Danfoss ECL Comfort 301 - L66 User guide

Type
User guide
ECL COMFORT
ECL COMFORT
ECL Comfort
Installation and
Maintenance
L66
Mixing controller with PI controlled
hot water service
VI.JD.T1.02
ECL Comfort
User's Guide
L66
Table of Contents
Sections of the Installers part of this guide
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections relevant to
your ECL Comfort controller are included here.
Before you start
Installation
10
Identifying the system type
11
Mounting the ECL Comfort controller
12
Electrical connections 230 V a.c.
13
Electrical connections 24 V a.c.
14
Connecting and placing the temperature sensors
15
Inserting the ECL Card
Basic Set-up
16
Adjusting the ECL Card settings
17
Setting the time and date - line A
18
Monitoring temperatures and system units - line B
19
Manual control - line B
20
Setting the heat curve - line C
21
Heating cut-out - line 1
22
Flow temperature limits - line 2
23
Room temperature infl uence - line 3
26
Setting the PI regulation - lines 4 - 7
Control & Overviews
29
Check list
30
ECL Card settings
31
Service parameters
Extended Service
32
Adjusting the service parameters
Miscellaneous
34
Copying with the ECL Card
Daily use,
turn the guide over for sections 1-7
1
Choose favourite display
2
Select controller mode
3
Adjust room and hot water temperature
4
Set your personal day plan
5
Advantages of the ECL Card
6
Hot points
7
Defi nitions
Table of Contents
Daily use
Section
1
Choose favourite display
2
Select controller mode
3
Adjust room and hot water temperature
4
Set personal day plan
5
Advantages of the ECL Card
6
Hot points
7
Defi nitions
The documentation for the ECL Comfort controller is composed of
numbered sections. Only sections that are relevant to your ECL Comfort
controller are included here.
Installation and maintenance.
Grey sections 10 and onwards.
Turn the guide over.
Your personal week plan:
This guide is associated to ECL Card 087B4871
Installer:
By:
Date:
*087B4871*
*viJDT102*
*087B4871*
*viJDT102*
Note!
The functions can only be realized with ECL Comfort 301 - and as
of ECL Card version CI05 and controller version 2.00.
Day plan II 0 3 6 9 12 15 18 21 24
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
Factory settings are grey
Comfort 0 3 6 9 12 15 18 21 24
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
A
B
C
1
2
3
4
5
6
7
The shown diagram is a fundamental and simplifi ed example
and does not contain all components that are necessary in a
system.
If the system you are about to install diff ers from the shown
diagram of a standard heating system, feel free to sketch an
outline for comparison. Adaptation of systems, see section 10.
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
heating and hot water circuit.
Circuit indicator
Circuit
selector
Shift
button
Adjustment
Controller
mode
Room temperature /
Hot water circuit II
System information
Today's program
Day plans
913
20
8
A
Line indicator
Line indicator
Circuit
5
5
6
A
5
5
1
1
ON
2
0
3
6
B
3
2
8
8
0
3 6 9
12
15
18
21
24
3 6 9
3 6 9
3 6 9
3 6 9
1
9
1
3
5
-
C
3
8
8
0
3 6 9
12
15
18
21
3 6 9
3 6 9
3 6 9
3 6 9
24
1
5
5
5
C
3
1
2
3
4
6
0
3 6 9
12
15
3 6 9
3 6 9
3 6 9
3 6 9
0
0
0
0
5
0
0
0
0
1
2
3
4
6
0
0
0
0
3 6 9
3 6 9
3 6 9
3 6 9
12
12
12
12
15
15
15
15
3 6 9
3 6 9
3 6 9
3 6 9
0
5
0
0
6
8
8
0
3 6 9
12
15
18
21
3 6 9
3 6 9
3 6 9
3 6 9
0
7
0
0
6
8
8
0
3 6 9
12
15
18
21
3 6 9
3 6 9
3 6 9
3 6 9
0
7
0
0
The ECL Card
For daily use and your personal adjustments, the yellow side of
the ECL Card must face you.
The display
Each line, A, B, C, 1, 2 etc. of the ECL Card has its own
display. See section 1.
Heating - circuit I
Hot water - Circuit II
The circuit indicator
shows the selected circuit.
List of components:
ECL Comfort 301
S1
Outdoor temperature sensor
S2
Alarm input
S3
Flow temperature sensor
S4
Return temperature sensor - circuit I
S5
Flow temperature sensor for hot water - circuit II
S6
Return temperatur sensor - circuit II
P1-1
Circulation pump 1 for heating - circuit I
P1-2
ECA 80 Circulation pump 1 for hot water - circuit II
P2-1
Circulation pump 2 for heating - circuit I
P2-2
ECA 80 Circulation pump 2 for hot water - circuit II
P3
Alarm output
M1
Motorized control valve - circuit I
M2
Motorized control valve - circuit II
The ECL Card: Installers instruction
The grey side of the card must face you
when you change settings. For daily
use and during start-up the yellow side
of the card must face you.
8
9
10
199
Extended service parameters,
see section 31.
Installation & maintenance
The ECL Card, grey side
for installation and maintenance.
Lines A to C, and lines 1 to
7 for basic settings, see overview
section 30.
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
heating and hot water circuit.
5
1 2
036
B
2
3
1
ON
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of heating systems.
The ECL Comfort controller ensures you of the following;
Room and hot water temperatures will be adjusted to your
personal settings.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
The automatic pump motion program protects the
circulation pump against blocking.
Sketch an outline of your heating system
The ECL Comfort controller is designed for a wide range of
heating systems with di erent confi gurations and
capacities.
If your heating system diff ers from the diagrams shown in
section 10, you may want to sketch an outline of the
system about to be installed. This makes it easier to use the
Installer’s Guide, which will guide you step-by-step from
installation to fi nal adjustments before the end-user takes
over.
The controller is pre-programmed with factory
settings which are shown in the relevant sections of this guide.
However, you might come across some settings that
are not listed in this instruction. These settings are used in
connection with optional modules, and you can fi nd a description
of the settings and the corresponding parameters in the
instruction for the optional module in question.
How to use this guide
This guide is divided into two parts:
Users Guide (turn the guide over)
Yellow sections 1-7
Installation and Maintenance:
Grey sections 10 and onwards
Before you start
VI.JD.T1.02
L66
2004.08
Installation
Installation
In this section you fi nd the most frequently used systems. If
your system is not quite as shown below, fi nd the diagram
which has the best resemblance to your system and make
your own combinations.
Alternatives using the same settings:
Heat exchanger or direct district heating
Heating system type 1
Indirectly connected heating circuit and PI-regulated hot water
service circuit
Check the setting of line 24 in circuit I (gear motor/thermo
actuator).
Heating system type 2
Directly connected heating circuit and indirectly connected PI-
regulated hot water service circuit
Check the setting of line 24 in circuit I (gear motor/thermo
actuator).
System diagrams in this instruction are principal drawings and
do not contain all components which are necessary in heating
systems.
Identifying the system type
10
Installation
Installation
For easy access, you should mount the ECL Comfort
controller near the system. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fi xing
screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 93 x 139 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fi x it with the
two locks which are placed diagonally in two corners of the
controller.
Mounting the ECL Comfort
controller
11a
11b
Installation
Installation
12a
Connecting the 230 V a.c. units
Terminal
Description
Max. load
1
L
Supply voltage 230 V a.c.
2
N
Supply voltage 230 V a.c.
3
M1
Gear motor - open/circuit I
0.2 A 230 V a.c.
4
M1
Gear motor - close/circuit I
alt.: ABV thermo actuator
0.2 A 230 V a.c.
5
230 V a.c. supply for
M1/circuit I
6
M2
Gear motor - open/circuit II
0.2 A 230 V a.c.
7
M2
Gear motor - close/circuit II
0.2 A 230 V a.c.
8
230 V a.c. supply for
M2/circuit II
9
P1-1
Circulation pump 1-1
for heating circuit I
4(2) A 230 V a.c.
10
230 V a.c. supply for
pump relay R1
11
P2-1
Circulation pump 2-1
for heating circuit I
4(2) A 230 V a.c.
12
230 V a.c. supply for
pump relay R2
13
Alarm relay
4(2) A 230 V a.c.
14
230 V a.c. supply for
pump relay R3
25
P1-2
Circulation pump 1-2
for hot water circuit II
4(2) A 230 V a.c.
26
230 V a.c. supply for
pump relay R4
28
P2-2
Circulation pump 2-2
for hot water circuit II
4(2) A 230 V a.c.
29
230 V a.c. supply for
pump relay R5
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 8
Jumper from 8 to 10
Jumper from 10 to 12
Jumper from 12 to 14
Jumper from 14 to 26
Jumper from 26 to 29
Jumper from 2 to common N-terminal
Connecting the temperature sensors, alarm inputs
and the BUS
Terminal
Description
Type
(recommended)
15 and 16
System device bus
17 and 16
Outdoor sensor (S1)
ESMT
18 and 16
R
alarm
19 and 16
Flow sensor (S3) circuit I
ESMU/ESM-11/ESMC
20 and 16
Return sensor (S4) circuit I
ESMU/ESM-11/ESMC
21 and 16
Hot water fl ow sensor (S5)
circuit II
ESMU/ESM-11/ESMC
22 and 16
Hot water return sensor (S6)
circuit II
ESMU/ESM-11/ESMC
Establish the jumper from 16 to common terminal.
Wire cross section: 0.75 - 1.5 mm2
Electrical connections
Max. 2 x 1.5 mm2 wires can be inserted into each screw terminal.
Incorrect connection can damage the TRIAC outputs. Max. load
(terminal 3, 4, (6 and 7)) 0.2 A / 230 V a.c.!
Terminal 16 and 18
External circuit for alarm contact; R
x
and R
y
are the external alarm
relays; the contacts should be gold-plated. The resistance in the
contact must be below 10 ohms (5V / 1.7 mA).
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I } Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
ECL ECL
ECL ECL
ECL ECL
ECL ECL
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
} Alarm input circuit II
} Alarm input circuit II
} Alarm input circuit II
12b
Electrical connections -
230 V a.c.
Installation
Installation
13a
Connecting the 24 V a.c. and 230 V a.c. units
Terminal
Description
Max. load
1
L
Supply voltage 24 V a.c.
2
N
Supply voltage 24 V a.c.
3
M1
Gear motor - open/circuit I
1.0 A 24 V a.c.
4
M1
Gear motor - close/circuit I
alt.: ABV thermo actuator
1.0 A 24 V a.c.
5
24 V a.c. supply for
M1/circuit I
6
M2
Gear motor - open/circuit II
1.0 A 24 V a.c.
7
M2
Gear motor - close/circuit II
1.0 A 24 V a.c.
8
24 V a.c. supply for
M2/circuit II
9
K1*
Relay for circulation pump 1-1
for heating circuit I
4(2) A 24 V a.c.
10
24 V a.c. supply for
pump relay K1
11
K2*
Relay for circulation pump 2-1
for heating circuit I
4(2) A 24 V a.c.
12
24 V a.c. supply for
pump relay K2
13
Alarm relay
4(2) A 24 V a.c.
14
24 V a.c. supply for R
alarm
25
K3*
Relay for circulation pump 1-2
for hot water - circuit II
4(2) A 24 V a.c.
26
24 V a.c. supply for
pump relay K3
28
K4*
Relay for circulation pump 2-2
for hot water - circuit II
4(2) A 24 V a.c.
29
24 V a.c. supply
for pump relay K4
*
K1/K2/K3/K4 auxilliary relay
Coil: 24 V a.c.
Contacts: 4A 230 V a.c.
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 8
Jumper from 8 to 10
Jumper from 10 to 12
Jumper from 12 to 14
Jumper from 14 to 26
Jumper from 26 to 29
Jumper from 2 to common N-terminal
Wire cross section: 0.75 - 1.5 mm2
Electrical connections
Max. 2 x 1.5 mm2 wires can be inserted into each screw terminal.
Incorrect connection can damage the TRIAC outputs. Max. load
(terminal 3, 4, (6 and 7)) 0.2 A / 230 V a.c.!
Electrical connections -
24 V a.c.
Connecting the temperature sensors, alarm inputs
and the BUS
Terminal
Description
Type
(recommended)
15 and 16
System device bus
17 and 16
Outdoor sensor (S1)
ESMT
18 and 16
R
alarm
19 and 16
Flow sensor (S3) circuit I
ESMU/ESM-11/ESMC
20 and 16
Return sensor (S4) circuit I
ESMU/ESM-11/ESMC
21 and 16
Hot water fl ow sensor (S5)
circuit II
ESMU/ESM-11/ESMC
22 and 16
Hot water return sensor (S6)
circuit II
ESMU/ESM-11/ESMC
Establish the jumper from 16 to common terminal.
Wire cross section: 0.75 - 1.5 mm2
Electrical connections
Max. 2 x 1.5 mm2 wires can be inserted into each screw terminal.
Incorrect connection can damage the TRIAC outputs. Max. load
(terminal 3, 4, (6 and 7)) 0.2 A / 230 V a.c.!
Terminal 16 and 18
External circuit for alarm contact; R
x
and R
y
are the external alarm
relays; the contacts should be gold-plated. The resistance in the
contact must be below 10 ohms (5V / 1.7 mA).
} Alarm input circuit I
} Alarm input circuit I
} Alarm input circuit I
ECL ECL
ECL ECL
ECL ECL
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
terminal 16 terminal 18
} Alarm input circuit II
} Alarm input circuit II
} Alarm input circuit II
13b
Installation
Installation
It is important that the sensors are mounted in the correct
position in your heating system.
Special attention should be paid to the following sensors:
Outdoor temperature sensor
(ESMT type)
The outdoor sensor should be mounted on the north side
of the building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors or windows.
Flow temperature sensor
(ESMU, ESM-11 or ESMC types)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends the
ESMU-type to be inserted into the exchanger fl ow outlet.
Make sure that the surface of the pipe is clean at the area
where the sensor is mounted.
Do not move the sensor after it has been fastened in
order to avoid damage to the sensor element.
Return temperature sensor
(ESMU, ESM-11 or ESMC types)
The return sensor should always be placed max. 15 cm from
the mixing point. It should always be placed on a pipe in
which the water fl ow never stops.
Room temperature sensor
(ECA 60 and 61 remote control)
Place the room sensor in the room where the temperature is
to be controlled. Do not place it on outside walls or close to
radiators, windows or doors.
14
Placing the temperature
sensors
Installation
Installation
15b
How to insert your ECL Card the fi rst time
After the power has been switched on, open the lid on the
front side of the controller.
Place the ECL Card with the yellow side facing you. This
enables the controller to read the ECL Card data.
The controller immediately starts to copy the factory
settings and heating system type from the ECL Card. After
copying, the display will show the heating system type the
controller is set to control. After approx. 10 sec. the display
will change to display line C.
C
C 9
C 99C 9
Y
0
P
C 9
C 99C 9
L
7
0
5
1
0
6
6
1
8
8
0
3 6 9
12
15
18
21
24
3 6 9
3 6 9
3 6 9
3 6 9
1
0
2
3
5
C
3
Line
Circuit
Time
Outdoor
temperature
Desired room
temperature
The controller is now ready to be set to control your heating
system.
Inserting the ECL Card
15a
Understanding the ECL Card
The ECL Card contains factory settings for a standard
heating system. If the actual heating system diff ers from the
standard system, the controller must be adjusted
accordingly. After the adjustment, the new settings can be
stored on the ECL Card.
For ECL Card copying and daily use including
adjustment of temperatures and time periods, insert the
ECL Card with the yellow side facing you.
For system set-up adjustments, the grey side of the ECL
Card - the installer’s side - must be facing you.
As a main rule, the ECL Card should always remain in the
controller during service, maintenance and settings.
If the card is removed please note that:
The controller settings are locked after approx. 10 min.
The ECL Card must not be exposed to direct heat or
sunshine
If several controllers are installed in the system you can
write a title on the ECL Card with a permanent ink pen.
The grey
side of the
ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings on the grey
side of the ECL Card.
Use the arrow buttons to move from line to line of
the ECL Card, for example line 2:
Line
indicator
Settings to
be adjusted
Value in range
indicator
Circuit
1
1
ON
2
0
9
10
0100
2
3
2
0
Use the minus/plus buttons to adjust the
setting(s).
In some displays more than one setting or value
can be adjusted. Use the shift button to switch
between the options.
The circuit selector shifts between circuit I
and II. You can adjust all settings and service
parameters individually in both circuits, ie.
circuit II.
Update of the ECL Card after maintenance and
service
All new settings can be stored on the ECL Card. For details
about copying, see section 34. Insert the ECL Card with the
yellow side facing you.
Go to line 9 (bottom line)
C
C 9
C 99C 9
Y
0
P
C 9
C 99C 9
Accept to copy as indicated. No other keys are
active.
When the copying is fi nished display line C will appear
8
8
0
3 6 9
12
15
18
21
24
3 6 9
3 6 9
3 6 9
3 6 9
1
0
2
3
5
C
3
You can make other changes in the day plan, set time and
date or change settings
(see User’s Guide).
Adjusting the ECL Card
settings
16
Go to line A.
0
1
0
0
1
2 4
2 412 4
0
5
A
3
1
Actual time
Actual time
Actual time
Actual time
A
Actual time
A
Actual time
Actual time
Actual time
Actual time
Actual time
Actual time
Actual time
Actual time
Actual time
Year Month, day
Year Month, day
Year Month, day
Year Month, day
0
Year Month, day
0
1
Year Month, day
1
2 4
Year Month, day
2 4
2 4
Year Month, day
2 4
2 412 4
Year Month, day
2 412 4
0
Year Month, day
0
Year Month, day
1
Year Month, day
1
Year Month, day
1
Year Month, day
1
Year Month, day
Year Month, day
Year Month, day
Year Month, day
Year Month, day
Year Month, day
Use the shift botton to switch between hours,
minutes, years, months and days.
Set the correct time and date.
In case of a power failure which lasts longer than 12 hours, the
time and the date have to be set again.
All other settings are stored as programmed.
Use the yellow side of the ECL card to enter the day plan settings.
See User’s Guide, section 4.
Setting the time and date -
line A
17
The grey
side of the
ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
Go to line B.
5
1 2
0
3
6
B
3
1 2
2
1 2
1
ON
Flow temperature
Return temperature
State indicator
Controlled units
Push the shift button to see:
- the calculated fl ow temperature
- the return temperature set points.
The activation direction of the motorized valve is shown as
arrows below the valve symbol. When the circulation pump is
operating, it is indicated as
ON
below the pump symbol.
If a sensor is not mounted or is disconnected, the display will
indicate it as “
- -
.
If the sensor is short-circuited, the display will indicate it as
- - -
.
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Relationship between temperature and ohmic value
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25
0 2
5 5
0 7
5
100
125
150
˚C
808
846
884
921
961
1000
1039
1078
1117
1155
1194
1232
1271
1309
1347
1385
1423
1462
1501
1539
1578
˚C
-50
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
Monitoring temperatures
and system units - line B
Monitoring temperatures
and system units - line B
Monitoring temperatures
18
Go to line B.
The circuit selector shifts between circuit I and II.
Shift to manual mode.
5
1
0
6
B
2
1
ON
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
B
Controlled Controller
B
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
Controlled Controller
units mode
units mode
units mode
units mode
units mode
units mode
units mode
units mode
ON
units mode
ON
Select the unit you want to control. The selected
unit symbol will fl ash.
The gear motor
opens
1
or closes
1
the valve as long as the the relevant button is
pressed.
The thermo actuator
(according to version *)),
closes
1
(NO) or opens
1
(NC)
the valve as long as the relevant button is pressed.
*) NO - normally open
NC - normally closed
If these buttons are pushed for at least 3 seconds, the gear motor/
thermo actuator will receive a constant signal.
Pumps are switched
off or
ON
on when the
relevant button is pressed.
Check the activation direction of the motorized valve either
by looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
This operation applies to both circuits. Press the
button to select circuit II.
During manual operation, the pump motion is OFF.
Manual control -
line B
19
The grey
side of the
ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
Go to line C.
The symbol for the slope of the heat curve will
ash.
1 2
8
C
1
1
0
3
1
ON
1 2
2
1 2
Slope
Displacement
Slope
Circuit
Setting range
Factory setting
I
0.2 ... 3.4
1.8
Adjust the slope of the heat curve, if required.
If you want to adjust the parallel displacement of
the heat curve, push the shift button. The symbol
for the parallel displacement will fl ash.
Parallel displacement
Circuit
Setting range
Factory setting
I
-9 ... 9 K
0 K
Make your adjustments.
Setting the heat curve -
line C
Setting the heat curve -
line C
Setting the heat curve -
20a
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
1.0
1.4
0.6
0.2
1.8 2.2 3.0 3.4
100
110
2.6
o
C
o
C
Floor heating systems
This controller is factory set for radiator systems, which typically
are high fl ow temperature systems.
To control fl oor heating systems, which typically are low fl ow
temperature systems, you need to change the heat curve
according to your type of system.
Slope
Setting range
Typical setting
0.2 ... 3.4
1.0
Parallel displacement
Setting range
Typical setting
-9 ... +9 K
0 K
20b
The grey
side of the
ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
1 Limit for heating cut-out
Circuit
Setting range
Factory setting
I
10 ... 30 °C
18 °C
Go to line 1.
1 2
8
1
1
3
1
ON
1 2
2
1 2
Set the outdoor temperature limit at which you
want the system to start or stop.
18 ˚C
Temperature
Actual outdoor Accumulated outdoor
temperature temperature
temperature temperature
Heating OFF
Heating OFF
Heating OFF
Heating OFF
Heating OFF
Heating OFF
Time
Heating Heating
This function can save energy by stopping the heating system
when the outdoor temperature gets above a set limit. The heating
system switches ON again when the outdoor temperature and the
accumulated temperature become lower than the set limit.
Heating cut-out -
line 1
Heating cut-out -
line 1
Heating cut-out -
21
2 Flow temperature limits, min. and max.
Circuit
Setting range
Factory setting
I
10 ... 150 °C
min. 10°C, max. 90 °C
Go to line 2.
1
1
ON
2
0
9
10
0100
2
3
2
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
0
Min. fl ow Max. fl ow
0
9
Min. fl ow Max. fl ow
9
10
Min. fl ow Max. fl ow
10
0100
Min. fl ow Max. fl ow
0100
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
Min. fl ow Max. fl ow
temperature temperature
temperature temperature
temperature temperature
temperature temperature
0
temperature temperature
0
9
temperature temperature
9
10
temperature temperature
10
0100
temperature temperature
0100
temperature temperature
Setting range
The left end of the setting range fl ashes. Adjust the
min. limit of your system temperature.
Choose the max. limit. The right end of the setting
range fl ashes.
Adjust the max. limit.
Flow temperature limits -
line 2
22
The grey
side of the
ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
This section is only relevant if you have installed ECA 60 / ECA 61
/ ECA 62 / ECA 63. There are two basic principles for control of the
room temperature infl uence:
A: Max. room temperature limitation
Use this limitation if your heating system is fully equipped
with radiator thermostats and you also want to obtain a max.
limitation of the room temperature. The controller will allow
for free heat gains, i.e. solar radiation or heat from a fi re place,
etc.
3 Room temperature infl uence
Circuit
Setting range
Factory setting
I
0 ... 99 / -99 ... 0
min. 0, max. -40
Go to line 3.
The bar below the min. value fl ashes.
Adjust the min. infl uence.
0
-4
0
3
1
1
ON
2
ON
2
3
ON
Min. Max.
Min. Max.
Min. Max.
Min. Max.
0
Min. Max.
0
-4
Min. Max.
-4
0
Min. Max.
0
Min. Max.
Min. Max.
Min. Max.
Min. Max.
Min. Max.
Min. Max.
Min. Max.
Min. Max.
Min. Max.
Min. Max.
infl uence infl uence
infl uence infl uence
infl uence infl uence
infl uence infl uence
0
infl uence infl uence
0
-4
infl uence infl uence
-4
0
infl uence infl uence
0
infl uence infl uence
Select the max. infl uence.
The bar below the range indicator fl ashes in the
right side of the display.
Adjust the max. infl uence.
+
_
In uence
In uence
Desired room
Desired room
Desired room
temperature
temperature
temperature
Room
Room
Room
Room
temperature
temperature
temperature
temperature
Max.
Max.
Max.
limitation
limitation
limitation
The max. in uence determines how much the room
temperature should infl uence the desired fl ow temperature.
Example
The actual room temperature is 2 degrees too high.
The infl uence at max. limitation (right corner of the display) is
set to -40.
The infl uence at min. limitation (left corner of the display) is set
to 0.
Heat curve H is 1.8.
Result:
The desired fl ow temperature is changed by
2 x -40 x 1.8 x 0.1= -14.4 degrees.
Room temperature infl uence -
line 3
23a
B: Reference room temperature control
Used if your heating system is not equipped with radiator
thermostats and you select the room with room sensor as a
temperature reference for the rest of the rooms.
(However, should you have a few radiator thermostats
installed, make sure that they are fully open).
Set a positive value for the min. infl uence and a
negative value for the max. infl uence.
The room sensor in the reference room registers
the diff erence between the desired and the actual
room temperature. The desired fl ow temperature
will be corrected to eliminate this diff erence.
Example 1
The actual room temperature is 2 degrees too low.
The infl uence at max. limitation (right corner of the display) is
set to -35.
The infl uence at min. limitation (left corner of the display) is set
to 20.
Heat curve H is 1.8.
Result:
The desired fl ow temperature is changed by
2 x 20 x 1.8 x 0.1= 7.2 degrees.
Example 2
The actual room temperature is 2 degrees too high.
The infl uence at max. limitation (right corner of the display) is
set to -35.
The infl uence at min. limitation (left corner of the display) is set
to 20.
Heat curve H is 1.8.
Result:
The desired fl ow temperature is changed by
2 x (-35) x 1.8 x 0.1= -12.6 degrees.
23b
+
_
In uence
In uence
Min. limitation
Min. limitation
Min. limitation
Desired room
Desired room
Desired room
Desired room
temperature
temperature
temperature
temperature
temperature
Room
Room
Room
Room
Room
Room
temperature
temperature
temperature
temperature
temperature
Max. limitation
Max. limitation
Max. limitation
The grey
side of the
ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
4 Proportional band, Xp
Circuit
Setting range
Factory setting
I/II
1 ... 250 K
80 K / 80 K
Go to line 4.
1
1
ON
2
0
4
8
3
2
Setting to
Setting to
Setting to
Setting to
0
Setting to
0
Setting to
Setting to
Setting to
Setting to
Setting to
Setting to
Setting to
Setting to
Setting to
Setting to
Setting to
Setting to
8
Setting to
8
Setting to
Setting to
Setting to
Setting to
Line be adjusted
Line be adjusted
Line be adjusted
Line be adjusted
0
Line be adjusted
0
Line be adjusted
8
Line be adjusted
8
indicator
Set the proportional band.
A higher value will result in a stable but slow
control of the fl ow temperature.
5 Integration time constant
Circuit
Setting range
Factory setting
I/II
5 ... 999 sec.
30 sec. / 20 sec.
Go to line 5.
Set a high integration time constant to obtain a
slow but stable reaction to deviations.
A small integration constant will make the
controller react fast but with less stability.
6 Running time of the motorized control valve
Circuit
Setting range
Factory setting
I/II
5 ... 250 sec.
35 sec. / 15 sec.
Go to line 6.
Set the running time of the motorized control
valve according to the example on the opposite
page. This is the time it takes the controlled unit to
move from fully closed to fully open position.
7 Neutral zone
Circuit
Setting range
Factory setting
I/II
0 ... 9 K
3 K / 3 K
Go to line 7.
Set the neutral zone to a high value if you can
accept a high variation in fl ow temperature.
When the actual fl ow temperature is within the
neutral zone, the controller does not activate the
motorized valve.
The neutral zone is symmetrical around the desired fl ow
temperature.
Setting the PI regulation -
lines 4-7
26a
If you want to tune the PI regulation precisely, you
can use the following method:
Set the integration time (line 5) to its max. value (999 sec.).
Decrease the value for the proportional band (line 4) until the
system starts hunting with a constant amplitude (it might be
necessary to force the system by setting an extreme value).
Find the critical time period on the temperature recording or
use a stop watch.
Temperature
Critical time period
Critical time period
Critical time period
Critical time period
Time
Time
This time period will be characteristic for the system, and you can
evaluate the settings from this critical period.
Integration time = 0.85 x critical time period
Proportional band = 2.2 x proportional band value in the
critical time period.
If the regulation seems to be too slow, you can decrease the
proportional band value by 10%.
Make sure there is a consumption when you set the parameters.
How to calculate the running time of a motorized valve
Valve type
Valve
stroke
(mm)
Actuator
type
Actuator
speed
(sec. / mm)
Running
time
(sec.)*
VS 2, DN 15
3.0
AMV 100
90
250
VS 2, DN 15-25
VM 2, DN 15-25
VB 2, DN 15-20
5.0
AMV(E)
10, 20
15
75
VS 2, DN 15-25
VM 2, DN 15-25
VB 2, DN 15-20
5.0
AMV(E) 30
3
15
VM 2, DN 32
VB 2, DN 25
7.0
AMV(E) 30
15
105
VM 2 DN 32
VB 2, DN 25
7.0
AMV(E) 30
3
21
The running time of the motorized valve is calculated using the
following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec. / mm)
Example: 5.0 mm x 15 sec. / mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec. / degr.)
Example: 90 degrees x 2 = 180 sec.
* Max. value = 250
26b
Control & over views
Control & over views
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 (Live) and 2 (Neutral). See section 12 or
13.
Check that the required actuators, pumps, fans,
dampers and burners are connected to the correct
terminals. See sections 12 or 13.
Check that all sensors are connected to the correct
terminals. See section 14.
Mount the controller and switch on the power.
Insert the ECL Card with the yellow side facing you
and push
, if necessary. See section 15.
Choose manual operation as controller mode. See
section 2.
Check that valves open and close, and that
required pumps, fans, dampers and burners start
and stop when operated manually. See section 19.
Having completed the manual operation check,
choose automatic operation as controller mode.
Check that the temperatures shown in display A
and B match the actual sensors. See section 1.
Check list
29a
Adapting the ECL Comfort controller to the
system
Turn the ECL Card so that the grey side faces you
and push
, if necessary.
Set the time and the date (line A). See section 17.
Check all settings on the ECL Card. See sections 20
to 27.
Check all settings in Extended Service (section 32)
are set or that the factory settings comply with
your requirements.
If your system di ers from the diagram shown on the
cover, you should check and alter your service parameters, if
necessary.
Check that the settings mentioned in section 10
have been set correctly.
29b
Control & over views
Control & over views
ECL Card settings
(circuit I: Heating)
30a
A
Time and date
Sections 16 & 17
B
System information
Sections 18 & 19
C
Heat curve
Sections 20
Setting range
Factory setting
Your settings
C
Heat curve - slope
0.2 ... 3.4
1.8
Set the slpe of the heat curve.
See section 20.
C
Heat curve - parallel displacement
-9 ... +9 K
0 K
Set the parallel displacement of the heat
curve. See section 20.
1
Limit for heating cut-out
10 ... 30 °C
18 °C
Saves energy by stopping the heating system
when the ourdoor temperature gets above a
certain limit. See section 21.
2
Flow temperature , min. / max. limits
10 ... 150 °C
min. 10°C, max. 90 °C
The limits for min. and max. fl ow temperature.
See section 22.
3
Room temperature infl uence
0 ... 99 / -99 ... 0
min. 0, max. -40
The room temperature's in uence on the fl ow
temperature control. See section 23.
4
Proportional band
1 ... 250 K
80 K
Set the PI-regulation. See section 26.
5
Integration time constant
5 ... 999 sec.
30 sec.
Set the PI-regulation. See section 26.
6
Running time of the motorized valve
5 ... 250 sec.
35 sec.
Set the PI-regulation. See section 26.
7
Neutral zone
0 ... 9 K
3 K
Set the PI-regulation. See section 26.
ECL Card settings
(circuit II: Hot water service)
30b
A
Time and date
Sections 16 & 17
B
System information
Sections 18 & 19
Setting range
Factory setting
Your settings
4
Proportional band
1 ... 250 K
80 K
Set the PI-regulation. See section 26.
5
Integration time constant
5 ... 999 sec.
20 sec.
Set the PI-regulation. See section 26.
6
Running time of the motorized valve
5 ... 250 sec.
15 sec.
Set the PI-regulation. See section 26.
7
Neutral zone
0 ... 9 K
3 K
Set the PI-regulation. See section 26.
Control & over views
Control & over views
Service parameters
31a
Circuit I (heating and cooling)
Line
Setting range
Factory setting
Your settings
10
Choice of room panel/remote control
1, 2
1
11
Reduced temperature dependent
on outdoor temperature
OFF / -29 ... +10 °C
-15 °C
°C
12
Boost
0 ... 99%
0%
%
13
Reference ramping
0 ... 99 min.
0
min.
14
Optimizing time constant
OFF / 10 ... 59
OFF
15
Adaptive function of room
temperature
OFF / 1 ... 30
OFF
17
Temperature reference feedback
OFF / 1 ... 20 K
OFF
K
20
Optimization based on room /
outdoor temperature
ON / OFF
OFF
21
Total stop
ON / OFF
OFF
22
Pump motion for circuit I
ON / OFF
OFF
23
Valve motion
ON / OFF
OFF
24
Gear motor / thermo actuator
ON / OFF
ON
31
Return temperature limitation (X)
-60 ... +20 °C
+15 °C
°C
32
Return temperature limitation (Y)
10 ... 110 °C
40 °C
°C
33
Return temperature limitation (X)
-60 ... +20 °C
-15 °C
°C
34
Return temperature limitation (Y)
10 ... 110 °C
60 °C
°C
35
Return temperature infl uence - max.
-9.9 ... 0 ... +9.9
-2
36
Return temperature infl uence - min.
-9.9 ... 0 ... +9.9
0
37
Adaptive function of return limitation
OFF / 1 ... 50
25
43
Priority or parallel operation
OFF / 1 ... 99 K
OFF
K
52
Closed valve / PI-regulation
ON / OFF
OFF
81
Time constant for outdoor
temperature sensor S1
1, 2 ... 250
50
141
Override input selection
OFF / 1 ... 6
OFF
142
TR restart period
OFF / 1, 2 ... 99 min.
20
min.
145
TP change over period
0.0 ... 23.9
16.1
146
TST pressure stabilisation time
1, 2 ... 99 sec.
15
sec.
153
THC change over time
OFF, 1, 2 ... 99 sec.
5
sec.
31b
Service parameters
Circuit I (heating and cooling)
Line
Setting range
Factory setting
Your settings
196
Service pin LON
ON / OFF
OFF
197
LON reset
ON / OFF
ON
198
Summer time change
ON / OFF
ON
196
Slave address
0 ... 9
15
Circuit II (hot-water service)
Line
Setting range
Factory setting
Your settings
22
Pump motion for circuit II
ON / OFF
OFF
30
Return temperature limitation
(hot water service)
10 ... 110 °C
50 °C
°C
35
Return temperature infl uence - max.
-9.9 ... 0 ... 9.9
-2
36
Return temperature infl uence - min.
-9.9 ... 0 ... 9.9
0
37
Adaptive function of return limitation
OFF / 1 ... 50
25
141
Override input selection
OFF / 1 ... 6
OFF
142
TR restart period
OFF / 1, 2 ... 99 min.
20
min.
145
TP change over period
0.0 ... 23.9
16.1
146
TST pressure stabilisation time
1, 2 ... 99 sec.
15
sec.
153
THC change over time
OFF / 1, 2 ... 99 sec.
5
sec.
The grey
side of the
ECL Card
Extended service
The grey
side of the
ECL Card
Extended service
In addition to the settings in line 1 to 7 on the grey side of the
ECL Card, there is an extended service menu from line 10 and
onwards.
Push repeatedly to reach the lines numbered 10
and onwards.
1
0
1
1
1
Value
Value
Value
Value
Value
Value
Value
Value
Value
Value
Value
1
Value
1
Value
Value
Value
Value
Line
number
Range indicator
Range indicator
Range indicator
Range indicator
Range indicator
Range indicator
Range indicator
Range indicator
Range indicator
Range indicator
Now you can move to any line of your choice.
Set the parameter value.
You can select any of the two circuits no matter
what line you are in. You will not necessarily enter
the same line number. See the service parameters
in section 31.
Check that you have entered all the required settings in
circuit I - and circuit II, if available.
If you want to copy the new settings to the ECL Card
(recommended by Danfoss), see section 34.
Make a note of your new settings in the parameter list in section
31.
When you have entered all your personal settings, turn the ECL
Card over so that the yellow side faces you.
The mentioned factory settings and setting ranges in this
instruction may vary from your ECL Card.
Adjusting the service
parameters
32a
Service parameters 10-11
32b
10 Choice of room panel / remote control
Circuit
Setting range
Factory setting
I
1, 2
1
Dedicates the unit for the time control of the comfort and
reduced temperature periods.
Choose between
1
Room panel ECA 60 or remote control
ECA 61 on address A.
2
Room panel ECA 60 or remote control
ECA 61 on address B.
The time control of the hot water circuit is always dedicated to the
day plan of circuit II.
11 Reduced temperature dependent on outdoor
temperature
Circuit
Setting range
Factory setting
I
OFF / -29 ... +10 °C
-15 °C
Limit of the outdoor temperature at which the reduced
temperature setting is switched off .
-29 to +10 °C:
The setting of reduced temperature depends
on the outdoor temperature, when the outdoor
temperature is higher than the set limit.
The lower the outdoor temperature the less the
temperature reduction. When the outdoor
temperature is below the set limit, there is no
temperature reduction.
1
00%
0%
-20
-10
-29
0 1
0 2
0
0 2150 2
Reduction
Reduction
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
temperature °C
temperature °C
temperature °C
temperature °C
temperature °C
temperature °C
temperature °C
temperature °C
0%
temperature °C
0%
Setting line 11
OFF:
The reduced temperature setting will
be constant at all outdoor temperatures.
The grey
side of the
ECL Card
Extended service
The grey
side of the
ECL Card
Extended service
32c
Service parameter
12-13
12 Boost
Circuit
Setting range
Factory setting
I
0 ... 99%
0%
Shortens the heating-up period by increasing the fl ow
temperature by the percentage you set.
Set the percentage at which you want the fl ow
temperature increased temporarily.
In order to shorten the heating-up period after a reduced
temperature period, the fl ow temperature can be increased
temporarily.
If a room temperature sensor is installed, the boost stops
when the optimising period is over or the room temperature
has been reached.
13 Reference ramping
Circuit
Setting range
Factory setting
I
0 ... 99 min.
0 min.
The time in which the fl ow temperature increases slowly to avoid
load peaks in the supply.
Set the opening time you want the valve to use.
In order to avoid load peaks in the supply network, the fl ow
temperature reference can be set to increase slowly after a
period with reduced temperature. This causes the valve to
open slowly.
T
ref
T
ref
T
T
ref
T
ref
T
Setting line 13 Time
Setting line 13 Time
Setting line 13 Time
Setting line 13 Time
Setting line 13 Time
Setting line 13 Time
Setting line 13 Time
Setting line 13 Time
32d
14 Optimising time constant
Circuit
Setting range
Factory setting
I
OFF / 10 ... 59
OFF
Optimises the start and stop times for the reduced temperature
period to obtain the best comfort at the lowest energy
consumption.
Adjust the optimising time constant. The value
consists of a number of two digits. You can select
the following values:
10, 11, ..... 59.
The two digits have the following meaning:
1. digit (system type and heat accumulation of the
building)
1. digit
Heat accumulation
of the building
System type
1
light
Radiator
system
2
medium
3
heavy
Floor heating
systems
4
medium
5
heavy
2. digit (capacity of the heating system)
2. digit
Dimensioning
temperature
Capacity
1
- 50 °C
large
5
- 25 °C
normal
9
- 05 °C
small
OFF:
No optimisation. The heating starts and
stops at the times set in the day plan.
Dimensioning temperature:
The lowest outdoor temperature at which the heating system can
obtain the desired temperature.
Service parameter
14-15
15 Adaptive function of the room temperature
Circuit
Setting range
Factory setting
I
OFF / 1 ... 30
OFF
Controls how fast the room temperature adapts to the desired
temperature.
OFF:
The adaptive funtion is cancelled.
1:
The desired temperature is adapted quickly.
30:
The desired temperature is adapted slowly.
The adaptive funtion will eliminate the diff erence
between the required and the actual room
temperature by integrating the diff erence and
adjusting the reference for the fl ow temperature.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35

Danfoss ECL Comfort 301 - L66 User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI