Danfoss ECL Comfort 300 - C37 Operating instructions

Type
Operating instructions
ECL COMFORT
ECL Comfort
Users Guide
C37
This guide is associated to ECL Card 087B4758
Installer:
By:
Date:
ECL COMFORT
ECL Comfort
Installation and
Maintenance
Mixing controller with ON/OFF controlled
hot-water charging
C37
VI.7C.E4.02
2001.02
Your personal week plan:
Heating 0 3 6 9 12 15 18 21 24
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
Hot Water
0 3 6 9 12 15 18 21 24
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
The factory setting is indicated in grey.
823-
5 - 8 18 - 22
6-8 16 - 22
823-
Table of Contents
Daily use
Section
1 Choose favourite display
2 Select controller mode
3 Adjust room and hot water temperature
4 Set personal daily plan
5 Advantages of the ECL Card
6 Hot points
7 Definitions
Installation and maintenance. Grey sections 10 and
onwards. Turn the guide over.
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Daily use, turn the guide over sections 01 - 07
1 Choose favourite display
2 Select controller mode
3 Adjust room and hot water temperature
4 Set personal day plan
5 Advantages of the ECL Card
6 Hot points
7 Definitions
Table of Contents
Sections of the Installers part of this guide
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Before you start
Installation
10 Identifying the system type
11 Mounting the ECL Comfort controller
12 Electrical connections 230 V a.c.
14 Placing the temperature sensors
15 Inserting the ECL Card
Basic Set-up
16 Adjusting the ECL Card settings
17 Setting the time and date - Line A
18 Monitoring temperatures and system units - Line B
19 Manual control - Line B
20 Setting the heat curve - Line C
21 Heating cut-out - Line 1
22 Flow temperature limits - Line 2
23 Room temperature influence - Line 3
26 Setting the PI-regulation - Line 4 - 7
27 Hot water controller - Line 1 and 2
Control & Overviews
29 Check list
30 ECL Card settings
31 Service parameters
Extended Service
32 Adjusting the service parameters
Miscellaneous
34 Copying with the ECL Card
The shown diagram is a fundamental and simplified
example and does not contain all components that are
necessary in heating systems.
If the system you are about to install is different than the
shown diagram of a standard heating system, feel free to
sketch an outline for comparison. Adaptation of heating
systems, See section 10.
List of components:
ECL Comfort 300
S1 Outdoor temperature sensor (ESM-10)
S2 Room temperature sensor (ESM-10) - circuit I
S3 Flow temperature sensor (ESM-) - circuit I
S4 Return temperature sensor (ESM-)
S5 Lower tank sensor (ESM-)
S6 Upper tank sensor (ESM-)
P1 Circulation pump for heating - circuit I
P2 Primary charging pump for hot water - circuit II
P3 Secondary charging pump for hot water - circuit II
M1 Control valve with motor - circuit I (Heating)
Installation & maintenance
The ECL Card, grey side
for installation and maintenance.
Lines A to C, and lines 1 to
7 for basic settings, see overview
section 30.
Extended service parameters,
see section 31
The ECL Card: Installer’s
instruction
The grey side of the card must face
you when you change settings. For
daily use and during start-up the
yellow side of the card must face you.
Circuit indicator
Circuit
selector
Shift
button
Adjustment Controller
mode
The circuit indicator shows the selected circuit.
The ECL Card
For daily use and your personal adjustments the yellow side
of the ECL Card must be facing you.
The display
Each line, A, B, C, 1, 2 etc. of the ECL Card has its own
display. See section 1.
Controller mode
Manual operation (Used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
heating and hot water circuit.
Room
temperature /
Hot water circuit II
Heating system
information
Todays
programme
Day plans
A
B
C
1
2
3
4
5
6
7
Hot water - circuit IIHeating - circuit I
Line indicator
Circuit
6
036912
0
5
0
8
0 3 6 9 12 15 18 21
7
00
1
3
3
2
2
1
6
6
4
4
6
0369121
0
5
0
6
0 3 6 9 12 15 18 21
0
7
0
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
heating and hot water circuit.
55
A
52
1
2
ON
B
1
ON
3
ON
8
0 3 6 9 12 15 18 21 24
1
55
5
C
3
5
1
2
ON
036
B
1
ON
3
ON
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
913
0
A
2
8
9
10
199
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of heating and hot water systems.
The ECL Comfort controller ensures you of the following;
Room and hot water temperatures will be adjusted to
your personal settings.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
The automatic pump motion program protects the
circulation pump against blocking.
Sketch an outline of your heating system
The ECL Comfort controller is designed for a wide range of
heating systems with different configurations and
capacities.
If your heating system differs from the diagrams shown in
section 10, you may want to sketch an outline of the system
about to be installed. This makes it easier to use the
Installers Guide, which will guide you step-by-step from
installation to final adjustments before the end-user takes
over.
Note! The controller is pre-programmed with factory
settings which are shown in the relevant sections of this
guide.
However, you might come across some settings that
are not listed in this instruction. These settings are used in
connection with optional modules, and you can find a de-
scription of the settings and the corresponding parameters
in the instruction for the optional module in question.
How to use this guide
This guide is divided into two parts:
Daily Use (turn the guide over)
Yellow sections 1-7
Installation and maintenance:
Grey sections 10 and onwards
Before you start
VI.7C.E4.02
2001.02
Installation
Note!
System diagrams in this instruction are principal drawings and
do not contain all components which are necessary in heating
systems.
Identifying the system type
10a
In this section you find the most frequently used systems. If
your system is not quite as shown below, find the diagram
which has the best resemblance to your system and make
your own combinations.
Alternatives using the same settings:
• Heat exchanger or direct district heating
• 2 - or 3-way control valve
Alternatives which require different settings:
• Primary or secondary connected hot water circuit
• Charging pump or change-over valve in charging circuit
Installation
Line 51 Water pump / change-over valve
Setting
OFF
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Heating system type 1
Heating system and secondary connected hot water
charging system
Line 51 Water pump / change-over valve
Setting
ON
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Heating system type 2
Heating system and secondary connected hot water
charging system
Heating system type 3
Heating system and secondary connected hot water
system
Line 51 Water pump / change-over valve
Setting
OFF
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Heating system type 4
Heating system and secondary connected hot water
system
Line 51 Water pump / change-over valve
Setting
ON
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Heating system type 5
Heating system and primary connected hot water
Line 51 Water pump / change-over valve
Setting
ON
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
ON
10b
Mounting the ECL Comfort
controller
11a
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Installation
Installation
11b
Terminal Description Type (recommended)
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESM-10
18 and 16 Room sensor (S2) ESM-10
19 and 16 Flow sensor (S3) ESMU/ESM-11/ESMC
20 and 16 Return sensor (S4) ESMU/ESM-11/ESMC
21 and 16 Hot-water sensor
- lower (S5) ESMU/ESMB
22 and 16 Hot-water sensor
- upper (S6)* ESMU/ESMB
Connecting the temperature sensors
Establish the jumper from 16 to common terminal
Connecting the 230 V a.c. units
12a
Electrical connections -
230 V a.c.
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 10 to 12
Jumper from 12 to 14
Jumper from 2 to common N-terminal
Installation
Installation
Wire cross section: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted into each screw
terminal.
Wire cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Cable type: Copper cable
Note! Cable lengths above 100 m may cause noise sensibility
(EMC).
Terminal Description Max. load
1 L Voltage supply 230 V a.c.
2 N Voltage supply 230 V a.c.
3 M1 Gear motor - open 0.2 A/ 230 V a.c.
4 M1 Gear motor - close 0.2 A/230 V a.c.
5 Phase for M1
9 P1 Circulation pump for 4(2)A/230 V a.c.
heating circuit
10 Phase for pump relay - R1
11 P2 Charging pump - primary 4(2)A/230 V a.c.
12 Phase for pump relay - R2
13 P3 Charging pump - secondary 4(2)A/230 V a.c.
14 Phase for pump relay - R3
* Connected if only one tank sensor is used.
12b
Make sure that the surface of the pipe is clean at the area
where the sensor is mounted.
Note!
Valid for ESM-11: Do not move the sensor after it has been
fastened in order to avoid damage to the sensor element.
Return temperature sensor
(ESMU, ESM-11 or ESMC types)
The return sensor should always be placed max. 15 cm
from the mixing point. It should always be placed on a pipe
in which the water flow never stops.
Room temperature sensor
(ESM-10, ECA 60 and 61 remote control)
Place the room sensor in the room where the temperature
is to be controlled. Do not place it on outside walls or close
to radiators, windows or doors.
14
Placing the temperature
sensors
It is important that the sensors are mounted in the
correct position in your heating system.
Special attention should be paid to the following sensors:
Outdoor temperature sensor
(ESM-10 type)
The outdoor sensor should be mounted on the north side of
the building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors or windows.
Flow temperature sensor
(ESMU, ESM-11 or ESMC types)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends the
ESMU-type to be inserted into the exchanger flow outlet.
Installation
Installation
Hot water temperature sensor
(ESMU or ESMB types)
Place the hot water sensor according to the
manufacturers specification.
Understanding the ECL Card
The ECL Card contains factory settings for a standard
heating system. If the actual heating system differs from
the standard system, the controller must be adjusted
accordingly. After the adjustment, the new settings
should be stored on the ECL Card.
For ECL Card copying and daily use including
adjustment of temperatures and time periods, insert the
ECL Card with the yellow side facing you.
For system set-up adjustments, the grey side of the
ECL Card - the installers side - must be facing you.
As a main rule, the ECL Card should always remain in
the controller during service, maintenance and set-
tings.
If the card is removed please note that:
The controller settings are locked after approx. 10 min.
The ECL Card must not be exposed to direct heat or
sunshine
If several controllers are installed in the heating system
you can write a title on the ECL Card with a permanent
ink pen.
15a
Inserting the ECL Card
How to insert your ECL Card the first time
After the power has been switched on, open the lid on the
front side of the controller.
Place the ECL Card with the yellow side facing you. This
enables the controller to read the ECL Card data.
The controller immediately starts to copy the factory
settings and heating system type from the ECL Card. After
copying, the display will show the heating system type the
controller is set to control. After approx. 10 sec. the display
will change to display line C.
The controller is now ready to be set to control your
heating system.
Installation
Installation
Software version
for ECL Card
Line
Circuit
Time
Outdoor
temperature
Desired
room
temperature
C
C99
Y
0
P
C73
05 107
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
Software version
for controller
15b
17
Setting the time and date -
Line A
In case of a power failure which lasts longer than 12 hours,
the time and the date have to be set again.
All other settings are stored as programmed.
Go to line A.
Use the shift button to switch between minutes,
hours, year, month and day
Set the correct time and date
Use the yellow side of the ECL Card to enter the day
plan settings.
See Users Guide, section 4.
16
Adjusting the ECL Card
settings
Update of the ECL Card after maintenance and service
All new settings can be stored on the ECL Card. For details
about copying, see section 34. Insert the ECL Card with the
yellow side facing you.
C
C99
Y
0
P
When the copying is finished display line C will appear
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
You can make other changes in the day plan, set time and
date or change settings
(see Users Guide).
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings on the grey
side of the ECL Card.
Use the arrow buttons to move from line to line
of the ECL Card, for example line 2:
Line
indicator
Settings to
be adjusted
Value in range
indicator
Circuit
1
1
ON
2
ON
09
2
04
3
ON
Use the minus/plus buttons to adjust the
settings.
In some displays more than one setting or value
can be adjusted. Use the shift button to switch
between the options.
The circuit selector shifts between circuit I
and II. You can adjust all settings and service
parameters individually in both circuits, ie.
circuit II.
Go to line 9 (bottom line)
Accept to copy as indicated. No other keys are
active.
Basic set-up
Basic set-up
01
01
25110
5
A
3
Actual time
Month, day
Year
The grey
side of the
ECL Card
The gear motor
opens or closes
the valve as long as the the relevant button is
pressed.
Pumps are switched off or on when the
relevant button is pressed.
19
Manual control - Line B
Basic set-up
Go to line B.
Shift to manual mode
Monitoring temperatures
and system units - Line B
18
Go to line B.
Note! This display also shows actual and reference values
of flow and return temperature during hot water charging.
The activity of the motorized valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display
will indicate it as
- -.
If the sensor is short-circuited, the display will indicate it as
- - - .
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Push the shift button to see:
- the calculated flow temperature
- the return temperature set points
Relationship between temperature and ohmic value
-10 °C 961 Ohm
0 °C 1000 Ohm
10 °C 1039 Ohm
20 °C 1078 Ohm
30 °C 1117 Ohm
40 °C 1156 Ohm
50 °C 1195 Ohm
60 °C 1234 Ohm
70 °C 1273 Ohm
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Temperature
Ohm
Basic set-up
0360
B
3
ON
1
1
ON
2
ON
Controlled
units
Controller mode
0360
B
3
ON
1
1
ON
2
ON
Flow temperature
Return temperature
Select circuit II to see the actual temperatures of
upper and lower tank sensors.
35
B
52
3
ON
1
1
ON
2
ON
S6 actual
Upper tank sensor
S5 actual
Lower tank sensor
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Note!
During manual operation, the pump motion is OFF.
1
ON
1
Check the activation direction of the motorized valve either
by looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
This operation applies to both circuits. Press the
button to select circuit II.
Select the unit you want to control. The selected
unit symbol will flash.
1
1
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
1.0
1.4
0.6
0.2
1.8 2.2 3.0 3.4
100
110
2.6
o
C
o
C
Floor heating systems
This controller is factory set for radiator systems, which are
typically high flow temperature systems.
To control floor heating systems, which are typically low flow
temperature systems, you need to change the heat curve
according to your type of system.
Setting the heat curve -
Line C
20a
Go to line C.
The symbol for the slope of the heat curve will
flash.
Make your adjustments.
8
C
1
3
ON
0
1
1
ON
2
ON
Slope
Displacement
Adjust the slope of the heat curve, if required.
If you want to adjust the parallel displacement of
the heat curve, push the shift button. The symbol
for the parallel displacement will flash.
Basic set-up
Basic set-up
20b
Slope
Circuit Setting range Factory setting
I 0.2 ... 3.4 1.8
Parallel displacement
Circuit Setting range Factory setting
I -9... +9 0
Parallel displacement
Circuit Setting range Typical setting
I -9... +9 0
Slope
Circuit Setting range Typical setting
I 0.2 ... 3.4 1.0
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Flow temperature limits -
Line 2
22
Go to line 2.
The left end of the range indicator flashes.
Adjust the min. limit of your heating system.
Select the max. limit. The right end of the range
indicator flashes.
Adjust the max. limit.
Heating cut-out - Line 1
21
1
2
ON
8
1
1
1
ON
3
ON
Set the outdoor temperature limit at which you
want the heating system to stop.
Go to line 1.
Basic set-up
Basic set-up
This function can save energy by stopping the heating
system when the outdoor temperature gets above a set limit.
The heating system is activated again when the actual
outdoor and the accumulated temperatures get below the set
limit.
The accumulated T
out symbolises the heat stored in the
building.
18 ˚C
Temp
Actual T
out
Accumulated T
out
Time
Heating Heating off Heating
1
1
ON
2
ON
09
2
04
3
ON
Max. flow
temperature
Min. flow
temper-
ature
Temperature
range for flow
temperature
1 Limit for heating cut-out
Circuit Setting range Factory setting
I 10 ... 30 °C 18 °C
2 Flow temperature min., max. limits
Circuit Setting range Factory setting
I 10 ... 110 °C min. 40 °C max. 90 °C
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Room temperature influence
- Line 3
23a
Basic set-up
Basic set-up
+
_
1
2
ON
0-4
0
3
1
ON
3
ON
The room sensor in the reference room registers
the difference between the desired and the
actual room temperature. The flow temperature
reference will be corrected to eliminate this
difference.
B: Reference room control
Used if your heating system is not equipped with radiator
thermostats and you select the room with room sensor as a
temperature reference for the rest of the rooms.
(However, should you have a few radiator thermostats
installed, make sure that they are fully open).
Set a positive value for min. influence and a
negative value for max. influence.
+
_
Influence
Min. limitation
Max. limitation
T
ROOM
This section is only relevant if you have installed a room
sensor or ECA 60/61. There are two basic principles for
control of the room temperature influence:
A: Max. room temperature limitation
Use this limitation if your heating system is fully equipped with
radiator thermostats and you also want to obtain a max. limita-
tion of the room temperature. The controller will allow for free
heat gains, i.e. solar radiation or heat from a fire place, etc.
The max. influence determines how much the
room temperature should influence the flow
temperature.
Go to line 3.
Select the max. influence.
The bar below the range indicator flashes in the
right side of the display.
Adjust the max. influence.
T
ROOM
Set
T
ROOM
Influence
Max. limitation
Min.
influence
Max.
influence
Example
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to
-40.
The influence at min. limitation (left corner of the display) is
set to 0.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x
-40 x 0.1 x H = -14.4 degrees.
Example 1
The actual room temperature is 2 degrees too low.
The influence at max. limitation (right corner of the display) is
set to
-20.
The influence at min. limitation (left corner of the display) is
set to 20.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x 20 x 0.1 x H = 7.2 degrees.
Example 2
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to
-35.
The influence at min. limitation (left corner of the display) is
set to 35.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x (-35) x 0.1 x H = -12.6 degrees.
23b
3 Room temperature influence
Circuit Setting range Factory setting
I 0 ... 99/-99 ... 0 min. 0 max. -40
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Set
T
ROOM
Setting the PI-regulation -
Line 4-7
26a
Go to line 4.
1
2
ON
4
80
1
ON
3
ON
Setting to be adjusted
Line
indicator
Set the proportional band.
A higher value will result in a stable, but slow
regulation of the flow temperature.
Go to line 5.
Set a high integration time constant to obtain a
slow but stable reaction to deviations.
A small integration constant will make the
controller react fast but with less stability.
Go to line 6.
Set the running time of the motorized valve
according to the example on the opposite page.
This is the time it takes the valve to move from
closed to fully open position.
Go to line 7.
Set the neutral zone to a high value if you can
accept a high variation in flow temperature.
When the actual flow temperature is within the
neutral zone, the controller does not activate the
motorized valve.
Basic set-up
Basic set-up
If you want to tune the PI-regulation precisely, you can
use the following method:
Set the integration time (line 5) to its max. value (999 sec.).
Decrease the value for the proportional band (Line 4) until
the system starts hunting with a constant amplitude (it might
be necessary to force the system by setting an extreme
value).
Find the critical time period on the temperature recording or
use a stop watch.
This time period will be characteristic for the system, and you
can evaluate the settings from this critical period.
Integration time = 0.85 x critical time period
Proportional band = 2.2 x proportional band value in the
critical time period.
If the regulation seems to be too slow, you can decrease the
proportional band value by 10%.
Note!
Make sure there is a consumption when you set the
parameters.
Time
Temp.
Critical time period
How to calculate the running time of the motorized valve
The running time of the motorized valve is calculated using the
following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec/mm)
Example: 5.0 mm x 15 sec/mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec/degr.)
Example: 90 degrees x 2 = 180 sec.
VS2 15 3.0 AMV 100 90 270
VS2 15...25, VM2 15...25, AMV(E)
VB2 15...20 5.0 10, 20 15 75
VS2 15...25, VM2 15...25,
VB2 15...20 5.0 AMV(E) 30 3 15
VM2 32, VB2 25 7.0 AMV(E) 20 15 105
VM2 32, VB2 25 7.0 AMV(E) 30 3 21
Valve type Valve Actuator Actuator Running
stroke type speed time
(mm) (sec./mm) (sec.)
26b
4 Proportional band
Circuit Setting range Factory setting
I 1 ... 250 K 80 K
5 Integration time constant
Circuit Setting range Factory setting
I 5 ... 999 sec. 30 sec.
6 Running time of the motorized valve
Circuit Setting range Factory setting
I 5 ... 250 sec. 35 sec.
7 Neutral zone
Circuit Setting range Factory setting
I 0 ... 9 K 3 K
Note! The neutral zone is symmetrical around the flow
reference value.
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Hot water controller -
Line 1 and 2
27a
The controller with the ECL Card C37 can control the hot
water temperature with either one or two sensor(s). The
controller will automatically register the number of sensors.
Select circuit II
Note!
If only one sensor is mounted, the hot water temperature
difference is equal to the cut-out temperature minus the
cut-in temperature.
Example: 45 °C minus 40 °C = 5 K
Basic set-up
Basic set-up
Set the difference.
Example:
Desired hot water temperature 60 °C
Cut-out difference 15 K
Calculated cut-out temperature
(60-15 =) 45 °C
Set the difference.
Example:
Desired hot water temperature 60 °C
Cut-in difference 20 K
Calculated cut-in temperature
(60-20 =) 40 °C
--------------------------------
--------------------------------------
--------------------------------
Temp.
One sensor (S6)
Cut-out difference - line 1
Cut-in difference - line 2
Cut-out
Time
P2/P3
Desired hot
water temperature
(charging temp.)
S6
Two sensors (S5 + S6)
--------------------------------------
---------------------------------------
Temp.
Cut-out difference - line 1
Cut-in difference - line 2
Cut-in
Cut-out
Time
P2/P3
Desired hot
water temperature
(charging temp.)
S6
S5
27b
2 Difference 2, cut-in temperature - upper sensor
Circuit
Setting range Factory setting
II 1 ... 30 K 20 K
Setting the difference between the desired tank temperature and
cut-in temperature during hot water charging.
1 Difference 1, cut-out temperature - lower sensor
Circuit
Setting range Factory setting
II 1 ... 30 K 15 K
Setting the difference between the desired tank temperature and
cut-out temperature during hot water charging.
Cut-in
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Adapting the ECL Comfort controller to the heating
system
29b
Check list
If your heating system differs from the diagram shown on
the overleaf of the cover, you should check and perhaps
alter the following service parameters.
To ensure that you have the correct settings see section
10 for examples of different heating systems.
Control & overviews
Turn the ECL Card so that the grey side faces
you.
Set the time and the date (Line A)
See section 17.
Check all settings referring to the grey side of the
ECL Card
See sections 20 to 27.
51 Water pump / change-over valve
52 Closed valve / normal operation
53 PI reference when heating hot water
Line
Check list
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 (Live) and 2 (Neutral).
See section 12.
Check that valves and pumps are connected to
the correct terminals.
See section 12.
Check that all sensors are connected to the
correct terminals.
Mount the controller, and switch on the power.
Insert the ECL Card with the yellow side facing
you and press
, if necessary.
See section 15.
Select manual operation in the controller mode.
See section 2
in the users guide.
Check that valves open and close, and that
pumps start and stop when operated manually.
See section 19.
Check that the temperatures shown in display A
and B match the actual sensors, both for circuit
I (heating) and circuit II (hot water).
See section 1
in the users guide.
Control & overviews
29a
ECL Card settings
(circuit II: Hot water service)
30b
Setting range Factory setting Your settings
1
Difference 1 - hot water temperature
1 ... 30 K 15 K
Cut-out condition,
see section 27.
2
Difference 2 - hot water temperature
1 ... 30 K 20 K
Cut-in condition,
see section 27.
ECL Card settings
(circuit I: Heating)
30a
A Time and date See sections 16 & 17
B System information See sections 18 & 19
C Heat curve See section 20
Heat curve - Slope
0.2 ... 3.4 1.8
Set the slope of the heat curve
,
see section 20
Heat curve - Parallel displacement
-9 ... +9 K 0 K
Set the parallel displacement of the
heat curve
, see section 20
1
Limit for heating cut-out
10 ... 30 °C 18 °C
Save energy by stopping the heating system
when the outdoor temperature gets above
a certain limit,
see section 21.
2
Flow temperature min.-/max. limits
10 ... 110 °C min. 40, max. 90 °C
The limits for min. and max. flow
temperature
, see section 22.
3
Room temperature influence
0 ... +99 / -99 ... 0 min. 0, max. -40
The room temperatures influence on the
flow temperature control,
see section 23.
4
Proportional band
1 ... 250 K 80 K
Set the PI-regulation
, see section 26.
5
Integration time constant
5 ... 999 sec. 30 sec.
Set the PI-regulation,
see section 26.
6
Running time of motorized valve
5 ... 250 sec. 35 sec.
Set the PI-regulation,
see section 26.
7
Neutral zone
0 ... 9 K 3 K
Set the PI-regulation,
see section 26.
Setting range Factory setting Your settings
Control & overviews
Control & overviews
A Time and date See sections 16 & 17
B System information See sections 18 & 19
C
10 Choice of room panel / remote control
0 ... 5 0
11 Reduced temperature dependent
on outdoor temperature
OFF / -29 ... +10 °C -15 °C °C
12 Boost
0 ... 99% 0% %
13 Reference ramping
0 ... 99 min 0 min min
14 Optimising time constant
OFF / 10 ... 59 OFF
15 Adaptive function of room
temperature
OFF / 1 ... 30 OFF
17 Temperature reference feedback
OFF / 1 ... 20K OFF K
20 Optimisation based on room /
outdoor temperature
ON / OFF OFF
21 Total stop
ON / OFF OFF
22 Pump motion
ON / OFF ON
23 Valve motion
ON / OFF OFF
31 Return temperature
limitation - upper limit (X)
-30 ... +15 °C +15 °C °C
32 Return temperature
limitation - upper limit (Y)
10 ... 110 °C 40 °C °C
33 Return temperature
limitation - lower limit (X)
-30 ... +15 °C -15 °C °C
34 Return temperature
limitation - lower limit (Y)
10 ... 110 °C 60 °C °C
35 Return temperature influence
- max
-9.9 ... 0 ... +9.9 °C -2 °C
36 Return temperature influence
- min
-9.9 ... 0 ... +9.9 °C0 °C
37 Adaptive function of return
limitation
OFF / 1 ... 50 25
43 Priority or parallel operation
OFF / 1 ... 99K OFF K
141 Override input selection
OFF / 1 ... 6 OFF
174 Motor protection
OFF / 10...59 min OFF
Service parameters
31b
Service parameters
31a
Circuit I (heating)
Control & overviews
Control & overviews
30 Return temperature limitation
10 ... 110 °C 50 °C °C
35 Return temperature
influence - max
-9.9 ... 0 ... +9.9 -2
36 Return temperature
influence - min
-9.9 ... 0 ... +9.9 0
37 Adaptive function of return
limiter (HWS)
OFF / 1 ... 50 25
40 Charging pump post run
(primary pump P2)
0 ... 9 min 1 min
41 Charging pump post run
(secondary pump P3)
0 ... 9 min 1 min
51 Charging pump / change-over valve
ON / OFF OFF
52 Closed valve / normal operation
ON / OFF OFF
53 Reference temperature at S3 when
charging hot water
ON / OFF OFF
141 Override input selection
OFF / 1 ... 6 OFF
Circuit II (hot water service)
Line Setting range Factory setting Your setting
Circuit I (heating)
196 Service pin LON
ON / OFF OFF
197 LON reset
ON / OFF ON
198 Summer time change
ON / OFF ON
199 Slave address
0 ... 9 15
Line Setting range Factory setting Your setting Line Setting range Factory setting Your setting
32b
Service parameters
10-11
Extended service
Choose between
0 ECL Comfort controller - week plan
circuit I
1 Room panel ECA 60 or remote control
ECA 61 on address A
2 Room panel ECA 60 or remote control
ECA 61 on address B
3 ... 5 Not used
Note! The time control of the hot water circuit is always
dedicated to the week plan of circuit II.
-29 to +10 °C
The setting of reduced temperature depends on
the outdoor temperature, when the outdoor
temperature is above the set limit.
The lower the outdoor temperature, the less the
temperature reduction. When the outdoor
temperature is below the set limit, there is no
temperature reduction.
OFF: The reduced temperature setting will be
constant at all outdoor temperatures.
32a
Adjusting the service
parameters
In addition to the settings in line 1 to 7 on the grey side of the
ECL Card, there is an extended service menu from line 10
and onwards.
When you have entered all your personal settings, turn the
ECL Card over so that the yellow side faces you.
If you want to copy the new settings to the ECL Card
(recommended by Danfoss), see section 34.
Make a note of your new settings on the parameter list in
section 31.
Push repeatedly to reach the lines
numbered 10 and onwards.
Line
number
Value
Range indicator
01
0
Now you can move to any line of your choice.
Set the parameter value.
You can select any of the two circuits no matter
what line you are in. You will not necessarily en-
ter the same line number.
See the service parameters in section 31.
Extended service
100%
0%
-20 -10-29 0 10 2015
Reduction
Outdoor
temp.
o
C
10 Choice of room panel / remote control
Circuit Setting range Factory setting
I 0 ... 5 0
Decides the communication with the room panel or remote
control. Choose either 1 or 2 if you have installed a room panel or
remote control.
11 Reduced temperature dependent on outdoor
temperature
Circuit Setting range Factory setting
I OFF / -29 ... +10 °C -15 °C
The outdoor temperature at which the reduced temperature
setting is switched off. Below this outdoor temperature, the
reduced temperature setting has no influence.
The grey
side of the
ECL Card
The adaptive function will eliminate the difference
between the required and the actual room temperature by
integrating the difference and adjusting the reference for
the flow temperature.
32d
Service parameters 14-15
Dimensioning temperature: The lowest outdoor
temperature at which the heating system can obtain
the desired temperature.
OFF: The adaptive function is cancelled.
1: The desired temperature is adapted
quickly.
30: The desired temperature is adapted
slowly.
32c
Service parameters 12-13
In order to avoid load peaks in the supply network, the
flow temperature reference can be set to increase slowly
after a period with reduced temperature. This causes the
valve to open slowly.
In order to shorten the heating-up period after a reduced
temperature period, the flow temperature can be
increased temporarily.
If a room sensor is installed, the boost stops when the
optimising period is over or the room temperature has
been reached.
°C
T
ref
T
ref
Setting line 13
Time
Set the percentage at which you want the flow
temperature increased temporarily.
Set the ramping time for the controller.
Extended service
Extended service
OFF: No optimisation. The heating starts and stops at
the times set in the week plan.
41
25
Adjust the optimising time constant. The value
consists of a number of two digits. You can select
the following values:
10, 11, ..... 59.
The two digits have the following meaning:
1. digit (system type and heat accumulation of
the building)
2. digit (capacity of the heating system)
12 Boost
Circuit
Setting range Factory setting
I 0 ... 99% 0%
Shortens the heating-up period by increasing the flow
temperature by the percentage you set.
13 Reference ramping
Circuit
Setting range Factory setting
I 0 ... 99 min 0 min
The time in which the flow temperature increases slowly to avoid
load peaks in the supply.
14 Optimising time constant
Circuit
Setting range Factory setting
I OFF / 10 ... 59 OFF
Optimises the start and stop times for the reduced
temperature period to obtain the best comfort at the lowest energy
consumption.
1 light
Radiator
2 medium
system
3 heavy
4 medium Floor heating
5 heavy system
1. digit Heat accumulation System type
of the building
2. digit Dimensioning Capacity
temperature
0 -50 °C large
·· ·
·· ·
5 -25 °C normal
·· ·
·· ·
-05 °C small
15 Adaptive function of the room temperature
Circuit
Setting range Factory setting
I OFF / 1 ... 30 OFF
Controls how fast the room temperature adapts to the
desired temperature.
The grey
side of the
ECL Card
The grey
side of the
ECL Card
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Danfoss ECL Comfort 300 - C37 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI