1
Installation Guide
AM-PBU 25
District Energy VI.AE.P2.02 DEN-SMT/SI
Description
AM-PBU 25 is a standby power supply for AME 55 and AME
85 actuators. It will drive the actuators to open or closed
position during a power failure. The AM-PBU 25 can power one
AMV(E) 85/86 or two AMV(E) 55/56 actuators.
L 24 Vac power
LN System neutral
BT Battery Test
RC Remote Control
TG Test Ground
C1 Common, Output 1
NC1 Normally Closed, Output 1
NO1 Normally Open, Output 1
AC 24 Vac output
C2 Common, Output 2
NC2 Normally Closed, Output 2
NO2 Normally Open, Output 2
Installation
1. Connect the VMS25 to the actuator(s) as shown.
Connect NC1 or NC2 to terminal 3 on an actuator to drive the valve stem down during power failure or to terminal
2 to drive the valve stem up during a power failure.
2. Connect AM-PBU 25 to 24 volts ac power.
3. Connect the red wire to the battery positive (+) and the black wire to the battery negative (-).
Connect the 24 volt power to the AM-PBU 25
before connecting the battery. Connecting
the battery rst causes the AM-PBU 25 to go
into the power failure mode.