MGE Galaxy 3500

APC MGE Galaxy 3500 Product information

  • Hello! I am an AI chatbot trained to assist you with the APC MGE Galaxy 3500 Product information. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
MGE™Galaxy™
3500Series
10-40kVA380/400/415V
10-30kVA208/220V
Operation
TableofContents
AboutthisManual..........................................................................................................1
FindUpdatestothisManual.....................................................................................1
Safety....................................................................................................................................2
Overview..............................................................................................................................3
UserInterface................................................................................................................3
DisplayInterface..........................................................................................................4
MenuTree...........................................................................................................................5
Operation............................................................................................................................7
Modes..............................................................................................................................7
NormalOperation......................................................................................................7
BatteryOperation......................................................................................................7
InternalBypassOperation........................................................................................7
ExternalMaintenanceBypassOperation...................................................................7
OptionalParallelOperation........................................................................................7
SingleSystemwithoutExternalBypassPanel....................................................8
TurnintoInternalBypass...........................................................................................8
TurnintoNormalOperation.......................................................................................9
PerformaTotalPowerOff..........................................................................................10
PerformaRestart.......................................................................................................11
SingleSystemwithExternalBypassPanel..........................................................12
TurnintoExternalMaintenanceBypass....................................................................12
TurnintoNormalOperationfromExternalMaintenanceBypass...............................13
PerformaTotalPowerOff..........................................................................................14
PerformaRestart.......................................................................................................14
ParallelSystem.............................................................................................................15
TurnintoExternalMaintenanceBypass....................................................................15
TurnintoNormalOperationfromExternalMaintenanceBypass...............................16
PerformaTotalPowerOff..........................................................................................17
PerformaRestart.......................................................................................................17
IsolateoneUPSinaParallelSystem.........................................................................18
TurntheIsolatedUPSintoNormalOperation............................................................18
SingleandParallelSystems.....................................................................................19
TurnLoadoff/onviatheDisplayInterface.................................................................19
TurnLoadoffDisconnecttheUPSOutputtotheLoadEquipment.........................19
TurnLoadOnConnecttheUPSOutputtotheLoadEquipment.............................20
ViewtheStatusScreens............................................................................................20
ViewLogging.............................................................................................................22
ViewStatistics...........................................................................................................23
UsetheDiagsScreen................................................................................................24
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
i
Conguration....................................................................................................................25
Settings...........................................................................................................................25
ChangetheClock,theAlarmThresholds,andtheDustFilterStatus........................25
Clock.........................................................................................................................26
DustFilter..................................................................................................................27
AlarmThresholds......................................................................................................28
ChangetheBeeperSetup,theContrast,andtheLanguage......................................29
Maintenance......................................................................................................................30
PartsReplacement......................................................................................................30
DetermineifyouNeedaReplacementPart...............................................................30
ReturnPartstoAPC..................................................................................................30
RemovetheFrontPanel............................................................................................31
InstalltheFrontPanel................................................................................................32
InspecttheDustFilter...............................................................................................32
StoretheBatteriesandtheUPSSystem....................................................................34
BatteryModule.................................................................................................................36
BatteryReplacement.........................................................................................................37
Troubleshooting..............................................................................................................40
StatusandAlarmMessages.....................................................................................40
DisplayMessages......................................................................................................40
DustFilter.......................................................................................................................45
ii
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
AboutthisManual
ThismanualisintendedfortheuseroftheMGEGalaxy3500series.Itreferstoimportantsafety
warningsandinstructions,givesanintroductiontothedisplayinterface,andprovidesinformationon
operation,loadconnection,partsreplacement,troubleshooting,totalpoweroffandrestart.
Note:OnlygraphicsofMGE™Galaxy™3500productswithbuilt-inbatteriesareshownin
thismanual,butthemanualisintendedforusersofoneormoreunitswithintheMGE™
Galaxy™3500series.Mostillustrationsshow523mmenclosuresbutapplytoboth
enclosuresizes.Anydifferencesbetweentheenclosuresizeswillbeaddressedinthemanual.
FindUpdatestothisManual
Youcancheckforupdatestothismanualonwww.apc.com.Lookforthelatestletterrevision(A,
Betc.)ofthemanual.
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
1
Safety
WARNING:AllsafetyinstructionsintheSafetySheet(990-2940)mustberead,
understoodandfollowedpriortohandling/usingthesystem.Failuretodosocould
resultinequipmentdamage,seriousinjury,ordeath.
WARNING:Forsafetyreasons,onlyqualiedpersonnelisallowedtoperformthe
proceduresdescribedunderthechapters“Operation”and“Maintenance”.
Note:Mostillustrationsshow523mmenclosuresbutapplytobothenclosuresizes.Any
differencesbetweenthetwoenclosuresizeswillbeaddressedinthemanual.
2
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
Overview
UserInterface
ThefourLEDstotheleftofthedisplayindicatetheoperationalstatusoftheUPS.Thevenavigation
keystotherightareusedtoselectandopenmenuitems,toaccessinformation,changesystemparameters,
andtogetcontext-sensitivehelp.
ALOADON
WhenthegreenLEDislit,theUPSprovidespowertotheloadequipment.
B
ONBA TT
WhentheyellowLEDislit,powerowsfromthebatteriestotheload.
CBYPASS
WhentheyellowLEDislit,powertotheloadissuppliedthroughbypass.
D
FAULT
WhentheredLEDislit,afaultconditionexists.
E
LCDSCREEN
Displaysalarms,statusdata,instructionalhelp,andcongurationitems.
F
UPANDDOWN
NA VIGA TIONKEYS
Usedtoscrollthroughandselectmenuitems.
G
HELPKEY
Openscontext-sensitivehelp.
HENTERKEY
Opensmenuitemsandconrmschangestothesystemparameters.
I
ESCKEY
Returnstothepreviousscreendisplayed.
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
3
DisplayInterface
TheOverviewScreenisthemainentrancetotheuserfunctionsofthedisplayinterface.TheUP/DOWN
navigationkeystakeyoufromonescreentoanother.
TheENTERkeytakesyoufromtheOverviewScreentotheMainScreen.
FromtheMainScreenitispossibletocommand,congure,andmonitorthesystemthroughthesubmenu
screens:Control,Status,Setup,LCM,Logging,Display,Diags,andHelp(see“MenuTree“).The
selectorarrow(→)iscontrolledbytheUP/DOWNnavigationkeys.Thearrowmarkstheitemyou
mayopenbypressingENTER.
OverviewScreen
Chrgxxx%
Loadxxx%
xxxVinxxxVoutxxHz
Runtime:xxhrxxmin
Press
MainScreen
ControlLogging
StatusDisplay
SetupDiags
LCMHelp
Press
4
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
MenuTree
Caution:Thedisplayprovidesaccesstomorefunctionsthandescribedinthismanual.
ThosefunctionsshouldnotbeaccessedwithouttheassistanceofAPCCustomerSupport
inordertoavoidunwantedloadimpacts.ForAPCbySchneiderElectricWorld-Wide
CustomerSupport,refertothebackcoverofthismanual.Ifyoubyaccidentgobeyondthe
functionsdescribed,pressESCtoreturntopreviousscreens.
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
5
Themenutreeprovidesaquickoverviewofthefunctionsandviewsyoumayaccess.
ControlTurnLoadOff/On
UPSinto/outofBypass
Status
VinVbypV outDustlter
linlbyplout
Resetdust
lter
kW&kV A
FrequenciesLoad
Load&Bat&RuntimeShutdownRuntime
BatAmpHr/UPSTempDefault
Par.
redund.
AlarmThresholds
System
OverviewScreen
ParallelstatusAlarms
Clock
Other
Setup
Settings
Chrgxxx%
Loadxxx%
xVinxV outxHz
Runtime:xxhr
LCMAlarmsPending
LCMContactInfo
LCMAlarmSettings
LCM
LifeCycleMonitoring
Control
Status
Setup
LCM
Logging
Display
Diags
Help
Language
MainMenu
Screen
ViewLog
Contrast
ViewStatistics
Beep.Setup
LoggingLoggingMenu
Display
FW
FontPack
DisplayDisplaySetup
Int.mechByp.SW
DiagsFaultsandDiagnosticsQ3ExternalBypSW
SystemInformationStatusfromMBP
SwitchStatus
RawStatusData
Onanyscreen
andanyline,press?
Help
forcontext
sensitivehelp
6
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
Operation
WARNING:Forsafetyreasons,onlyqualiedpersonnelisallowedtoperformthe
operationproceduresdescribedinthischapter.
Modes
TheUPShasdifferentoperationmodes.IftheinstallationincludesaMaintenanceBypassPanel(MBP),
anexternalmaintenancebypassoperationmodewillalsobeavailable.
NormalOperation
TheUPSconvertsutility/mainspowertoconditionedpowerfortheconnectedload.
BatteryOperation
TheUPSprovidespowertotheconnectedloadfromitsinternaland(ifavailable)externalbatteriesfor
aniteperiod.TheUPStransferstobatteryoperationifthesupplyofutility/mainspowerfails,oris
outsidethepre-denedlimits.
InternalBypassOperation
Internalbypasskeepstheloadsuppliedwithutility/mainspowerduringmaintenanceoftheUPSpower
sections.Ininternalbypassoperation,utility/mainspowerissentdirectlytotheconnectedloadbypassing
allinternalUPSfunctionsandlters.Batteryback-upisnotavailableininternalbypassoperationeven
thoughthebatteriesareinplace.
ExternalMaintenanceBypassOperation
TheUPScanbeconnectedtoanoptionalexternalMBP .Whenactivated,thispanelbypassestheentire
UPSenclosure,feedingutility/mainspowerdirectlytotheload.AnactivatedexternalMBPcompletely
isolatestheUPSandallowsmaintenancetobeperformed.AnexternalMBPismandatoryiftheUPS
isrunninginparallel.
OptionalParallelOperation
TheconnectedloadispoweredbymultipleUPSunitstoincreasesystemredundancyortoincreasepower.
Theinternalmechanicalbypassleverisnotavailable.
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
7
SingleSystemwithoutExternalBypassPanel
WARNING:Forsafetyreasons,onlyqualiedpersonnelisallowedtoperformthe
operationproceduresdescribedinthischapter.
TurnintoInternalBypass
WARNING:Inbypassoperationthebatteriesarestillpowered.Ifatotalpower
offisrequired,theloadmustbeoff,andthebatteriesmustbepulledouttothered
disconnectline,seethesection“PerformaT otalPowerOff“inthischapter.
Caution:TheloadisnotprotectedbytheUPSandthepowerisnotconditionedwhenthe
internalmechanicalbypassleverisactivated.
Note:Thisprocedureisnotapplicabletoparallelsystemsastheinternalmechanicalbypass
leverisunavailable.
1.IftheUPSisrunningandcontrollablethrough
thedisplay,carryoutsteps2-5.Ifnot,go
directlytostep6.
2.FromtheOverviewScreen,pressENTER.
Use
Chrgxxx%
Loadxxx%
xxxVinxxxVoutxxHz
Runtime:xxhrxxmin
Press
3.GotoControlbyusingtheUP/DOWN
navigationkeysandpressENTER.
Use
ControlLogging
StatusDisplay
SetupDiags
LCMHelp
Press
4.GotoUPSintoBypassbyusingtheUP/DOWN
navigationkeysandpressENTER.
Use
UPSintoBypass
DoSelftest
SimulatePowerFail
StartRuntimeCal
Press
8
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
5.GotoYES,UPSintoBypassbyusingthe
UP/DOWNnavigationkeysandpressENTER.
Use
Confirm:
UPSintoBypass
NO,ABORT
YES,UPSintoBypass
Press
6.CheckthattheUPSisinbypass.Thegreen
(LOADON)andtheyellow(BYPASS)LEDs
areilluminated.
WARNING:Forsafetyreasons,
onlyqualiedpersonnelisallowed
toperformthefollowingsteps.
7.RemovethefrontpanelfromtheUPS(see
“RemovetheFrontPanel“).
8.Turntheinternalmechanicalbypasslever
upwardstoactivateit.Theloadwillnowbe
supporteddirectlybyutility/mainspower.
9.Reinstallthefrontpanel.
TurnintoNormalOperation
Caution:NeverattempttoswitchbacktheUPSintonormaloperationtillyouhaveveried
thattherearenointernalUPSfaults.
1.CheckthattheUPSisinbypass.Thegreen(LOADON)andtheyellow(BYPASS)LEDsare
illuminated.
2.Turnthemechanicalbypassleverdownwardsintoahorizontalpositiontodeactivatetheinternal
bypassoperation.
3.IftheUPShasnotreturnedtonormaloperation:PressESCtoreturntothepreviousmenusand
turnoutofbypassfromthedisplayviaControl>UPSoutofbypass>Y es,UPSoutofbypass.
4.CheckthattheUPSisinnormaloperation.Theyellow(BYPASS)LEDturnsoffandthegreen
(LOADON)LEDremainsilluminated.
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
9
PerformaTotalPowerOff
Note:InordertocarryoutthisproceduretheloadsupportedbytheUPSmustbeturnedoff.
10/100Base-T
Probe
AP9619NetworkManagementCardEM
Reset
Output
Pwr
Zone
10/100
ON
OFF
3
4
5
6
A
B
B
C
A
Mainsbreaker
B
UPS
C
XREnclosure
1.CheckthattheloadwhichissupportedbytheUPSisturnedOFF.
2.FromtheUPS:TurnloadOFFfromthedisplayviaControl>TurnLoadOff>Y es,Turn
LoadOff.
3.FromtheXREnclosure(s)(ifavailable):SettheDCdisconnectswitch(es)topositionOFF.
4.FromtheUPS:Disconnectthebatteries(ifavailable)bypullingthemouttothereddisconnect
lineshownoneachbatteryunit.
5.FromtheXREnclosure(s)(ifavailable):Disconnectthebatteriesbypullingthemouttothered
disconnectlineshownoneachbatteryunit.
6.Settheutility/mainsbreakertopositionOFForLOCKED-OUT.IftheUPShasdualutility/mains
supply,setbothsuppliestopositionOFForLOCKED-OUT.
WARNING:Thelockoutproceduresattheutility/mainsbreakermustbefollowed.
Ifnecessary,installapadlock.
Note:FordetailsonhowtoremoveBatteryLocks(ifavailable)(seethesection“Replacea
BatteryModule“andhereunder“RemoveandInstallBatteryLocks“).
10
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
PerformaRestart
WARNING:Onlyqualiedpersonnelfamiliarwiththeconstructionandtheequipment
mayrestarttheUPS.
1.Settheutility/mainsbreakertopositionON.2.IfyourinstallationincludesanXRBattery
EnclosurewithaDCdisconnectswitch,setthe
DCdisconnectswitchtopositionON.
Note:Waitapproximately30
secondsforthesystemtobootup
andcarryoutaselftest.
Aftersystemboot-up,thedisplaywillautomatically
askyoutoconrm/selectvoltageandfrequencyas
showninthefollowing.
Voltageconrmation.Atrestart,thedisplaywill
promptyouthroughthefollowingscreens:
3.WhentheConrmVoltagepromptappearson
thescreen,gotothedesiredvoltageusingthe
UP/DOWNnavigationkeysandpressENTER.
Use
ConfirmVoltage
Use400V
Yes,use400V
No,selectanother
Press
4.WhenthepromptApplyloadappears,goto
YesusingtheUP/DOWNnavigationkeysand
pressENTERifyouwanttheUPStoprovidea
loadoutputnow.(IfyoudonotwantaUPSload
outputatthispoint,gotoNo).
Use
Applyload
Yes
No
Press
5.Thegreen(LOADON)LEDisnowlit.Press
ESCtwotimesandthedisplaywillreturntothe
OverviewScreen.
Use
Chrgxxx%
Loadxxx%
xxxVinxxxVoutxxHz
Runtime:xxhrxxmin
Press
Note:TheUPSisnowreadytosupporttheload.
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
11
Note:
Theauto-detectiononfrequencyhasbeenimprovedinrmwareversion5.1andhigherfor
singleunits(withparallelcapability).Auto-detectiononfrequencyisanoptionintheSetup
menu(inalignmentwiththevalues50Hzand60Hz)butalsoafeaturewherebyasingleUPS
systemdetectstheinputfrequencyinasystemstart-up.
IftheUPSsystemduringastart-updetectsaninputfrequencydifferentfromwhatisalready
set,thentheuserwillbeaskedtochoosethedetectedfrequency.Thesystemwillnotchange
frequencybyitself.Forsafetyreasons,theinputfrequencycanonlybechangedbytheuser.
Theauto-detectiononfrequency-featureisonlyapplicableinasinglesystemstart-up.Ifa
problemoccurscallAPCCustomerSupport(seethebackcoverofthismanual).
SingleSystemwithExternalBypassPanel
WARNING:Forsafetyreasons,onlyqualiedpersonnelisallowedtoperformthe
operationproceduresdescribedinthischapter.
TurnintoExternalMaintenanceBypass
WARNING:Inbypassoperationthebatteriesarestillpowered.Ifatotalpower
offisrequired,theloadmustbeoff,andthebatteriesmustbepulledouttothered
disconnectline(see“PerformaTotalPowerOff“inthischapter).
1.FromtheOverviewScreen,pressENTER.
Use
Chrgxxx%
Loadxxx%
xxxVinxxxVoutxxHz
Runtime:xxhrxxmin
Press
2.GotoControlbyusingtheUP/DOWN
navigationkeysandpressENTER.
Use
ControlLogging
StatusDisplay
SetupDiags
LCMHelp
Press
3.GotoUPSintoBypassbyusingtheUP/DOWN
navigationkeysandpressENTER.
Use
UPSintoBypass
DoSelftest
SimulatePowerFail
StartRuntimeCal
Press
12
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
4.GotoY es,UPSintoBypassbyusingthe
UP/DOWNnavigationkeysandpressENTER.
Use
Confirm:
UPSintoBypass
NO,ABORT
YES,UPSintoBypass
Press
5.FromtheexternalMaintenanceBypassPanel
(MBP):Turnthebypassswitch(Q3)toposition
“|”(ON).
6.FromtheexternalMBP:Turntheoutputswitch
(Q2)toposition“O”(OFF).Nowtheloadisnot
supportedbytheUPS.
Note:Note!Ifyouneedtoturnthe
UPScompletelyOFF,proceedwith
steps7–11.
7.IfyouneedtoturntheUPScompletelyOFF:
FromtheexternalMBP:Turntheinputswitch
(Q1)toposition“O”(OFF).
8.FromtheXREnclosure(s)(ifavailable):Setthe
DCdisconnectswitch(es)topositionOFF.
9.FromtheUPS:Disconnectthebatteries(if
available)bypullingthemouttothered
disconnectlineshownoneachbatteryunit.
10.FromtheXREnclosure(s)(ifavailable):
Disconnectthebatteriesbypullingthemoutto
thereddisconnectlineshownoneachbattery
unit.
TurnintoNormalOperationfromExternalMaintenanceBypass
Caution:NeverattempttoswitchbacktheUPSintonormaloperationtillyouhaveveried
thattherearenointernalUPSfaults.
1.IftheUPShasbeencompletelyturnedOFF,proceedwithsteps2–10.IftheUPShasnotbeen
completelyturnedOFF,proceedwithsteps6–10.
2.FromtheXREnclosure(s)(ifavailable):Connectthebatteriesbypushingthemin.
3.FromtheUPS:Connectthebatteries(ifavailable)bypushingthemin.
4.FromtheXREnclosure(s)(ifavailable):SettheDCdisconnectswitch(es)topositionON.
5.FromtheXREnclosure(s)(ifavailable):SettheDCdisconnectswitch(es)topositionON.
6.FromtheexternalMBP:Turntheoutputswitch(Q2)toposition“|”(ON).Nowtheloadis
supportedbytheUPS.
7.FromtheUPS:Checkthattheyellow(BYPASS)LEDisilluminatedandthegreen(LOADON)
LEDisilluminated.
8.FromtheexternalMBP:Turnthebypassswitch(Q3)toposition“O”(OFF).
9.IftheUPShasnotreturnedtonormal:FromtheUPS:Turnoutofbypassfromthedisplayvia
Control>UPSoutofbypass>Y es,UPSoutofbypass.
10.FromtheUPS:CheckthattheUPSisinnormaloperation.Theyellow(BYPASS)LEDturnsoff
andthegreen(LOADON)LEDremainsilluminated.
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
13
PerformaTotalPowerOff
Note:InordertocarryoutthisproceduretheloadsupportedbytheUPSmustbeturnedoff.
1.CheckthattheloadwhichissupportedbytheUPSisturnedOFF.
2.FromtheUPS:TurnloadOFFfromthedisplayviaControl>TurnLoadOff>Y es,Turn
LoadOff.
3.FromtheexternalMBP:Turntheoutputswitch(Q2)toposition“O”(OFF).
4.FromtheexternalMBP:Turntheinputswitch(Q1)toposition“O”(OFF).
5.FromtheXREnclosure(s)(ifavailable):SettheDCdisconnectswitchtopositionOFF.
6.FromtheUPS:Disconnectthebatteries(ifavailable)bypullingthemouttothereddisconnect
lineshownoneachbatteryunit.
7.FromtheXREnclosure(s)(ifavailable):Disconnectthebatteriesbypullingthemouttothered
disconnectlineshownoneachbatteryunit.
PerformaRestart
Note:Onlyqualiedpersonnelfamiliarwiththeconstructionandtheequipmentmayrestart
theUPS.
1.FromtheXREnclosure(s)(ifavailable):Connectthebatteriesbypushingthemin.
2.FromtheUPS:Connectthebatteries(ifavailable)bypushingthemin.
3.FromtheXREnclosure(s)(ifavailable):SettheDCdisconnectswitch(es)topositionON.
4.FromtheexternalMBP:Turntheinputswitch(Q1)toposition“|”(ON).
5.FromtheexternalMBP:Turntheoutputswitch(Q2)toposition“|”(ON).
6.FromtheUPS:TurnloadONfromthedisplayviaControl>T urnLoadOn>Yes,Turn
LoadOn.
7.CheckthattheloadisON.
Note:TheUPSisnowreadytosupporttheload.
Note:Theauto-detectiononfrequencyhasbeenimprovedinrmwareversion5.1and
higherforsingleunits(withparallelcapability).Auto-detectiononfrequencyisanoptionin
theSetupmenu(inalignmentwiththevalues50Hzand60Hz)butalsoafeaturewherebya
singleUPSsystemdetectstheinputfrequencyinasystemstart-up.
IftheUPSsystemduringastart-updetectsaninputfrequencydifferentfromwhatisalready
set,thentheuserwillbeaskedtochoosethedetectedfrequency.Thesystemwillnotchange
frequencybyitself.Forsafetyreasons,theinputfrequencycanonlybechangedbytheuser.
Theauto-detectiononfrequency-featureisonlyapplicableinasinglesystemstart-up.Ifa
problemoccurscallAPCCustomerSupport(seethebackcoverofthismanual).
14
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
ParallelSystem
WARNING:Forsafetyreasons,onlyqualiedpersonnelisallowedtoperformthe
operationproceduresdescribedinthischapter.
WARNING:ParallelOperationisnotavailablewhenthesystemissetupfor3–wire
operation,whichonlyappliestoJapanesesystems.
TurnintoExternalMaintenanceBypass
WARNING:Inbypassoperationthebatteriesarestillcharged.Ifatotalpoweroffis
required,theloadmustbeoffandthebatteriesmustbepulledouttothereddisconnect
line(see“PerformaTotalPowerOff“inthischapter).
1.FromtheOverviewScreen,pressENTER.
Use
Chrgxxx%
Loadxxx%
xxxVinxxxVoutxxHz
Runtime:xxhrxxmin
Press
2.GotoControlbyusingtheUP/DOWN
navigationkeysandpressENTER.
Use
ControlLogging
StatusDisplay
SetupDiags
LCMHelp
Press
3.GotoUPSintoBypassbyusingtheUP/DOWN
navigationkeysandpressENTER.
Use
UPSintoBypass
DoSelftest
SimulatePowerFail
StartRuntimeCal
Press
4.GotoYES,UPSintoBypassbyusingthe
UP/DOWNnavigationkeysandpressENTER.
Use
Confirm:
UPSintoBypass
NO,ABORT
YES,UPSintoBypass
Press
5.FromtheUPS:CheckthatallUPSunitsare
inbypassoneachofthedisplays.Theyellow
bypassLEDisilluminatedoneachUPSunit.
6.FromtheexternalMaintenanceBypassPanel
(MBP):Checkthatthebypasslampindicator
(H3)isilluminatedatQ3.
990–2386D-001
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
15
7.FromtheexternalMBP:Turnthebypassswitch
(Q3)toposition“|”(ON).
8.FromtheexternalMBP:Checkthatthelamp
indicatoroftheoutputisolationbreaker(H4)at
Q4isilluminated.
9.FromtheexternalMBP:Turntheoutput
isolationbreaker(Q4)toposition“O”(OFF).
TheUPSisnowinexternalmaintenancebypass
withthebatteriesstillpowered.Note!Ifyou
needtoturntheUPSunitscompletelyOFF,
proceedwithsteps11–18.
Note:Note!Ifyouneedtoturnthe
UPSunitscompletelyOFF,proceed
withsteps11–18.
10.FromtheUPS:TurnOFFeachUPSunitfrom
thedisplayviaControl>TurnLoadOff>Y es,
TurnLoadOff.
11.FromtheexternalMBP:Checkthatallthe
outputlamps(H2a,H2b,H2c)forQ2are
illuminated.
12.FromtheexternalMBP:Turnalloutput
switches(Q2)toposition“O”(OFF).
13.FromtheexternalMBP:Turnallinputswitches
(Q5)(ifavailable)toposition“O”(OFF).
14.FromtheexternalMBP:Turnallinputswitches
(Q1)toposition“O”(OFF).
15.FromtheXREnclosure(s)(ifavailable):Set
theDCdisconnectswitch(es)topositionOFF.
16.FromtheUPS:Disconnectthebatteries(if
available)bypullingthemouttothered
disconnectlineshownoneachbatteryunit.
17.FromtheXREnclosure(s)(ifavailable):
Disconnectthebatteriesbypullingthemoutto
thereddisconnectlineshownoneachbattery
unit.
18.De-energizeallUPSinputs.
TurnintoNormalOperationfromExternalMaintenanceBypass
Caution:NeverattempttoturntheUPSintonormaloperationtillyouhaveveriedthat
therearenointernalUPSfaults.
1.IftheUPSunitshavebeencompletelyturnedOFF,proceedwithsteps2–16.IftheUPSunits
havenotbeencompletelyturnedOFF,proceedwithstep13–16.
2.FromtheUPS:Connectthebatteries(ifavailable)ineachUPSbypushingthemin.
3.FromtheXREnclosure(s)(ifavailable):ConnectthebatteriesineachUPSbypushingthemin.
4.FromtheXREnclosure(s)(ifavailable):SettheDCdisconnectswitch(es)topositionON.
5.FromtheexternalMBP:Turnallinputswitches(Q1)toposition“|”(ON).
6.FromtheexternalMBP:Checkthatallthebypassinputlamps(H5)atQ5(ifavailable)are
illuminated.
7.FromtheexternalMBP:Turnallbypassinputswitches(Q5)(ifavailable)toposition“|”(ON).
8.FromtheexternalMBP:Checkthatalltheoutputlamps(H2)forQ2areilluminated.
9.FromtheexternalMBP:Turnalloutputswitches(Q2)toposition“|”(ON).Thelampindicatorof
theoutputisolationbreaker(Q4)isstillilluminated.
10.FromtheUPS:TurnONallUPSunitsfromeachdisplayviaControl>TurnLoadON>Y es,
TurnLoadON.ThegreenonlineLEDsareilluminatedoneachUPSunit.
16
MGE™Galaxy™3500Series10-40kV A380/400/415V10-30kV A208/220V
990–2386D-001
/