APC MGE GALAXY 5000 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

This manual is also suitable for

APC MGE GALAXY 5000 is a reliable power protection solution for small to medium data centers, server rooms, and critical equipment. Its advanced features include efficient double-conversion online operation, flexible ECO mode for energy savings, paralleling capability for increased capacity and redundancy, and advanced diagnostics for proactive maintenance.

APC MGE GALAXY 5000 is a reliable power protection solution for small to medium data centers, server rooms, and critical equipment. Its advanced features include efficient double-conversion online operation, flexible ECO mode for energy savings, paralleling capability for increased capacity and redundancy, and advanced diagnostics for proactive maintenance.

MGEGalaxy5000
40-130kVA480V
Operation
TableofContents
AboutThisManual.........................................................................................................1
SymbolsUsed...................................................................................................................1
CompanionManuals.........................................................................................................1
FindUpdatestothisManual.............................................................................................1
Overview..............................................................................................................................2
UserInterface....................................................................................................................2
DisplayScreens.................................................................................................................2
BasicOperationofDisplay........................................................................................2
Measurements...........................................................................................................3
Alarms.......................................................................................................................3
Status........................................................................................................................4
Settings.....................................................................................................................4
Controls.....................................................................................................................4
UPSConguration.........................................................................................................6
AccesstothePersonalizationFunctions..............................................................6
PersonalizationSettings....................................................................................................6
Operation............................................................................................................................8
OperatingModes...............................................................................................................8
Normal(DoubleConversion)Mode............................................................................8
ECOMode(SingleUPSOnly)....................................................................................8
LoadonBatteryPower..............................................................................................9
OperationofMimic-PanelLEDs......................................................................................10
OperationProcedures........................................................................................................11
ShutDownaSingleUPS............................................................................................11
RestartaSingleUPS..................................................................................................12
ShutDownaParallelConguration...........................................................................13
RestartaParallelConguration.................................................................................14
IsolateUPS................................................................................................................15
ReturntoNormalOperation.......................................................................................18
RestarttheUPSUnitforwhichSwitchQ3BP(10)isONandtheOtherSwitchesare
OFF...................................................................................................................................19
RestarttheUPSforwhichAllSwitchesareSettoOFF...................................................20
OperationoftheRelayCommunicationCard(DryContacts)...............22
StandardMode..................................................................................................................22
ProgrammableMode.........................................................................................................23
ListofOperatingStatusConditionsThatCanbeAssignedtoanSECIOutput..............23
Maintenance......................................................................................................................26
LifeCycleMonitoring(LCM)..........................................................................................26
ServicingBatteries............................................................................................................27
IMPORTANTSAFETYINSTRUCTIONSFORSERVICINGBATTERIES........................27
Troubleshooting..............................................................................................................28
IdenticationofAlarms....................................................................................................28
AlarmorStatusDisplayMessagesList............................................................................29
990-5219-001
MGEGalaxy500040-130kVA480V
i
ii
MGEGalaxy500040-130kVA480V
990-5219-001
AboutThisManual
Thismanualdescribesthestartup,shutdown,andnormaloperationoftheMGEGalaxy5000with
informationontheuserinterfacedisplayanddisplaymenustructure.Formaintenancethemanual
describesalarmconditions,UPSisolationoperationandmaintenanceandsafetyinformationonservicing
batteriesfortheMGEGalaxy5000.
SymbolsUsed
WARNING:Indicatesanelectricalhazard,which,ifnotavoided,couldresultininjury
ordeath.
Caution:Indicatesahazard,which,ifnotavoided,couldresultininjuryordeath.
Note:Indicatesimportantinformation.
See:Indicatesthatmoreinformationisavailableonthesubject.
CompanionManuals
ForadditionalinformationabouttheMGEGalaxy5000,seethefollowingdocuments:
MGEGalaxy5000Installation990–5217–001
MGEGalaxy5000Receiving&Unpacking990–5218–001
FindUpdatestothisManual
Youcancheckforupdatestothismanualonwww.apc.com.Lookforthelatestletterrevision(A,
Betc.)ofthemanual.
990-5219-001
MGEGalaxy500040-130kV A480V
1
Overview
UserInterface
TheUPSisoperatedusingthecontrolanddisplayinterface.
A.GraphicalDisplay
B.LoadprotectedLED
C.MinorfaultLED
D.MajorfaultLED
E.Helpkey
F.Functionkeys.Each
keycorrespondsto
afunctionpresented
onthedisplay.The
functionofeachkey
changesdependingon
themenudisplayedon
thescreen.
G.Menukey.Thisbutton
providesdirectaccess
tothemainmenu.
H.ONbutton.
I.OFFbutton.
J.PFCONLED
K.UPSONLED
L.Operationonbattery
powerLED
M.LoadsuppliedLED
N.Bypassinoperation
LED
DisplayScreens
BasicOperationofDisplay
2
MGEGalaxy500040-130kV A480V
990-5219-001
A
PresstheMenukeytoaccesstheMainMenu.
B
PresstheHelpkeyforinformationonthepictogramfunctions.Thekeymustbehelddown.
Measurements
TheMeasurementsdisplayscreensconsistofthefollowingmeasurementsscreens:
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightMeasurementsonthedisplay.
3.PressthefunctionkeytoselectMeasurements.
4.Usethefunctionkeysortoselectbetweenthefollowingmeasurements:
BatteryMeasurements
V oltageMeasurements
CurrentMeasurements
PowerMeasurements
FrequencyMeasurements
RatiosMeasurements
ParallelMeasurements(option)
5.Pressthefunctionkeytoselecttherequiredmeasurementsscreen.
Alarms
Detailedinformationonallalarmsissuppliedonthedisplay.Seethe“Troubleshooting“sectionfor
alistofpossiblealarmmessagesinthedisplay.
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightAlarmsonthedisplay.
3.PressthefunctionkeytoselectAlarms.
4.Usethefunctionkeysortoselectbetweenthealarmmessages.
5.Pressthefunctionkeytoselecttherequiredalarmscreen.
990-5219-001
MGEGalaxy500040-130kV A480V
3
Status
TheStatusdisplayscreensconsistofthefollowingStatusscreens:
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightStatusonthedisplay.
3.PressthefunctionkeytoselectStatus.
4.UsethefunctionkeysortoselectbetweenthefollowingtwoStatusscreens:
Timestampedevents
Statistics
5.PressthefunctionkeytoselecttherequiredStatusscreen.
Settings
TheSettingsdisplayscreensconsistofthefollowingSettingsscreens:
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightSettingsonthedisplay.
3.PressthefunctionkeytoselectSettings.
4.UsethefunctionkeysortoselectbetweentheSettingsscreens:
Language
Date/time
Displaycontrast
Buzzervolume
Personalization
Outputvoltage
Password
Dry-contactsettings
5.PressthefunctionkeytoselecttherequiredSettingsscreen.
Controls
TheControlsdisplayscreensconsistofthefollowingControlsscreens:
1.PresstheMenukeytoreturntotheMainMenu.
2.UsethefunctionkeysortohighlightControlsonthedisplay.
3.PressthefunctionkeytoselectControls.
4.UsethefunctionkeysortoselectbetweentheControlsscreens:
ResetAlarms
Inverteron
Inverteroff
Forceloadtransfertoinverter
Forceloadtransfertobypass
Desynchronizeinverterfrombypass
Resynchronizeinverterandbypass
4
MGEGalaxy500040-130kV A480V
990-5219-001
TestsLEDs
BuzzerOFF
EnableLCMindications
DisableLCMindications
5.PressthefunctionkeytoselecttherequiredControlsscreen.
990-5219-001
MGEGalaxy500040-130kV A480V
5
UPSConguration
AccesstothePersonalizationFunctions
Caution:PersonalizationmustbecarriedoutwithswitchesQ1(8)andQ5N(11)open
(OFF)andswitchQ4S(9)closed(ON).
1.Pressthemenukey(A).
2.SelectSettings,thenPersonalizationusingthe
functionkeys(B)or↓.
3.Conrmbypressingthefunctionkey(B)←).
4.Enterthepasswordbysuccessivelyselecting
eachiconusingthecorrespondingfunctionkey.
5.Conrmbypressingthefunctionkey(B)←.
6.Tosavethepersonalizationsettings,conrmby
pressingthefunctionkey(B)←.
Thepasswordisfactorysetto:
Forinformationonhowtochangethepassword,
see“Settings“.
PersonalizationSettings
OperatingMode
FunctionFactorysettingOptions
UPSoperatingmode
NORMAL
UPSautomaticstartDisabledEnabled
Authorizednumberofstarts
41to255
Delaybeforeresetofnumberof
executedautomaticstarts
4seconds1to60seconds
Frequency
FunctionFactorysettingOptions
UPSoutputfrequency
60Hz60Hz
ToleranceforbypassACsource
8%0.5124%
Synchronizationspeedwithbypass
ACsource
2Hz/s1Hz/s
6
MGEGalaxy500040-130kV A480V
990-5219-001
AutomaticBypass
FunctionFactorysettingOptions
TransfertobypassACsourceEnabledDisableddisabledwhenlimiting
TransfertobypasswithbypassAC
sourceoutoftolerances
EnabledDisabled
Battery
FunctionFactorysettingOptions
Lowbatterywarningthresholdif
batterymonitorinactive
40%remainingbackuptime206080%remainingbackup
time
Lowbatterywarningthresholdif
batterymonitoractive
4minutesofbatterybackuptime1toXminutesofbatterybackup
time
Intervalbetweentwobatterytests30days1to180days
990-5219-001
MGEGalaxy500040-130kV A480V
7
Operation
Caution:Alloperationsconcerningsystemstart-upandcompliancewithstandardsand
regulations,includingthoserelatedtothebatterycabinet,mustbecarriedoutbytrainedand
certiedpersonnelbeforeusingtheUPS.
OperatingModes
Normal(DoubleConversion)Mode
Thisisthestandardoperatingmode,setbydefaultinthefactory.Twopossiblecases:
1.NormalACsourceavailable:LED(A)isON.
TheloadisprotectedbytheUPS.
2.NormalACsourcenotavailable:LED(B)isON.
Thebuzzersoundsintermittently.Operationonbattery
powerLEDonthemimic-panelisgreen.
TheloadissuppliedbytheUPSfrombatterypower .
Note:ThedisplayindicatesanyanomaliesrelatedtotheACsourceortheUPSaswell
asremedialactionifapplicable.Pressthefunctionkeyindicatedbythedisplaytoturn
thebuzzerOFF.
ECOMode(SingleUPSOnly)
Themainadvantageofthismodeisthatitreducestheconsumptionofelectricalpower.ECOmodemaybe
selectedexclusivelyviathecontrolpanelontheUPS.Threepossiblescenarios:
1.BypassACsourceavailable:LED(A)isON.
TheloadissuppliedinECOmode.
2.BypassACsourcenotavailable:LED(A)isON.The
buzzersoundsintermittently.Theloadisautomatically
suppliedinnormalmodeviatheNormalACinput.
8
MGEGalaxy500040-130kV A480V
990-5219-001
3.BothnormalandBypassACsourcesnotavailableor
outoftolerance:LED(B)isON.Thebuzzersounds
intermittently.TheloadissuppliedbytheUPSfrom
batterypower.
Note:ThedisplayindicatestheUPSoperatingstatusconditionsandtherequiredactions.
LoadonBatteryPower
TheloadcontinuestobeprotectedbytheUPSwhenthenormalACsourceisnotavailable.Poweris
suppliedbythebattery.
TransfertoBatteryPower
LED(B)isON.
Thebuzzersoundsintermittently.
Theloadissuppliedbythebattery.
EndofBatteryPower
LED(C)isON.
Thebuzzersoundsintermittently.
TheloadistransferredonthebypassACinputif
itispresent.
990-5219-001
MGEGalaxy500040-130kV A480V
9
OperationofMimic-PanelLEDs
TheMGEGalaxy5000systemissimpletooperateandyetprovidesawealthofcontinuousmonitoring
anddiagnosticfeaturestoensureproperoperation.OperatorsgainaccesstoinformationintheMGE
Galaxy5000systemthroughthedisplayanditsintegratedLEDmimicpanel.
Themimicdiagramdisplaysinformationdirectlyonthefrontpanel.Segmentsaregreenwhenthefunction
isactive.SegmentsareOFFwhenthefunctionisnotactive.Segmentsareredwhenafaulthasoccurred
inthefunction.
A.PFCONLED
B.UPSONLED
C.OperationonbatterypowerLED
D.LoadsuppliedLED
E.BypassinoperationLED
F.ONbutton
StartUpSingleUPSonNormalACInput
StepsActionLED(A)LED(B)LED(C)LED(D)LED(E)
1Q1open
OffOffOffOffOff
2
CloseQ1
green
OffredOffred
3
CloseBatteryCB
green
OffOffOffred
4
CloseQ4S
green
OffOffOff
green
5
CloseQ5N
green
OffOff
greengreen
6OpenQ3BP
green
OffOff
greengreen
7
PressONbutton
(F)
greengreen
Off
green
Off
StartUpSingleUPSonBypassACInput
StepsActionLED(A)LED(B)LED(C)LED(D)LED(E)
1Q4Sopen
OffOffOffOffOff
2
CloseQ4SOffOffredOff
green
3
CloseQ5NOffOffred
greengreen
4OpenQ3BP
OffOffred
greengreen
5
CloseQ1
green
Offred
greengreen
6
CloseBatteryCB
green
OffOff
greengreen
7
PressONbutton
(F)
greengreen
Off
green
Off
10
MGEGalaxy500040-130kV A480V
990-5219-001
OperationProcedures
ShutDownaSingleUPS
TheUPSremainsenergizedunlessitisshutdown.
1.Pressabuttontoexitsleepmode.
2.PresstheOFFbutton(A)for3seconds.
TheloadisnolongerprotectedbytheUPS.
Itissuppliedviathebypass.
3.Setthebatterycircuitbreakeroftheauxiliary
cabinetstoOFF.
4.SettheinputswitchQ1(B)toOFF.
Thechargernolongeroperatestokeepthe
batteriesfullycharged.
5.Opentheupstreamcircuitbreakersofthe
NormalACsourceandBypassACsourceto
completelypowerofftheUPS.
990-5219-001
MGEGalaxy500040-130kV A480V
11
RestartaSingleUPS
CheckthatswitchesQ4S(B)andQ5N(C)areclosed.Ifthisisthecase,continuewiththisprocedure,
otherwisereferto“ReturntotheNormalOperation,SingleUPS“.
1.SettheNormalACsourceinputswitchQ1(A)
totheONposition.
2.Waituntiltheendofthestartsequence.
3.Setthebatterycircuitbreakeroftheauxiliary
cabinetstotheONposition.
TheUPSstartsautomatically.
LED(D)isON.Theloadisprotectedbythe
UPS.
IftheLED(D)remainsOFF,presstheON
button(G)(theUPSisinmanualstartmode)and
conrmifnecessarybypressingthefunction
key(H)marked←.
IftheLED(C)stillremainsOFFandeitherof
theLEDs(E)or(F)isON,afaulthasoccurred
(see“IdenticationofAlarms“.
12
MGEGalaxy500040-130kV A480V
990-5219-001
ShutDownaParallelConguration
1.Pressabuttononeachunittoexitsleepmode.
2.PresstheOFFbutton(A)oneachunitfor3
seconds.
TheloadisnolongerprotectedbytheUPSs.
Itissuppliedviathebypass.
3.Setthebatterycircuitbreakersoftheauxiliary
cabinetstotheOFFposition.
4.SettheinputswitchQ1(B)ineachUPStothe
OFFposition.
Thechargernolongeroperatestokeepthe
batteriesfullycharged.
5.OpentheupstreamcircuitbreakersofNormal
ACsourceandBypassACsourcetocompletely
powerofftheinstallation.
990-5219-001
MGEGalaxy500040-130kV A480V
13
RestartaParallelConguration
CheckthatswitchesQ4S(B)andQ5N(C)areclosed.Ifthisisthecase,continuewiththisprocedure,
otherwisereferto“ReturntoNormalOperation,ParallelUPS“.
1.CheckthattheoutputswitchCB2intheexternal
systembypasscabinetisclosed.
2.CheckthatthebypassswitchCB1intheexternal
systembypasscabinetisopen.
Thencarryoutsteps3to5belowoneachofthe
UPSs.
3.SettheNormalACsourceinputswitchQ1(A)
totheONposition.
4.Waituntiltheendofthestartsequence.
5.Setthebatterycircuitbreakeroftheauxiliary
cabinetstotheONposition.
TheUPSsstartautomatically.Oneachunit,
LEDs(E)and(F)goOFFandLED(D)goes
ON.
TheloadisprotectedbytheUPSs.
IftheLED(D)remainsOFF,presstheON
button(G)oneachUPS(theUPSisinmanual
startmode)andconrmifnecessarybypressing
thefunctionkey(H)marked←.
IftheLED(D)stillremainsOFFandeitherof
theLEDs(E)or(F)isON,afaulthasoccurred
(see“IdenticationofAlarms“).
14
MGEGalaxy500040-130kV A480V
990-5219-001
IsolateUPS
IsolateSingleUPS
ToisolatetheUPSfromtheelectricalpowersourceandsupplytheloaddirectlybythenormalorbypass
ACsource,followtheinstructionsbelow:
1.Pressabuttontoexitsleepmode.
2.ShutdowntheUPSbypressingtheOFFbutton
(A)for3seconds.
TheloadisnolongerprotectedbytheUPS.
3.SetbypassswitchQ3BP(D)toON.
4.SetoutputswitchQ5N(E)toOFF.
5.Setthebatterycircuitbreakeroftheauxiliary
cabinetstoOFF.
6.SettheinputswitchQ1(B)toOFF.
7.SettheswitchQ4S(C)toOFF.
8.WaituntilthedisplayandLEDsgooff.
TheloadisnolongerprotectedbytheUPS,but
continuestobesuppliedwithACpower.UPS
maintenanceorservicingcannowbecarried
out.
WARNING:Powerispresenton
thepowerconnectionterminals.
990-5219-001
MGEGalaxy500040-130kV A480V
15
IsolateParallelUPSWithoutExternalBypassCabinet
ShutdownandisolatetherstUPS:
1.CheckthatthetwoUPSsareoperating.
2.Pressabuttontoexitsleepmode.
3.ShutdowntheUPSbypressingtheOFFbutton
(A)for3seconds.
4.SetoutputswitchQ5N(E)toOFF.
5.Setthebatterycircuitbreakersoftheauxiliary
cabinetstoOFF.
6.SettheinputswitchQ1(B)toOFF.
7.SettheswitchQ4S(C)toOFF.
8.WaituntilthedisplayandLEDsgooff.
TheloadisstillprotectedbytheotherUPS.
Maintenanceorservicingcannowbecarried
outontheUPSthathasbeenshutdown.
WARNING:Powerispresenton
thepowerconnectionterminals.
ShutdownandisolatethesecondUPS:
9.Pressabuttontoexitsleepmode.
10.ShutdowntheUPSbypressingtheOFFbutton
(A)for3seconds.
11.SetbypassswitchQ3BP(D)toON.
12.SetoutputswitchQ5N(E)toOFF.
13.Setthebatterycircuitbreakeroftheauxiliary
cabinetstoOFF.
14.SettheinputswitchQ1(B)toOFF.
15.SettheswitchQ4S(C)toOFF.
16.WaituntilthedisplayandLEDsgooff.
TheloadisnolongerprotectedbytheUPS,but
continuestobesuppliedwithACpower.UPS
maintenanceorservicingcannowbecarried
out.
WARNING:Powerispresenton
thepowerconnectionterminals.
16
MGEGalaxy500040-130kV A480V
990-5219-001
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

APC MGE GALAXY 5000 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
This manual is also suitable for

APC MGE GALAXY 5000 is a reliable power protection solution for small to medium data centers, server rooms, and critical equipment. Its advanced features include efficient double-conversion online operation, flexible ECO mode for energy savings, paralleling capability for increased capacity and redundancy, and advanced diagnostics for proactive maintenance.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI