
CT Requirements for REL356 Current Differential Protection
REL356 uses the operating principle of comparing an operating quantity OP with a restraint quantity RES. The operating
quantity is formed from:
TLTR
IIOP +=
where ITR
is the remote composite current and ITL is the local composite current. ITR and ITL are formed by local and
remote currents, respectively, in the following manner:
02211
0ICICICI
T
++=
The restraint quantity is formed from:
TLTR
IIRES +=
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237

ABB REL 356 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI