  • Hello! I am an AI chatbot trained to assist you with the Danfoss AM-PBU 25 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Instructions
AM-PBU 25
7369082-0 SIBC 06 / 04 VI.AE.P1.02
1 (2)
Description
AM-PBU 25 is a standby power supply for AME 55 and AME 85 actuators. It will drive the actuators to open or closed
position during a power failure. The AM-PBU 25 can power one AMV(E) 85/86 or two AMV(E) 55/56 actuators.








             
         
L
24 Vac power
LN
BT
Battery Test
RC
Remote Control
TG
Test Ground
C1
Common, Output 1
NC1
Normally Closed, Output 1
NC2
Normally Open, Output 1
AC
24 Vac output
C2
Common, Output 2
NC2
Normally Closed, Output 2
NO2
Normally Open, Output 2
Installation
1. Connect the VMS25 to the actuator(s) as shown.
Connect
NC1
or
NC2
to terminal
3
on an actuator to drive the valve
stem down during power failure or to terminal
2
to drive the valve
stem up during a power failure.
2. Connect AM-PBU 25 to 24 volts ac power.
3. Connect the red wire to the battery positive (+) and the black
wire to the battery negative (-).
Note: Connect the 24 volt power to the AM-PBU 25 before connecting
the battery. Connecting the battery  rst causes the AM-PBU 25 to go
into the power failure mode.
AM-PBU 25
2(2)
Testing the AM-PBU 25 and the battery
The jumper between LN & RC can be replaced by a connection to a
Building Management System (BMS), a controller or a manual switch. When
the contact opens, the mains power is disconnected and the AM-PBU 25
goes through a cycle, running on battery power. This feature can be used
for remote control of the valve or for testing of the battery.
Connecting terminals TG (-) and BT (+) to a BAS or volt meter and taking
a reading just after an exercise cycle, gives a good indication of battery
condition. At the end of the cycle (6.5 minutes), the battery should not be
below 10 V.
When the connection between LN & RC is restored the AM-PBU 25 will
charge the battery with 13 - 14 volts dc wich can be veri ed on terminals
TG & BT.






             
         

