Schneider Electric MGE GALAXY 5000 Specification

Category
Uninterruptible power supplies (UPSs)
Type
Specification

This manual is also suitable for

MGEGalaxy5000
40–130kVA480V
Installation
TableofContents
IMPORTANTSAFETYINSTRUCTIONS-SAVETHESE
INSTRUCTIONS...............................................................................................................1
SymbolsUsed...................................................................................................................1
Specications...................................................................................................................2
ACInput...........................................................................................................................2
ACOutput.........................................................................................................................2
Batteries............................................................................................................................2
ACBypass........................................................................................................................2
RecommendedFuses........................................................................................................3
ConnectInputandGroundCablesinSingleSystems..............................4
SingleUtility/MainsSystems....................................................................................4
DualUtility/MainsSystems........................................................................................4
ConnectACInputandPowerCablesinParallelSystems......................5
SingleUtility/Mains......................................................................................................5
DualUtility/MainsSystems........................................................................................6
ConnectCommunicationCables...........................................................................7
OverviewofCommunicationCablesinSingleSystems..................................................7
OverviewofCommunicationCablesinParallelSystems................................................8
ConnectRelayCommunicationCard.....................................................................9
CommunicationCardConnectionExample...............................................................10
ConnectGeneralShutdownorRemoteEmergencyPowerOff......................10
ConnectParallelCommunicationCablesinRedundantParallel
Systems..........................................................................................................................11
ConnectParallelCommunicationCablesinCapacityParallel
Systems..........................................................................................................................12
InstallanExternalBatteryCabinet.......................................................................15
InstallATIZPCAandGNDBusbar...........................................................................15
TheBatteryCircuitBreaker.......................................................................................16
ConnectPowerandControlCables........................................................................17
MounttheBatteryCells..............................................................................................19
InstallPanelsandLabelson26”BatteryCabinet(StandAloneOnly)...........20
InstallPanels,LabelsandPalleton26”BatteryCabinet..................................21
990–5217
MGEGalaxy500040–130kV A480V
i
InstallPanelsandLabelson48”BatteryCabinet(StandAloneOnly)...........21
InstallPanelsandLabelson48”BatteryCabinet...............................................22
ii
MGEGalaxy500040–130kV A480V
990–5217
IMPORTANTSAFETYINSTRUCTIONS-
SAVETHESEINSTRUCTIONS
SymbolsUsed
WARNING:Indicatesanelectricalhazard,which,ifnotavoided,couldresultininjury
ordeath.
Caution:Indicatesahazard,which,ifnotavoided,couldresultininjuryordeath.
Note:Indicatesimportantinformation.
See:Indicatesthatmoreinformationisavailableonthesubject.
990–5217
MGEGalaxy500040–130kV A480V
1
Specications
ACInput
ACinput40kV A50kV A60kV A80kV A100kV A130kV A
Nominalinputvoltage(V)
480480480480480480
Inputfrequency(Hz)
60Hz60Hz60Hz60Hz60Hz60Hz
Nominalinputcurrent(A)
1
48597194117151
Maxinputcurrent(A)
2
597088111150182
Inputcurrentlimit(A)
3
57
7085111148182
InputphaserotationA,B,Cclockwise
Inputpowerfactor
>0.98
1
Inputcurrentbasedonratedloadandbatteriesfullycharged.
2
Inputcurrentbasedonfullybatteryrecharge,nominalvoltageandratedload.
3
Currentlimitationthroughelectroniccurrentlimitingisbasedonfullbatteryrechargeand-10%
inputvoltage.
ACOutput
40kV A50kV A60kV A80kV A100kV A130kV A
Nominalinputvoltage(V)
480480480480480480
Nominaloutputcurrent(A)
48597194117151
Batteries
Batteryinput40kV A50kV A60kV A80kV A100kV A130kV A
Nominalvoltage(VDC)
432
Endvoltage(VDC)
356
Max.oatingvoltage
(VDC)
490
I
Nom
discharge
1
(A)
90113135180225293
I
Max
discharge
2
(A)
109137164219273355
1
Nominalbatterydischargecurrentbasedonratedloadandnominalbatteryvoltage.
2
Maximumbatterydischargecurrentbasedonratedloadattheendofthedischarge.
ACBypass
40kV A50kV A60kV A80kV A100kV A130kV A
Inputfrequency(Hz)
606060606060
Nominalinputcurrent(A)
48597194117151
2
MGEGalaxy500040–130kV A480V
990–5217
RecommendedFuses
40kV A50kV A60kV A80kV A100kV A130kV A
Inputandoutputfuserating
(A)
160160160160315315
990–5217
MGEGalaxy500040–130kV A480V
3
ConnectInputandGroundCablesin
SingleSystems
SingleUtility/MainsSystems
1.Removetheprotectioncoverinthebottomof
theenclosure.
2.ConnecttheACinputcablestotheACinput
terminalsandtotheUPSgroundingplate.
3.ConnecttheACoutputcablestotheACoutput
terminalsandtotheUPSgroundingplate.
4.Connectthebatterycablestothebattery
terminals.
5.Securethecablestothecabinet.
6.Reinstallthecoverprotectionforpower
terminals.
DualUtility/MainsSystems
1.Removetheprotectioncoverinthebottomof
theenclosure.
2.ConnecttheACinputcablestotheACinput
terminalsandtotheUPSgroundingplate.
3.ConnecttheACbypasscablestotheACbypass
terminalsandtotheUPSgroundingplate.
4.ConnecttheACoutputcablestotheACoutput
terminalsandtotheUPSgroundingplate.
5.Connectthebatterycablestothebattery
terminals.
6.Securethecablestothecabinet.
7.Reinstallthecoverprotectionforpower
terminals.
4
MGEGalaxy500040–130kV A480V
990–5217
ConnectACInputandPowerCablesin
ParallelSystems
SingleUtility/Mains
Note:AmaximumoftwoUPSunitscanbeinstalledforPn.
1.Removetheprotectioncoverinthebottomoftheenclosure.
2.ConnecttheACinputcablestotheACinputterminalsandtotheUPSgroundingplateforboth
UPSunitsinbothUPSunits.
3.ConnecttheACoutputcablestotheACoutputterminalsandtotheUPSgroundingplateinUPS1.
4.ConnectthethreeloadconnectorsfromACoutputterminalsinUPS1toACoutputterminals
inUPS2.
5.Connectthebatterycablestothebatteryterminals.
6.Securethecablestothecabinet.
7.Reinstallthecoverprotectionforpowerterminals.
990–5217
MGEGalaxy500040–130kV A480V
5
DualUtility/MainsSystems
Caution:IfthetwoUPSunitsareplacedsidebyside,connectasindicatedbelow.Inother
congurations,alwaysmakesurethatthecablesbetweentheUPSunitsandthebypass
sourcehavethesamecross-sectionandthesamelength.Thesameistrueforthecables
betweentheUPSunitsandtheload.
Note:ThedrawingsbelowshowcongurationswithoutanexternalSystemBypassCabinet.
1.Removetheprotectioncoverinthebottomoftheenclosure.
2.ConnecttheACinputcablestotheACinputterminalsandtotheUPSgroundingplateinboth
UPSunits.
3.ConnecttheACbypasscablestotheACbypassterminalsandtotheUPSgroundingplatein
bothUPSunits.
4.ConnecttheACoutputcablestotheACoutputterminalsandtotheUPSgroundingplateinUPS1.
5.ConnectthethreeloadconnectorsfromACoutputterminalsinUPS1toACoutputterminals
inUPS2.
6.Connectthebatterycablestothebatteryterminals.
7.Securethecablestothecabinet.
8.Reinstallthecoverprotectionforpowerterminals.
6
MGEGalaxy500040–130kV A480V
990–5217
ConnectCommunicationCables
OverviewofCommunicationCablesinSingleSystems
Caution:Toensuresufcientisolationofcontrolandcommunicationcables,theymust
berunseparatelyfromthepowercables.Reinforcetheinsulationofthesecontroland
communicationcablesifanyriskofcontactwiththepowercablesexists.
A.Relaycommunicationcard(SELV)
B.Optionalcommunicationcards(SELVor
LV)
C.Externalbatterycircuitbreakercables
(SELV)
D.Generalshutdowncable(SELV)
990–5217
MGEGalaxy500040–130kV A480V
7
OverviewofCommunicationCablesinParallel
Systems
Caution:Toensuresufcientisolationofcontrolandcommunicationcables,theymust
berunseparatelyfromthepowercables.Reinforcetheinsulationofthesecontroland
communicationcablesifanyriskofcontactwiththepowercablesexists.
A.Relaycommunicationcard(SELV)
B.Optionalcommunicationcards(SELVor
LV)
C.Externalbatterycircuitbreakercables
(SELV)
D.Generalshutdowncable(SELV)
E.PCAINTNforconnectionofexternalbypass
cabinetcable(ELV),CANcables(SELV),
andexchange-currentcables(SELV).
8
MGEGalaxy500040–130kV A480V
990–5217
ConnectRelayCommunicationCard
Caution:Isolateandlock-outallpowersourcesforthiscardbeforemakingconnections.
NeverconnectSELV(safetyextralowvoltage)andnon-SELVcircuitstothedifferent
outputsofthesamecard.
Characteristicsofoutputcontacts:
Permissiblevoltage:250VAC,30VDC
Permissiblecurrent:2A
Cable:4x0.93mm²,Ø6.6+/-0.3mm
Characteristicsofinputcontacts:
Switchedvoltage:5VDC
Consumption:10mA
Cable:4x0.34mm²,Ø5+/-0.5mm
1.Removethecoversecuredbythescrews.
2.Runthecommunicationcablesthroughthe
cableentryholes.
3.Connectconductorstotheinputterminals.
A.UPSON
B.UPSOFF
990–5217
MGEGalaxy500040–130kV A480V
9
4.Connectconductorstotheoutputterminals.
A.Generalalarm
B.Batteryfault
C.LoadonUPS
D.Loadonautomaticbypass
E.Loadonbatterypower
F.Lowbatterywarning
5.Putthecoverbackinplaceandsecureitwith
thescrews.
6.Tightenthescrewstolockthecables.
7.Indicatethelocationsofthepowersourceson
thelabels.
8.Insertthecardsinitsslot.
9.Securethecardwithtwoscrews.
CommunicationCardConnectionExample
IfaSELVsourceisused,itmustalwaysbepossibletoisolatethecommunicationcardfromtheupstream
sourcetoensurethesafetyofpersonnelworkingontheinstallation.
ConnectGeneralShutdownorRemoteEmergency
PowerOff
PressingthegeneralshutdownbuttoncausesUPSshutdownandopeningofthebatterycircuitbreaker
(withopeningofthebypassstaticswitchdependingonpersonalizationsettings).TheRemoteEmergency
PowerOff(REPO)notionisapplicabletoinstallationswherepressingthebuttonalsocausestheupstream
NormalACsourceandACbypasssourcecircuitbreakerstoopen.Inparallelsystems,theremustbea
singlegeneralshutdownbuttonwithaseparatecontactforeachUPSunit.
10
MGEGalaxy500040–130kV A480V
990–5217
1.Removethewirejumperfromtheterminal
block.
2.ConnectthegeneralshutdownNCcontactto
terminals1and2(SELV).
3.Securethecable.
ConnectParallelCommunicationCablesinRedundant
ParallelSystems
Note:Thesuppliedcables(33ft)limitthedistancebetweentwoUPSunitstoapproximately
20ft.
1.ConnectacommunicationcablefromXMS02inUPS1toXMS02inUPS2.
2.ConnectacommunicationcablefromXMS03inUPS1toXMS03inUPS2.
3.InstallabluepluginconnectorXMS06inUPS1.
4.ConnectacommunicationcablefromXMS07inUPS1toXMS06inUPS2.
5.InstallaredpluginconnectorXMS07inUPS2.
6.Fittheprotectioncoversuppliedwiththeparallelsystemovertheauxiliaryinterconnectioncables.
990–5217
MGEGalaxy500040–130kV A480V
11
ConnectParallelCommunicationCablesinCapacity
ParallelSystems
Note:Thesuppliedcables(33ft)limitthedistancebetweenthetwoUPSunitsto
approximately20ft.
1.UsetheXMS02andXMS03terminalstocreatealoopbetweenallUPSunitsasshownonthe
illustration(alltheXMS02andXMS03terminalsmustbeused).
12
MGEGalaxy500040–130kV A480V
990–5217
2.Daisy-chaintheUPSunitsusingtheXMS06andXMS07terminals.Fitablueconnectoron
therstUPSunitsandaredplugonthelastUPSunit(alltheXMS06andXMS07connectors
mustbeused).
3.Connectterminals7,8,9,and10ontheauxiliaryterminalblockTB2inthesystembypass
cabinettoUPSterminalblocksXMS04/XMS05pins1,2,3,and4respectivelyandcreatealoop
connectionbetweenthesystembypasscabinetandtheUPSasshown.
4.Fittheprotectioncoversuppliedwiththeparallelsystemovertheauxiliaryinterconnectioncables.
990–5217
MGEGalaxy500040–130kV A480V
13
14
MGEGalaxy500040–130kV A480V
990–5217
InstallanExternalBatteryCabinet
InstallATIZPCAandGNDBusbar
26”and32”BatteryCabinet48”BatteryCabinet
1.IftheA TIZPCAoptionhasbeenpurchased,installtheA TIZPCAintherstbatterycabinet.
2.InstalltheGround(GND)busbar.
990–5217
MGEGalaxy500040–130kV A480V
15
TheBatteryCircuitBreaker
Note:Onlyonecircuitbreakerisnecessaryevenifseveralbatterycabinetsareconnected.
1.Thebatterycircuitbreakerispre-installedinthebatterycabinetfromfactory.
2.Securethebaseplatetothebatterycabinettosupportthecircuitbreaker.
3.SecuretheXR1connectorboxtothebatterycabinetframe.
4.Securethetemperaturesensortothebatterycabinetframe.
5.Whenthebatterieshavebeenconnectedtothecircuitbreaker,installthefrontplateinfront
ofthecircuitbreaker.
BatteryCircuitBreakerControlWiring
TB5
QF1WireColor
1
Brown
2
Brown
3
Yellow
4
Blue/Yellow
5
Jumper2to4
16
MGEGalaxy500040–130kV A480V
990–5217
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Schneider Electric MGE GALAXY 5000 Specification

Category
Uninterruptible power supplies (UPSs)
Type
Specification
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI