Testing the AM-PBU 25 and the battery
The jumper between LN & RC can be replaced by a connection to a
Building Management System (BMS), a controller or a manual switch. When
the contact opens, the mains power is disconnected and the AM-PBU 25
goes through a cycle, running on battery power. This feature can be used
for remote control of the valve or for testing of the battery.
Connecting terminals TG (-) and BT (+) to a BAS or volt meter and taking
a reading just after an exercise cycle, gives a good indication of battery
condition. At the end of the cycle (6.5 minutes), the battery should not be
When the connection between LN & RC is restored the AM-PBU 25 will
charge the battery with 13 - 14 volts dc wich can be veri ed on terminals
AM-PBU 25
AM-PBU 25
AM-PBU 25