ABB SOLAR INVERTERS
Quick Installation Guide
PVS-175-TL (175.0 kW), “A.1 Version
BCM.V3103.1
2 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
ATTENTION – A IMPORTANT SAFETY INSTRUCTIONS
This document contains important safety instructions that must be followed during the installation
and maintenance of the equipment.
ATTENTION – A SAVE THESE INSTRUCTIONS
Keep this document in a safe place near the inverter for easy access during installation, operation and
maintenance.
ATTENTION – A The installer must read this document in its entirety before installing or
commissioning this equipment. In addition to what is explained below, the safety and installation
information provided in the product manual must be read and followed. For more detailed information
regarding proper installation and use of this product, refer to the product manual located at www.
abb.com/solarinverters.
ATTENTION – A The product must be used in the manner described in the document. If this is not the
case the safety devices guaranteed by the inverter might be ineffective.
ATTENTION – A All pictures and illustrations shown in this document are indicatives and must
be intended as support for installation instruction only. Actual product may vary due to product
enhancement. Specifications subject to change without notice. The latest version of this document is
available on the ABB website.
3
EN
Table of contents
1. Reference number index 4
2. Labels and Symbols 8
3. Models and range of equipment 9
4. Lifting and transport 10
4.1 Transport and handling 10
4.2 Unpacking and checking 10
4.3 Lifting 10
5. List of supplied components 12
6. Choice of installation location 13
6.1 General recommendation on
installation position 13
6.2 Tilting admittance 13
6.3 Distances 13
7. Mounting Instructions 15
7.1 Bracket assembly 15
7.2 Assembly the Inverter to the bracket 16
7.3 Opening the Wiring box cover 18
7.4 Final fastening operations 18
7.5 Opening the power module cover 19
7.6 Connection of the AC interface cables 20
7.7 Connection of the interface signal
connectors 21
7.8 Connection of the DC interface cables 21
8. Routing the cable to the inverter 23
9. Grid output connection (AC side) 24
9.1 Characteristics and sizing of the
protective grounding cable 24
9.2 Load protection breaker (AC disconnect
switch) and differential protection
downstream of the inverter 24
9.3 Characteristics and sizing of the line
cable 25
9.4 AC output cables connection 25
10. Input connection (DC) 28
11. Connection of the communication
and control signals 31
11.1 Communication and control board
references 31
11.2 Connections to the communication
and control board 32
11.3 Ethernet connection 32
11.4 Serial communication connection
(RS485) 33
11.5 Remote control connection 34
11.6 Multifunction Relay connection
(ALARM and AUX) 34
11.7 Demand Response Mode 0 (AS/NZS
4777.2) 35
12. Description of LED panel 35
13. Commissioning 37
13.1 Commissioning via ABB Installer for
Solar Inverters mobile APP 38
13.2 Commissioning via Web User Interface 39
14. Technical data table 40
4 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
1. Reference number index
Inverter external view
01 Power module 08 Status LEDs 15 Cover support brackets
02 Wiring box 09 AC disconnect switch (-SX2, -S2 only) 16 Side latches
03 Mounting bracket 10 Protective earth point (ext.) 17 Rear pins for bracket assembly
04 Handles 11 Phases cable glands 18 DC input quick fit connectors
05 Cover quarter cam locks 12 Protective earth cable gland 19 DC disconnect switches
06 Front power module cover 13 Signal cable glands
07 Front wiring box cover 14 RS485 Service connector
PVS
03
01
02
17
17
06
09
17
17
15
18
13
05
08
09
07
05
11
19
19
19
04
05
04 05
16
04
14
10
04
16
12
15
09
5
EN
Wiring box internal view
20 Junction screws 25 AC overvoltage surge arresters 30 Opening for DC interface cables
21 DC surge arrester plate 26
Communication and control
board
31 AC interface cable lugs
22 DC cable duct 27 AC connection busbar 32 Interface signal connectors (female)
23 AC protective shield 28 Protective earth point (int.)
24
DC overvoltage surge
arresters
29 DC interface faston connectors
B1
B2
RST
B1
B2
RST
B1
B2
RST
32
30
28
20
24
22
31
27
23
26
20
25
24
29
21
6 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
Power module internal view
33 DC interface cables 35 Interface signal connectors (male) 36 Interface protective earth point
34
AC interface
connection point
35
34
34
33
36
7
EN
Communication board
37
ABB RS485 service Ethernet
connector (RJ45) (service only)
41 Alarm terminal block 45 Ethernet connector 1 (RJ45)
38
RS485 ABB service 120Ohm
termination res. (service only)
42
Remote ON/OFF terminal
block
46 USB connector
39 DRM0 activation switch 43 RS485 line terminal block 47 CR2032 Backup battery
40 RS485 line 120Ohm termination res. 44 Ethernet connector 2 (RJ45)
J9 J10
X2
J2
S2
J4
J1
S1 S3
J3
J6
47
37
41
39
40
42
38
43
46
44
45
8 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
2. Labels and Symbols
The labels on the inverter and on wiring box have the Agency marking, main technical data and identification
of the equipment and manufacturer.
NOTE – D The labels shown below have to be intended as example only.
FORBIDDEN – H The labels affixed to the equipment must NOT be removed, damaged, stained,
hidden, etc., for any reason whatsoever.
PVS-175
Power module
Wiring Box
A
A
E
MODEL NAME
POWER-ONE ITALY S.p.A
Via S.Giorgio 642, Terranuova Bracciolini (AR), 52028, Italia
P/N:PPPPPPPPPPP
WO:XXXXXXX
SO:SXXXXXXXX Q1
SN:YYWWSSSSSS WK:WWYY
A
B
C
D
A. Inverter/wiring box model
B. Inverter/wiring box Part Number
C. Inverter/wiring box Serial Number
D. Week/Year of manufacture
E. Main technical data
An additional Communication Identification label is applied on the wiring box.
The Communication Identification label is divided in two separate parts by a dashed line; take the bottom
part and apply it on the plant documentation. (ABB recommend to create a plant map and apply the
Communication Identification label on it).
SN WLAN: SSSSSSSSSS
PN WLAN: .V2PVKA 53.1
Mac Address:
AA:BB:CC:DD:EE:FF
PK: 0000 - 0000 - 0000- 0000
SN WLAN: SSSSSSSSSS
SN Wiring Box: ZZZZZZZZZZ
Remove and apply on the plant documentation
MAC: AA:BB:CC:DD:EE:FF
F
G
H
J
I
F. WLAN embedded board Serial Number
G. WLAN embedded board Part Number
H. MAC address:
- To be used to obtain the SSID of the wireless access point
created by the inverter: ABB-XX-XX-XX-XX-XX-XX (where “X
is a hex digit of the MAC address).
- To be used to obtain the “Host Name”: http://ABB-XX-
XX-XX-XX-XX-XX.local (where “X” is a hex digit of the MAC
address).
I. Product Key:
To be used as wireless access point password, or to be used
to access to the Web UI as username and password in case
of lost credentials, and to commission inverter using ABB
Installer for Solar Inverters.
J. QR Code:
To be used to commission inverter using ABB Installer for
Solar Inverters for claiming process.
9
EN
In the manual and/or in some cases on the equipment, the danger or hazard zones are indicated with
signs, labels, symbols or icons.
Always refer to instruction
manual
General warning
Important safety information
Hazardous voltage
Protection rating of equipment Temperature range
Without isolation
transformer
Positive pole and negative pole
of the input voltage (DC)
Always use safety clothing
and/or personal safety devices
Point of connection for
grounding protection
Direct and alternating currents,
respectively
Hot surfaces
Time need to discharge
stored energy
3. Models and range of equipment
NOTE – D The choice of the inverter model must be made by a qualified technician who knows about the
installation conditions, the devices that will be installed outside the inverter and possible integration
with an existing system.
Wiring box
Model Number Description
WB-S-PVS-175-TL
Input with 24 quick fit connectors pairs (2 each MPPT) (18)
DC side varistor
DC disconnect switches (19)
WB-S2-PVS-175-TL
Input with 24 quick fit connectors pairs (2 each MPPT) (18)
DC side varistor
DC disconnect switches (19)
AC disconnect switch (09)
WB-SX-PVS-175-TL
Input with 24 quick fit connectors pairs (2 each MPPT) (18)
SPD Type 2 Pluggable Cartridges (DC & AC) (24) (25)
DC disconnect switches (19)
WB-SX2-PVS-175-TL
Input with 24 quick fit connectors pairs (2 each MPPT) (18)
SPD Type 2 Pluggable Cartridges (DC & AC) (24) (25)
DC disconnect switches (19)
AC disconnect switch (09)
Power Module
Model Number Description
PVS-175-TL-POWER-MODULE-1 Inverter section / power module with precharge
PVS-175-TL-POWER-MODULE-2 Inverter section / power module without precharge
10 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
4. Lifting and transport
4.1 Transport and handling
Transportation of the equipment, especially by road, must be carried out using appropriate vehicles and
methods to protect the components (particularly electronic components) from violent shocks, humidity,
vibration, etc.
4.2 Unpacking and checking
The components of the packaging must be disposed on in accordance with the regulations in force in the
country of installation.
When you open the package, check that the equipment is undamaged and make sure all the components are
present. If you find any defects or damage, stop unpacking and consult the carrier, and also promptly inform
the Service ABB.
Equipment weight
Device Weight (kg/lb) Lifting points Holes or Eyebolts UNI2947
Power module 76 kg 4 M8. Kit of handles (04) and eyebolts (to be ordered)
Wiring box ~ 77 kg 4 M8. Kit of handles (04) and eyebolts (to be ordered)
4.3 Lifting
ATTENTION – A Risk of injury due to the heavy weight of the equipment!
ABB usually stores and protects individual components by suitable means to make their transport and
subsequent handling easier. Nonetheless, as a rule, it is necessary to turn to the experience of specialised
staff to take charge of loading and unloading components.
The power module and the wiring box must be lifted using the 4 handles (04) or alternatively using suitable
lifting equipment. The means used for lifting must be suitable to bear the weight of the equipment.
ATTENTION – A In case of manual lifting the number of required operators necessary to lift the
equipment must be in accordance to local regulations relating lifting limits per operator.
The handles (04) must be mounted into the designated holes located on the enclosures; If lifting with ropes,
M8 eyebolts must be mounted in the same holes.
ATTENTION – A Handling and installation operations shall be performed only by using the special
tools and accessories provided with “PVS-175 Installation Kit” that have to be ordered separately. The
use of these equipment are mandatory to safely install the inverter. Refer to “Kit of recommended
spare parts” chapter content in the user manual for further information.
ATTENTION – A DO NOT grab the equipment from the rear flange! Risk of injury due to cutting
surfaces and risk of equipment damange. Always use proper lifting equipment!
11
EN
It is required to use one of the following lifting methods to move the equipment during installation or
maintenance phases:
PVS
Manual lifting (handles)
PVS
Ropes lifting (eyebolts)
ATTENTION – A Always consider the center of gravity of the enclosures while lifting.
ATTENTION – A Pay attention to completely tight the thread of the handles or eye-bolts.
PVS
Center of gravity (wiring box)
Center of gravity (power module)
12 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
ATTENTION – A In case of manual lifting it’s suggested to use a support plan (e.g. a table) to place
the equipment during the lifiting operation, to allow the change of hands position.
BA
A
B
5. List of supplied components
Available components for wiring box Qty
Connector for connection of
the configurable relay (41) and
aux relay (41) (pre-installed on
communication board (26))
2
Connector for connecting the
Remote ON/OFF (42) signal and
RS485 (43) (pre-installed on
communication board (26))
3
Two-hole gasket (6mm Ø) for
PG21 service cable glands (13)
and cap
2+2
Key tool for front covers quarter
cam-lock (05)
1
M8 bolt and washers for external
protective earth connection
point (10)
1+1+1
In addition to what is explained in this guide, the safety and installation information provided in the installation manual must be read and followed.
The technical documentation and the interface and management software for the product are available at the website.
XXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXX
ABB solar inverters
Technical documentation 1
Available components for power module Qty
M6 bolts with washers for AC
interface connection point
(phases) (34)
3
M5 bolts with washers for AC
interface connection point (MID
BULK) (34)
1
M5 nut and washers for Interface
protective earth point (36)
1+2
Sheating for DC interface cables
(33)
2
Available components for brackets Qty
M8 bolts with washers for
mechanically securing the half-
brackets
2
M6 screws for mechanically
securing the wiring box to the
bracket
2
13
EN
6. Choice of installation location
6.1 General recommendation on installation position
See characteristics and technical data paragraph to check the required environmental conditions
(protection rating, temperature, humidity, altitude, etc.).
The installation location shall be easily accessible.
Installation of the unit in a location exposed to direct sunlight NOT acceptable. (Add awning in case of
direct sunlight installation).
Final installation of the device must not compromise access to any disconnection devices that may be
located externally.
Do not install in small closed rooms where air cannot circulate freely.
Always ensure that the flow of air around the inverter is not blocked so as to prevent overheating.
Do not install in locations where flammable substances or gases may be present.
Do not install on wooden walls or other flammable supports.
Install on a wall or strong structure suitable to bear the weight.
Do not install in rooms where people live or where the prolonged presence of people or animals is expected,
because of the high noise that the inverter produces during operation. The level of the sound emission is
heavily influenced by where the appliance is installed (for example: the type of surface around the inverter,
the general properties of the room, etc.) and the quality of the electricity supply.
All installations over 6500’ (2,000 meters) must be assessed by ABB Technical Sales to determine the proper
datasheet derating.
6.2 Tilting admittance
The installation can be carried out with a maximum
inclination as indicated in the figures beside.
6.3 Distances
Hardware and software maintenance on device entails removing the front
cover. Check that the correct installation safety distances are observed in
order to allow routine check and maintenance operations.
Provide sufficient working space in front of the inverter that allows to open
the front covers (06)(07) and to make connections on the wiring box.
Install at a height which takes into consideration the weight of the appliance
and in a position which is suitable for servicing, unless suitable means are
provided to carry out the operation.
If possible, install at eye-level so that the status LEDS (08) can be seen easily.
Respect the minimum distances from objects around the inverter that could prevent the inverter installation
and restrict or block the air flow.
ATTENTION – A Do not install any object (e.g. AC or DC cables) that could be damaged by overheating
from outgoing hot air flow from top and side fan sections T= +15 °C compared to ambient
temperature). In case of this kind of installation needs, please evaluate the installation of a proper air
deflector. Always respect the minimum distances required.
A
C
B
C
PVS-175
MINIMUM CLEARANCE
DISTANCES
NO
OK
30° MAX
Vertical Tilting
±1° max
PVS-175
PVS-175
PVS-175
Side Tilting
50cm
*100cm
(*): minimum free
space to operate
with the inverter
14 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
The minimum clearance distances depends from multiple factor:
Ventilation flow on the top side of
the inverter. The upper (A) minimum
required free space must be 25 cm.
Possible flooding or damage during
grass cutting. It changes the bottom
(B) required free space: If the inverter
is installed in a place where there are
risks of flooding or there is need to
cut the grass growing underneath
the unit, the bottom (B) minimum
recommended free space is 50 cm;
otherwise in case the inverter is
installed in a place where there’s no
risks of flooding or grass cutting
evenience, the bottom (B) minimum
required free space can be reduced
to 15 cm.
Cables bending radius. Sides (C) minimum required free space
may depends from cable type (cable dimension, bending radius,
etc..): this evaluation must be done by the installer during the plant
design phase. In any case minimum required free space for proper
ventilation of the unit (near side fans) cannot be under 15 cm on
the right side and 30cm on the left side.
ATTENTION – A In case of manual installation (using handles (04)) consider a free side space to lift
the inverter of 60 cm minimum.
ATTENTION – A In case of installation with lifting equipments (eyebolts and ropes) the side distances
(C) could be reduced at the minimum required but a subsequent manual lifting it will no longer be
possible: in this case the lifting equipments must remain available on the field for any subsequent
operation.
Installation of multiple units
When installing multiple units position the inverters side by side paying attention to keep the minimum
clearance distances (measured from the outer edge of the inverter) for each inverter specified in the
following graph.
The installation of two inverters positioned back to back is also permitted on a structure which must be
composed of a 2 or 3 frame supports (refer to “Mounting with a support bracket” chapter). In this case the
minimum recommended distance between the units in order to avoid the use of an air deflector is 30cm.
30 cm
50 cm
20”
50 cm
20”
50 cm
20”
NOTE – D Please refer to the warranty terms and conditions to evaluate any possible warranty
exclusions due to improper installation.
25
cm
25
cm
PVS-175
C C
15
EN
7. Mounting Instructions
7.1 Bracket assembly
Assembly the two side bracket pieces together
with the central bracket, by sliding it as shown in
the picture and paying attention to the orientation
of the pieces (refer to arrow and “UP” markings
on the brackets): side brackets arrow have to be
turned downwards, central bracket have to be
turned upwards.
Slide the central bracket in order to match the
two holes with the centerning pins of the side
brackets.
Use the two M8 screws with flat and spring
washers (supplied) to fix the pieces of the bracket
together.
Position the bracket (03) perfectly level on the
support and use it as drilling template (consider
the overall dimensions of the power module and
the wiring box).
It is the installer’s responsibility to choose
an appropriate number and distribution of
attachment points. The choice must be based
on the type of support (wall, frame or other
support), the type of anchors to be used, and
their ability to support 4 times the inverter’s
weight (4x153Kg=612Kg for all models).
16 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
Attach the bracket (03) to the support with at
least 6 attachment screws (shown in RED) or at
least 6 frame fixing bracket for frame mounting
(shown in BLUE).
Depending on the type of anchor chosen, drill
the required holes to mount the bracket (03).
The pictures shown the recommended minimum
fixing point depending to the type of support.
Wall mounting minimum fixing points
Frame mounting (2 supports)
minimum fixing points
Frame mounting (3 supports)
minimum fixing points
In case of use of “frame fixing brackets” (see
picture below as example) it will be possible to fix
the bracket to the frame structure without drill
any additional holes.
Fix the bracket (03) to the support.
7.2 Assembly the Inverter to the
bracket
ATTENTION – A Handling and installation
operations shall be performed only by using
the special tools and accessories provided
with “PVS-175 Installation Kit” that have
to be ordered separately. The use of these
equipment are mandatory to safely install the
inverter. Refer to “Kit of recommended spare
parts” chapter content in the user manual for
further information.
Lift the wiring box up to the bracket (03) using
the handles (04) or the M8 eyebolts.
ATTENTION – A Risk of injury due to the
heavy weight of the equipment. Always
consider the center of gravity of the
enclosures while lifting.
Insert the heads of the two rear attachment pins
(17) (placed on the rear part of the wiring box)
into the two slots on the bracket (03). Check
that the pins (17) has been correctly inserted in
the slots as shown in the picture before releasing
the wiring box.
PVS
17
17
EN
Remove the handles (04) or eye bolts.
Insert the two gasket protective covers sliding
the positioning pins (shown in red in the picture)
into the proper bracket (03) holes. If the mounting
is correct the gasket protective cover will have a
locked position.
PVS
Lift the power module up to the bracket (03) and
over the wiring box, using the handles (04) or the
M8 eyebolts.
Insert the heads of two rear attachment pins (17)
(placed on the rear part of the power module) into
the slots on the bracket (03).
PVS
17
ATTENTION – A Risk of injury due to the
heavy weight of the equipment. Always
consider the center of gravity of the
enclosures while lifting.
Remove the previously installed gasket protective
covers from the inverter by slinding them pulling
from the handles.
PVS
NOTE – D Gasket protective covers and
handles can be reused for a new installation.
Fasten all of the four side closures (latches) (16)
as shown in the pictures.
PVS
A
B
16
ATTENTION – A Risk of injury due to the
high strength of latches (16) Use the proper
protection gloves.
18 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
7.3 Opening the Wiring box cover
Using the key tool provided with the installation
kit content in the wiring box package, open the
three cover quarter cam locks (05) following the
proper ways as shown in the related silkscreens
on the Wiring box cover (07).
(only for -S2, -SX2 version) Set the wiring box AC
disconnect switch (09) to OFF position; otherwise
it will not be possible to open the Wiring box
cover (07).
PVS
Open the Wiring box cover (07) and use the cover
support brackets (15) to lock the cover (07) in
open position.
15
ATTENTION – A Pay attention to properly
secure the cover support brackets (15) in
order to avoid falling of the cover!
7.4 Final fastening operations
In order to reach the two junction screws (20) and
complete the power module and wiring box mating,
the DC surge arrester plate (21) has to be opened
as follow:
Remove the DC cable duct (22) from the DC surge
arrester plate (21).
22
21
Remove the three M5 screws from the DC surge
arrester plate (21).
19
EN
Rotate the DC surge arrester plate (21) as shown
in the picture below.
21
Tighten the two hexagonal junction screws (20)
with a tightening torque of 12 Nm.
20
20
20
Close the DC surge arrester plate (21) using
the three M5 screws previously removed with a
tightening torque of 3 Nm.
Insert the DC cable duct (22) previously removed
to the DC surge arrester plate (21).
Tighten the two side screws (supplied) with a
tightening torque of 5 Nm, to avoid the tilting of
the bottom part of the inverter.
PVS
Close the Wiring box cover (07).
7.5 Opening the power module
cover
Using the key tool provided with the installation
kit content in the wiring box package, open the
three cover quarter cam locks (05) following the
proper ways as shown in the related silkscreens
on the power module cover (06).
PVS
20 Quick Installation Guide - PVS-175-TL “A.1 Version”
EN
Open the power module cover (06).
7.6 Connection of the AC interface
cables
The AC interface cable lugs (31) (RST phases, PE
and MID BULK) are situated into his cable housing
on the top side of wiring box.
31
34
Fix the R, S and T phases and MID BULK cable lugs
(31) to the respective AC interface connection
point (34) situated on the internal bottom
side of power module, paying attention to the
correspondence of the phases with the labels,
using the M6 bolts (for phases) and the M5 bolt
(for MID BULK) supplied in the power module
installation kit.
31
34
ATTENTION – A In case of a wrong phase
sequence the inverter will not connect to the
grid and it will provide an error state.
ATTENTION – A The cable lugs must be
installed with a tightening torque of 5 Nm
for phases (M6 bolts) and 3 Nm for MID-BULK
(M5 bolts).
Fix the protective earth cable lug (31) to the
protection earth connection point (36) situated
on the internal bottom side of power module,
using the washers and bolt supplied in the power
module installation kit, as shown in the following
picture:
1
2
3
4
1 = toothed washer
2 = cable lug
3 = toothed washer
4 = M5 nut
36
31
ATTENTION – A The cable lug must be
installed with a tightening torque of 3 Nm.
ATTENTION – A Any failure of the inverter
when it is not connected to earth through the
appropriate connection point is not covered
by the warranty.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46

ABB PVS-175-TL Series Quick Installation Manual

Category
Power adapters & inverters
Type
Quick Installation Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI