MGE GALAXY 5000

APC MGE GALAXY 5000, MGE GALAXY 5000 40 130KVA User manual

  • Hello! I am an AI chatbot trained to assist you with the APC MGE GALAXY 5000 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
MGEGalaxy5000
40-130kVA480V
Operation
TableofContents
AboutThisManual.........................................................................................................1
SymbolsUsed...................................................................................................................1
CompanionManuals.........................................................................................................1
FindUpdatestothisManual.............................................................................................1
Overview..............................................................................................................................2
UserInterface....................................................................................................................2
DisplayScreens.................................................................................................................2
BasicOperationofDisplay........................................................................................2
Measurements...........................................................................................................3
Alarms.......................................................................................................................3
Status........................................................................................................................4
Settings.....................................................................................................................4
Controls.....................................................................................................................4
UPSConguration.........................................................................................................6
AccesstothePersonalizationFunctions..............................................................6
PersonalizationSettings....................................................................................................6
Operation............................................................................................................................8
OperatingModes...............................................................................................................8
Normal(DoubleConversion)Mode............................................................................8
ECOMode(SingleUPSOnly)....................................................................................8
LoadonBatteryPower..............................................................................................9
OperationofMimic-PanelLEDs......................................................................................10
OperationProcedures........................................................................................................11
ShutDownaSingleUPS............................................................................................11
RestartaSingleUPS..................................................................................................12
ShutDownaParallelConguration...........................................................................13
RestartaParallelConguration.................................................................................14
IsolateUPS................................................................................................................15
ReturntoNormalOperation.......................................................................................18
RestarttheUPSUnitforwhichSwitchQ3BP(10)isONandtheOtherSwitchesare
OFF...................................................................................................................................19
RestarttheUPSforwhichAllSwitchesareSettoOFF...................................................20
OperationoftheRelayCommunicationCard(DryContacts)...............22
StandardMode..................................................................................................................22
ProgrammableMode.........................................................................................................23
ListofOperatingStatusConditionsThatCanbeAssignedtoanSECIOutput..............23
Maintenance......................................................................................................................26
LifeCycleMonitoring(LCM)..........................................................................................26
ServicingBatteries............................................................................................................27
IMPORTANTSAFETYINSTRUCTIONSFORSERVICINGBATTERIES........................27
Troubleshooting..............................................................................................................28
IdenticationofAlarms....................................................................................................28
AlarmorStatusDisplayMessagesList............................................................................29
990-5219-001
MGEGalaxy500040-130kVA480V
i
ii
MGEGalaxy500040-130kVA480V
990-5219-001
AboutThisManual
Thismanualdescribesthestartup,shutdown,andnormaloperationoftheMGEGalaxy5000with
informationontheuserinterfacedisplayanddisplaymenustructure.Formaintenancethemanual
describesalarmconditions,UPSisolationoperationandmaintenanceandsafetyinformationonservicing
batteriesfortheMGEGalaxy5000.
SymbolsUsed
WARNING:Indicatesanelectricalhazard,which,ifnotavoided,couldresultininjury
ordeath.
Caution:Indicatesahazard,which,ifnotavoided,couldresultininjuryordeath.
Note:Indicatesimportantinformation.
See:Indicatesthatmoreinformationisavailableonthesubject.
CompanionManuals
ForadditionalinformationabouttheMGEGalaxy5000,seethefollowingdocuments:
MGEGalaxy5000Installation990–5217–001
MGEGalaxy5000Receiving&Unpacking990–5218–001
FindUpdatestothisManual
Youcancheckforupdatestothismanualonwww.apc.com.Lookforthelatestletterrevision(A,
Betc.)ofthemanual.
990-5219-001
MGEGalaxy500040-130kV A480V
1
Overview
UserInterface
TheUPSisoperatedusingthecontrolanddisplayinterface.
A.GraphicalDisplay
B.LoadprotectedLED
C.MinorfaultLED
D.MajorfaultLED
E.Helpkey
F.Functionkeys.Each
keycorrespondsto
afunctionpresented
onthedisplay.The
functionofeachkey
changesdependingon
themenudisplayedon
thescreen.
G.Menukey.Thisbutton
providesdirectaccess
tothemainmenu.
H.ONbutton.
I.OFFbutton.
J.PFCONLED
K.UPSONLED
L.Operationonbattery
powerLED
M.LoadsuppliedLED
N.Bypassinoperation
LED
DisplayScreens
BasicOperationofDisplay
2
MGEGalaxy500040-130kV A480V
990-5219-001
A
PresstheMenukeytoaccesstheMainMenu.
B
PresstheHelpkeyforinformationonthepictogramfunctions.Thekeymustbehelddown.
Measurements
TheMeasurementsdisplayscreensconsistofthefollowingmeasurementsscreens:
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightMeasurementsonthedisplay.
3.PressthefunctionkeytoselectMeasurements.
4.Usethefunctionkeysortoselectbetweenthefollowingmeasurements:
BatteryMeasurements
V oltageMeasurements
CurrentMeasurements
PowerMeasurements
FrequencyMeasurements
RatiosMeasurements
ParallelMeasurements(option)
5.Pressthefunctionkeytoselecttherequiredmeasurementsscreen.
Alarms
Detailedinformationonallalarmsissuppliedonthedisplay.Seethe“Troubleshooting“sectionfor
alistofpossiblealarmmessagesinthedisplay.
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightAlarmsonthedisplay.
3.PressthefunctionkeytoselectAlarms.
4.Usethefunctionkeysortoselectbetweenthealarmmessages.
5.Pressthefunctionkeytoselecttherequiredalarmscreen.
990-5219-001
MGEGalaxy500040-130kV A480V
3
Status
TheStatusdisplayscreensconsistofthefollowingStatusscreens:
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightStatusonthedisplay.
3.PressthefunctionkeytoselectStatus.
4.UsethefunctionkeysortoselectbetweenthefollowingtwoStatusscreens:
Timestampedevents
Statistics
5.PressthefunctionkeytoselecttherequiredStatusscreen.
Settings
TheSettingsdisplayscreensconsistofthefollowingSettingsscreens:
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightSettingsonthedisplay.
3.PressthefunctionkeytoselectSettings.
4.UsethefunctionkeysortoselectbetweentheSettingsscreens:
Language
Date/time
Displaycontrast
Buzzervolume
Personalization
Outputvoltage
Password
Dry-contactsettings
5.PressthefunctionkeytoselecttherequiredSettingsscreen.
Controls
TheControlsdisplayscreensconsistofthefollowingControlsscreens:
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightControlsonthedisplay.
3.PressthefunctionkeytoselectControls.
4.UsethefunctionkeysortoselectbetweentheControlsscreens:
ResetAlarms
Inverteron
Inverteroff
Forceloadtransfertoinverter
Forceloadtransfertobypass
Desynchronizeinverterfrombypass
Resynchronizeinverterandbypass
4
MGEGalaxy500040-130kV A480V
990-5219-001
TestsLEDs
BuzzerOFF
EnableLCMindications
DisableLCMindications
5.PressthefunctionkeytoselecttherequiredControlsscreen.
990-5219-001
MGEGalaxy500040-130kV A480V
5
UPSConguration
AccesstothePersonalizationFunctions
Caution:PersonalizationmustbecarriedoutwithswitchesQ1(8)andQ5N(11)open
(OFF)andswitchQ4S(9)closed(ON).
1.Pressthemenukey(A).
2.SelectSettings,thenPersonalizationusingthe
functionkeys(B)or↓.
3.Conrmbypressingthefunctionkey(B)←).
4.Enterthepasswordbysuccessivelyselecting
eachiconusingthecorrespondingfunctionkey.
5.Conrmbypressingthefunctionkey(B)←.
6.Tosavethepersonalizationsettings,conrmby
pressingthefunctionkey(B)←.
Thepasswordisfactorysetto:
Forinformationonhowtochangethepassword,
see“Settings“.
PersonalizationSettings
OperatingMode
FunctionFactorysettingOptions
UPSoperatingmode
NORMAL
UPSautomaticstartDisabledEnabled
Authorizednumberofstarts
41to255
Delaybeforeresetofnumberof
executedautomaticstarts
4seconds1to60seconds
Frequency
FunctionFactorysettingOptions
UPSoutputfrequency
60Hz60Hz
ToleranceforbypassACsource
8%0.5124%
Synchronizationspeedwithbypass
ACsource
2Hz/s1Hz/s
6
MGEGalaxy500040-130kV A480V
990-5219-001
AutomaticBypass
FunctionFactorysettingOptions
TransfertobypassACsourceEnabledDisableddisabledwhenlimiting
TransfertobypasswithbypassAC
sourceoutoftolerances
EnabledDisabled
Battery
FunctionFactorysettingOptions
Lowbatterywarningthresholdif
batterymonitorinactive
40%remainingbackuptime206080%remainingbackup
time
Lowbatterywarningthresholdif
batterymonitoractive
4minutesofbatterybackuptime1toXminutesofbatterybackup
time
Intervalbetweentwobatterytests30days1to180days
990-5219-001
MGEGalaxy500040-130kV A480V
7
Operation
Caution:Alloperationsconcerningsystemstart-upandcompliancewithstandardsand
regulations,includingthoserelatedtothebatterycabinet,mustbecarriedoutbytrainedand
certiedpersonnelbeforeusingtheUPS.
OperatingModes
Normal(DoubleConversion)Mode
Thisisthestandardoperatingmode,setbydefaultinthefactory.Twopossiblecases:
1.NormalACsourceavailable:LED(A)isON.
TheloadisprotectedbytheUPS.
2.NormalACsourcenotavailable:LED(B)isON.
Thebuzzersoundsintermittently.Operationonbattery
powerLEDonthemimic-panelisgreen.
TheloadissuppliedbytheUPSfrombatterypower .
Note:ThedisplayindicatesanyanomaliesrelatedtotheACsourceortheUPSaswell
asremedialactionifapplicable.Pressthefunctionkeyindicatedbythedisplaytoturn
thebuzzerOFF.
ECOMode(SingleUPSOnly)
Themainadvantageofthismodeisthatitreducestheconsumptionofelectricalpower.ECOmodemaybe
selectedexclusivelyviathecontrolpanelontheUPS.Threepossiblescenarios:
1.BypassACsourceavailable:LED(A)isON.
TheloadissuppliedinECOmode.
2.BypassACsourcenotavailable:LED(A)isON.The
buzzersoundsintermittently.Theloadisautomatically
suppliedinnormalmodeviatheNormalACinput.
8
MGEGalaxy500040-130kV A480V
990-5219-001
3.BothnormalandBypassACsourcesnotavailableor
outoftolerance:LED(B)isON.Thebuzzersounds
intermittently.TheloadissuppliedbytheUPSfrom
batterypower.
Note:ThedisplayindicatestheUPSoperatingstatusconditionsandtherequiredactions.
LoadonBatteryPower
TheloadcontinuestobeprotectedbytheUPSwhenthenormalACsourceisnotavailable.Poweris
suppliedbythebattery.
TransfertoBatteryPower
LED(B)isON.
Thebuzzersoundsintermittently.
Theloadissuppliedbythebattery.
EndofBatteryPower
LED(C)isON.
Thebuzzersoundsintermittently.
TheloadistransferredonthebypassACinputif
itispresent.
990-5219-001
MGEGalaxy500040-130kV A480V
9
OperationofMimic-PanelLEDs
TheMGEGalaxy5000systemissimpletooperateandyetprovidesawealthofcontinuousmonitoring
anddiagnosticfeaturestoensureproperoperation.OperatorsgainaccesstoinformationintheMGE
Galaxy5000systemthroughthedisplayanditsintegratedLEDmimicpanel.
Themimicdiagramdisplaysinformationdirectlyonthefrontpanel.Segmentsaregreenwhenthefunction
isactive.SegmentsareOFFwhenthefunctionisnotactive.Segmentsareredwhenafaulthasoccurred
inthefunction.
A.PFCONLED
B.UPSONLED
C.OperationonbatterypowerLED
D.LoadsuppliedLED
E.BypassinoperationLED
F.ONbutton
StartUpSingleUPSonNormalACInput
StepsActionLED(A)LED(B)LED(C)LED(D)LED(E)
1Q1open
OffOffOffOffOff
2
CloseQ1
green
OffredOffred
3
CloseBatteryCB
green
OffOffOffred
4
CloseQ4S
green
OffOffOff
green
5
CloseQ5N
green
OffOff
greengreen
6OpenQ3BP
green
OffOff
greengreen
7
PressONbutton
(F)
greengreen
Off
green
Off
StartUpSingleUPSonBypassACInput
StepsActionLED(A)LED(B)LED(C)LED(D)LED(E)
1Q4Sopen
OffOffOffOffOff
2
CloseQ4SOffOffredOff
green
3
CloseQ5NOffOffred
greengreen
4OpenQ3BP
OffOffred
greengreen
5
CloseQ1
green
Offred
greengreen
6
CloseBatteryCB
green
OffOff
greengreen
7
PressONbutton
(F)
greengreen
Off
green
Off
10
MGEGalaxy500040-130kV A480V
990-5219-001
OperationProcedures
ShutDownaSingleUPS
TheUPSremainsenergizedunlessitisshutdown.
1.Pressabuttontoexitsleepmode.
2.PresstheOFFbutton(A)for3seconds.
TheloadisnolongerprotectedbytheUPS.
Itissuppliedviathebypass.
3.Setthebatterycircuitbreakeroftheauxiliary
cabinetstoOFF.
4.SettheinputswitchQ1(B)toOFF.
Thechargernolongeroperatestokeepthe
batteriesfullycharged.
5.Opentheupstreamcircuitbreakersofthe
NormalACsourceandBypassACsourceto
completelypowerofftheUPS.
990-5219-001
MGEGalaxy500040-130kV A480V
11
RestartaSingleUPS
CheckthatswitchesQ4S(B)andQ5N(C)areclosed.Ifthisisthecase,continuewiththisprocedure,
otherwisereferto“ReturntotheNormalOperation,SingleUPS“.
1.SettheNormalACsourceinputswitchQ1(A)
totheONposition.
2.Waituntiltheendofthestartsequence.
3.Setthebatterycircuitbreakeroftheauxiliary
cabinetstotheONposition.
TheUPSstartsautomatically.
LED(D)isON.Theloadisprotectedbythe
UPS.
IftheLED(D)remainsOFF,presstheON
button(G)(theUPSisinmanualstartmode)and
conrmifnecessarybypressingthefunction
key(H)marked←.
IftheLED(C)stillremainsOFFandeitherof
theLEDs(E)or(F)isON,afaulthasoccurred
(see“IdenticationofAlarms“.
12
MGEGalaxy500040-130kV A480V
990-5219-001
ShutDownaParallelConguration
1.Pressabuttononeachunittoexitsleepmode.
2.PresstheOFFbutton(A)oneachunitfor3
seconds.
TheloadisnolongerprotectedbytheUPSs.
Itissuppliedviathebypass.
3.Setthebatterycircuitbreakersoftheauxiliary
cabinetstotheOFFposition.
4.SettheinputswitchQ1(B)ineachUPStothe
OFFposition.
Thechargernolongeroperatestokeepthe
batteriesfullycharged.
5.OpentheupstreamcircuitbreakersofNormal
ACsourceandBypassACsourcetocompletely
powerofftheinstallation.
990-5219-001
MGEGalaxy500040-130kV A480V
13
RestartaParallelConguration
CheckthatswitchesQ4S(B)andQ5N(C)areclosed.Ifthisisthecase,continuewiththisprocedure,
otherwisereferto“ReturntoNormalOperation,ParallelUPS“.
1.CheckthattheoutputswitchCB2intheexternal
systembypasscabinetisclosed.
2.CheckthatthebypassswitchCB1intheexternal
systembypasscabinetisopen.
Thencarryoutsteps3to5belowoneachofthe
UPSs.
3.SettheNormalACsourceinputswitchQ1(A)
totheONposition.
4.Waituntiltheendofthestartsequence.
5.Setthebatterycircuitbreakeroftheauxiliary
cabinetstotheONposition.
TheUPSsstartautomatically.Oneachunit,
LEDs(E)and(F)goOFFandLED(D)goes
ON.
TheloadisprotectedbytheUPSs.
IftheLED(D)remainsOFF,presstheON
button(G)oneachUPS(theUPSisinmanual
startmode)andconrmifnecessarybypressing
thefunctionkey(H)marked←.
IftheLED(D)stillremainsOFFandeitherof
theLEDs(E)or(F)isON,afaulthasoccurred
(see“IdenticationofAlarms“).
14
MGEGalaxy500040-130kV A480V
990-5219-001
IsolateUPS
IsolateSingleUPS
ToisolatetheUPSfromtheelectricalpowersourceandsupplytheloaddirectlybythenormalorbypass
ACsource,followtheinstructionsbelow:
1.Pressabuttontoexitsleepmode.
2.ShutdowntheUPSbypressingtheOFFbutton
(A)for3seconds.
TheloadisnolongerprotectedbytheUPS.
3.SetbypassswitchQ3BP(D)toON.
4.SetoutputswitchQ5N(E)toOFF.
5.Setthebatterycircuitbreakeroftheauxiliary
cabinetstoOFF.
6.SettheinputswitchQ1(B)toOFF.
7.SettheswitchQ4S(C)toOFF.
8.WaituntilthedisplayandLEDsgooff.
TheloadisnolongerprotectedbytheUPS,but
continuestobesuppliedwithACpower.UPS
maintenanceorservicingcannowbecarried
out.
WARNING:Powerispresenton
thepowerconnectionterminals.
990-5219-001
MGEGalaxy500040-130kV A480V
15
IsolateParallelUPSWithoutExternalBypassCabinet
ShutdownandisolatetherstUPS:
1.CheckthatthetwoUPSsareoperating.
2.Pressabuttontoexitsleepmode.
3.ShutdowntheUPSbypressingtheOFFbutton
(A)for3seconds.
4.SetoutputswitchQ5N(E)toOFF.
5.Setthebatterycircuitbreakersoftheauxiliary
cabinetstoOFF.
6.SettheinputswitchQ1(B)toOFF.
7.SettheswitchQ4S(C)toOFF.
8.WaituntilthedisplayandLEDsgooff.
TheloadisstillprotectedbytheotherUPS.
Maintenanceorservicingcannowbecarried
outontheUPSthathasbeenshutdown.
WARNING:Powerispresenton
thepowerconnectionterminals.
ShutdownandisolatethesecondUPS:
9.Pressabuttontoexitsleepmode.
10.ShutdowntheUPSbypressingtheOFFbutton
(A)for3seconds.
11.SetbypassswitchQ3BP(D)toON.
12.SetoutputswitchQ5N(E)toOFF.
13.Setthebatterycircuitbreakeroftheauxiliary
cabinetstoOFF.
14.SettheinputswitchQ1(B)toOFF.
15.SettheswitchQ4S(C)toOFF.
16.WaituntilthedisplayandLEDsgooff.
TheloadisnolongerprotectedbytheUPS,but
continuestobesuppliedwithACpower.UPS
maintenanceorservicingcannowbecarried
out.
WARNING:Powerispresenton
thepowerconnectionterminals.
16
MGEGalaxy500040-130kV A480V
990-5219-001
/