  • Hello! I am an AI chatbot trained to assist you with the Ingersoll-Rand R Series Installation, Operation & Maintenance Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
R Series VCD Dryer
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
Service Department
1-800-526-3615
REFRIGERATED AIR DRYERS
2
REV:1203 StarWatch ID:
SPECIFICATIONS
Serial No. Model
ITEM DESCRIPTION VALUE UNIT
1 -------------------Dryer Design Max Air Flow @ PSI SCFM/PSI Comments:
2 --------------------------------Dryer Design Max Air PSI PSI
3
-
-----------------Dryer Design Max Inlet Temperature °F
REFRIGERANT
4
-
-----------------------------------------------Supply Voltage VOLT CHARGE: LBS.
5 -------------------------------------------------------------Cycle HZ
6 ------------------------------------------------------------Phase PH
7
REPLACEMENT
8
-
----------------------------------Number of Compressors ELEMENT:
9
-
--------------------------------Compressor Horse Power HP
10 --------------------------------------------------------------RLA AMPS
11
-
--------------------------------(copper) THHN Wire Size AWG #
11 ------------------------------Fuse / Circuit Breaker Size AMP
12
-
------------------------------------------Nema Starter Size #
13 --------------------------------------------------------Overload AMPS
14
-
-------------------------------------------Crankcase Heate
r
WATTS
15
-
-------------------------------Crankcase Heater Voltage VOLT
16
-
----------------------------------------------Number of Fans
17 -----------------------------------Fan Motor Horse Powe
r
HP
18 -----------------------------------------------Max Amp Dra
w
AMPS
19
-
--------------------------------(copper) THHN Wire Size AWG #
19
-
------------------------------------------------------Fuse Size AMP
20
-
--------(enter n/a if not used) Nema Starter Size #
21
-
---------------------------------------------Overload Setting AMPS
22
-
----------Water Condenser Max Inlet Temperature °F
23
-
--------Water Condenser Minimum Inlet Pressure PSI
24
-
-------------------------Control Transformer VA Rating VA
25
-
----------------Control Transformer Primary Voltage VOLT
26 -------------Control Transformer Primary Fuse Size AMP Electrical Dwg No.'s
27
-
------------Control Transformer Secondary Voltage VOLTS
28
-
--------Control Transformer Secondary Fuse Size AMP
29
-
-----------------------------Refrigerant Low PSI Setting PSI
30
-
----------------------------Refrigerant High PSI Setting PSI
31
-
-------------------------------Fan Bank #1 PSI Settings ON / OFF
32
-
-------------------------------Fan Bank #2 PSI Settings ON / OFF
33
-
-------------------------------Refrigerant Oil PSI Setting PSI
Control Center SN: Rev. V
Processed By: , Date:
3
TABLE OF CONTENTS
Page
1. Pre-Installation.................... 4
Inspection, Handling and Setup
Cautions and Operating Warnings
2. Dryer Installation................. 4
Location of Dryer
Air line Plumbing
Water Line Piping (Water Cooled Units)
Electrical Connections
3. Principle of Operation.......... 4-5
Air System
Refrigeration System
Operation
4. Flow Schematics ............... 6-9
5. Routine Maintenance
and Service.......................... 10
6. For The Refrigeration
Service Technician.............. 10-11
Refrigerant, Oil and Dryers
Evaporator Leaks
Refrigerant Control Valves
Drains
Electronic Controls
Factory Assistance
Page
7. Trouble Shooting Guide....... 12-13
8. Warranty.............................. 14-15
Warranty procedure
Maintenance records
Coverage
Standard Warranty
Heat Exchanger Warranty
Not covered by Standard Warranty
Chargeable service calls
Warranty registration
International Warranty
Disclaimer
In conclusion
Warranty registration card
(front & back)
9. Operational Controls...........16 - 36
10. Electricals & Applicable
Drawings.............................37 - 75
Water Cooled
Air Cooled
4
1. PRE-INSTALLATION
Inspection, Handling and Setup
Inspect the dryer carefully upon arrival and note any
damage on the freight bill. File a notice of concealed
damage if: (1) there are any dents in the cabinet; (2) the air
and drain pipes are not straight; (3) there is any sign of oil
on the skid floor. File these claims with the carrier
immediately!
Cautions and Operating Warnings
Never work on unit under air pressure.
Never work on unit when power is connected.
Do not over pressurize unit.
Install unit in a clean, cool (50º - 85ºF); well lighted
location.
Do not shut unit off at disconnect switch except during
servicing. Unit must be turned on and off by the panel
switch located on the dryer.
Do not pass air through the dryer while the dryer is in
the “OFF” position.
Do not operate dryer at abnormal conditions (high flow,
high inlet temperature, high ambient, high inlet pres-
sure, etc.)
2. DRYER INSTALLATION
Location of Dryer
Unless supplied for special conditions, the air cooled
dryers must be located in an area with an ambient tem-
perature between 50º and 100ºF., and free from explosive
and corrosive fumes. High ambient temperatures affect the
outlet dew point of the dryer. For every 10ºF of ambient
temperature over 100ºF, a decrease of 6% of dryer perfor-
mance is encountered with air cooled dryers. The unit
must not operate in an ambient of over 100ºF. For ambient
conditions of over 100ºF, water cooled dryers are sug-
gested and are available upon request.
CAUTION – Three feet of space must be allowed between
all open grills and walls or other objects. If the dryer is
installed in a confined area, an exhaust system must be
provided to avoid excessive recirculation of hot room air.
Air line Plumbing
All connections are made to the outside of the cabinet as
follows:
Air plumbing must be supported independently of the
dryer.
If vibration is present, flexible metal hoses must be
installed to prevent it from being transmitted to the dryer.
Use unions or flange joints.
Bypass piping around the dryer is recommended for
ease in servicing or removal of unit if necessary.
Direction of flow through the dryer must be observed. A
check valve on the outlet of the dryer to prevent back flow
and false loading is recommended.
NOTE: Use two wrenches when connecting to dryer piping
so as to prevent damage to internal air or water lines.
Water Line Piping (Water Cooled Units)
On water cooled units, install a strainer ahead of the water
inlet. Dryers are designed for 85ºF inlet water temperature.
Higher water temperature reduces dryer capacity. Minimum
water pressure is 25 psi. Maximum water pressure is 105
psi.
Electrical Connections
Before connecting electrical power to the dryer:
Check for correct voltage and phase at electrical con-
nection box.
Install a fused disconnect switch near the dryer.
Connect power to the stripped leads located in the
electrical connection box or to main lugs of contactor,
whichever is necessary.
(NOTE: All units must be externally grounded to protect
against the possibility of severe electrical shock.)
CAUTION: Wire the dryer separately from the air
compressor. The dryer must NOT cycle on and off with
the air compressor.
Phase rotation is only important if the dryer has a 3
phase condenser fan. Fans must PULL air through the
condenser coil.
Crankcase heaters are pre-wired at the factory to the
line side of the terminal box or contractor. Heaters must
be energized at all times, therefore the main disconnect
must be left on except when servicing the dryer.
3. PRINCIPLE OF OPERATION
The VCD REFRIGERATED AIR DRYER is designed to
operate automatically and continuously from no load to full
load without freeze up.
Air System:
The major air system components are the air to air
PRECOOLER / REHEATER, the EVAPORATOR, and the
MECHANICAL SEPARATOR.
Hot, wet air enters the inlet of the precooler/reheater where it
is cooled by the outgoing air. The air then enters the
evaporator where it is cooled by the refrigerant causing the
air’s humidity to condense into liquid water.
Next the air travels to the separator. First, the air enters the
separator where bulk oil and moisture are removed from the
air stream through a combination of centrifugal action and
velocity reduction. After removal from the air stream, all
contaminants are ejected from the air system by Demand
Control Solenoid Drains.
From the separator, the cold dry air enters the outgoing side
of the precooler/reheater where it is reheated by the hot
incoming air.
The precooler/reheater serves a triple purpose. By precool-
ing the incoming air, it conserves refrigeration use and by
5
reheating the outgoing air, it serves to eliminate sweating of
pipes in the plant air system. Most important, it increases
the temperature dew point split, preventing moisture from
condensing out of the compressed air when the air is
expanded.
Refrigeration System
The major components of this system are the COMPRES-
SOR, the CONDENSER, and the EVAPORATOR. The
compressor pumps high pressure, high temperature gas to
the condenser. The heat is dissipated through finned tubes
with the assistance of motor driven fans. On water cooled
units the heat is dissipated through a water filled tube and
shell condenser.
During the cooling process, the refrigerant changes from a
heat laden vapor to a liquid. This liquid refrigerant flows from
the condenser to the filter dryer, and then through the sight
glass which indicates refrigerant level. Immediately before
the inlet of the evaporator is a thermostatic expansion valve
which regulates the refrigerant flow to the evaporator as low
pressure cold liquid. The cold refrigerant cools the air in the
side of the evaporator. As the low pressure liquid refrigerant
absorbs the heat from the air it boils and changes to a
vapor. This low pressure, low temperature vapor is then
returned to the refrigerant compressor where it is again
compressed to a high pressure, high temperature gas, and
the refrigeration cycle repeats itself.
VCD Dryers are rated to deliver full capacity (SCFM at 35ºF
pressure dew point air) at 100 PSI line pressure, 100ºF.
inlet air, in 50º to 100ºF ambient, at 2 to 4 PSI pressure
drop. Higher line pressures, up to rated maximum and
cooler inlet air increases capacity. Free liquid water, low
pressures, higher air temperatures and condensable
chemical vapors, decrease capacity. Consult the factory for
proper dryer sizing.
5. START UP
NOTE: Please read and understand the entire operation and
maintenance manual prior to starting the dryer. This is a
brief start up procedure for those familiar with dryer opera-
tion.
CAUTION: There should be no air flow through the dryer
before or during start up. It is recommended that the dryer
be installed with bypass piping to better service the unit.
DRYER START UP PROCEDURE:
1) Make main electrical connection to dryer and apply
power. Refer to dryer name plate or manual to deter-
mine correct voltage. Leave power on unit for 8 hours
before proceeding.
2) On water cooled units make sure there is proper water
pressure and temperature supplied to the water con-
denser. (Min 25 psi and max 85º F water temperature)
3) Dryers are shipped with
TAGGED refrigeration service
valves closed. TAGGED service valves must not be
opened until main power is permanently applied.
However, ONLY TAGGED service valves must be
opened prior to start up.
Locate TAGGED service valves.
Remove protective cap from valve stem. (see figure
below)
Using a refrigeration service wrench or small crescent
wrench, turn the valve stem counterclockwise until it
stops. Occasionally it may be necessary to retighten
the packing nut (clockwise) if a leak is observed. The
valve will now be fully open.
Replace cap.
In case of refrigeration ball valves, you must turn 90
degrees to open as stated on valve. (See figure below)
4) Locate the compressor service toggle switch. This
service switch must be turned on immediately after
valves are opened.
· The refrigeration compressor may run briefly and then
stop. This process is called pump down. If storage
conditions were adverse, the compressor may make a
loud metallic hammering noise. If this happens, turn the
service switch off and wait half a minute, then turn back
on. Repeat this step until the compressor runs
smoothly, then stops. Leave the service switch in the
ON position.
5) The dryer is now ready to run. Turn the dryer on at the
control panel.
The digital display should start dropping.
6) With the dryer turned ON from the control panel and
cycling several times, you may now introduce com-
pressed air to the dryer. Open the inlet and outlet
ISOLATION VALVES. Close the BYPASS VALVE.
7) Check automatic drain for proper operation. Drain
should open at regular intervals based on the drain
control settings or water level.
8) Restart dryer using this procedure after maintenance,
power failure or after prolonged shutdown periods.
CAUTION: Failure to follow the above steps in the order
shown MAY result in damage to equipment NOT covered
under warranty.
Operating Instructions:
Always:
Turn dryer ON and OFF with control panel button.
Keep power to unit during off cycles.
Start dryer and allow it to cycle several times prior
to allowing air flow through the dryer.
Clean condenser when dirty.
Keep ambient temperature under 100º F.
Keep inlet temperature under 100º F.
Check and clean Y-strainer periodically.
10
Never:
Turn off main power disconnect except when
servicing.
Allow air to flow through the dryer when it is not
running.
Cycle dryer with air compressor
5. ROUTINE MAINTENANCE AND SERVICE
Air Cooled Condenser
Very little routine care is necessary for the VCD Dryer. The
most important step for an air cooled dryer is to keep the
air cooled condenser clean. The air is being taken in
across the condenser. Dirt from the ambient air will
accumulate on the finned tubes of the condenser coil. As
the dirt will accumulate on the rear of the condenser,
blowing from the inside out is most effective. In dusty
areas the simple, inexpensive installation of a furnace filter
will stop the majority of dirt entering the dryer’s condenser.
This should be changed when visibly dirty. If the condenser
does become dirty, an abnormally high refrigeration dis-
charge pressure will occur. The unit may shut down on
high dew point or high pressure. This will greatly reduce
the life of the refrigeration compressor and could void the
warranty.
Separator/Coalescer Drains
Drains should be checked regularly. Failure of an auto-
matic drain can result in extreme amounts of water and
debris in your air system.
6. FOR THE REFRIGERATION SERVICE
TECHNICIAN
IR recommends that only qualified and experienced refrig-
eration mechanics do repair work on these units. This
section is a list of hints and instructions for the skilled
serviceman.
Recharging Dryer – Refrigerant, Oil and Dryers
Consult the IR Service Department for the required charge
needed for each unit. The relatively large charges are
needed because of the flooded-shell evaporators. Use the
following to assess the adequacy of the charge when
unsure:
The sight-glass should stay filled most of the time
when the dryer has its customary air load. It is normal
for the glass to break up when the condenser fan starts
if the load is light or when the unit unloads. It may
take time to refill when it reloads. Don’t charge to clear
the glass with no load; that will be too much.
All units have a charging fitting on the evaporator shell.
The unit must be charged through this fitting and/or the
liquid line service valve. The best way is to dump liquid
into both ports with the dryer off, then start up and
continue feeding a full stream of liquid into the evapora-
tor until charged.
Do not charge vapor. You want the charge installed as
fast as possible so the oil will be returned to the compres-
sor as in normal operation.
Additional oil is added at the factory to compensate for the
migration with the freon. If a compressor is replaced,
remove the drain plug from the evaporator shell (on steel
shells) to drain any excess oil trapped. If that isn’t pos-
sible, it may be necessary to remove oil from the system
after start-up. Excess oil is indicated by noisy and vibrat-
ing compressor operation. Consult factory for recom-
mended oil changes. Prolonged operation with insufficient
charge or a bad TXV may cause oil to be trapped in the
evaporator. If the compressor is still good, this oil will
return within a few minutes of operation with the correct
conditions. For R-404 & R-134 applications use synthetic
refrigeration oil.
Please replace both suction and liquid filter-dryers together
whenever the system has been exposed to air or water,
unless it’s brand new or you know how much gas has gone
through it. Solids will be caught in the suction drier even if
the system is dry.
Evaporator Leaks
If there is a leak between the tube and shell side of the
evaporator, the usual symptom is high head pressure,
because the air pressure is higher than the refrigerant
pressure.
To determine this, bypass airflow, stop dryer, and observe
head pressure after it stabilizes. 20 minutes is sufficient. If
the pressure is much higher than that corresponding to the
ambient temperature, there is air in the system. Purge air
at compressor discharge or receiver inlet to verify.
Gross leak-checking of the evaporator is done at the
separator drain with air pressure off and at least an hour
wait. If a leak is verified, it can often be fixed by removing
the bonnets, locating the leak with bubble soap and re-
rolling the leaky tubes. Split evaporator tubes can be
plugged with special tapered brass plugs.
WARNING: If the refrigerant has been seriously contami-
nated with water you probably won’t be able to dry it with
dryers or vacuum. Do a solvent cleanup on the evaporator
and suction accumulator or replace the evaporator.
Refrigerant Control Valves
Expansion valves: The superheat (+15º F) that the valve
control’s is created in the control evaporator or suction line
heat exchanger. There is liquid or zero superheat at the
main evaporator outlet to facilitate oil return and keep the
shell flooded. If there is superheat at the main evaporator
outlet or if the suction line to the compressor is warm to the
hand, 1) check the charge. If the sight-glass is full, 2) the
TXV may be defective or the liquid line is blocked. The TXV
superheat adjustment is not critical.
IR uses standard type valves.
Don’t use any TCLE Alco valves. TCLE valves are too
slow.
Use cross-ambient “C” or liquid “L” charges. Do not
use any pressure limiting or all-purpose “W” charges.
11
We recommend that you increase the superheat setting
of the new valve about 5º F from the factory setting.
Turning the stem 2 turns in should be sufficient.
Position the sensing bulb of the new valve just where
the old one was. It is crucial that the suction line be
clean and the bulb well insulated.
Solenoid Valves: The suction solenoid valve rarely causes
any trouble because the pressure difference across it is
never great. Unloader solenoids operate with greater
differentials. The VCD Dryer uses valves with a rated life of
more than two million operations. When they finally wear
out, the usual symptom is failure to close. The valves can
usually be restored by installing a diaphragm repair kit
available from IR.
Drains
The draining of water from the separator is the most crucial
part of the whole process. A complaint of “there’s more
water in the air now than there was before the dryer was
installed” is usually a drain problem.
The VCD Dryer has a demand operated drain. Operate the
drain manually and be sure that air blows out of the drain
line. Clean the strainer and solenoid valve if not.
The MRD demand Drain has a SINGLE point hermetically
sealed float switch. This extremely simple mechanism
resists fouling and wear.
Normally a single point drain will not work because the
switch would be constantly short cycling on/off and the
solenoid or switch would fail, —but the MRD Solved the
problem with timed electronic delay that allows the drain to
empty the vessel without loss of Compressed air.
Caution – Warning: remove all pressure before servicing
drain. Remove all air pressure and disconnect electrical
power from the drain
The MRD is easily disassembled for cleaning by removing
the four main bolts.
Yearly (or sooner) disassemble and clean vessel.
After disassembly be sure the float switch is mounted in the
same position (check arrow on float)
The dew point temperature is sensed by a sensing probe
inserted in one of the evaporator tubes. When air passes
over the probe, the air temperature controls the dew point
normally. When there is little or no air flow, the controller
sees the evaporator temperature and is able to prevent it
from going below freezing.
A malfunction of the control system can be suspected if:
1) Suction pressure is very low even when controller reads
over the set point or unit appears to be pumped down
and stopped when it shouldn’t be.
2) Water freezes in the evaporator causing air pressure
drop.
3) There is erratic or out-of-range indication of dew point.
This is controller or sensor trouble. Consult factory for
details
4) Dryer won’t restart after you stopped it for a test. This is
normal if you stopped when it was below setpoint. It will
restart when the dew point temperature comes above the
controller setting.
Factory Assistance
Please do not hesitate to call the Ingersoll-Rand factory for
technical information and assistance. We have skilled
troubleshooting and engineering personnel who are thor-
oughly familiar with the equipment. A short call may save a
long troubleshooting experience. Call 1-800-526-3615.
Instructions for Ordering Parts
All parts orders should be placed with your local Ingersoll-
Rand Service provider.
When ordering parts specify dryer model and serial number
(See nameplate on unit). Please call 1-800-526-3615.
12
7. Trouble Shooting Guide
COMPRESSOR WILL NOT START. NO HUM:
Line disconnect switch open. Close switch.
Fuse removed or blown. Replace fuse.
Overload tripped. Wait 5 to 20 minutes to reset. Check ambient
and inlet air temperatures, operating pressure and air flow rates
against rated capacities listed, to determine cause of overload.
Loose or improper wiring. Check connections against schematic.
Tighten loose connections.
Safety controls tripped (oil, temperature, refrigerant). Test controls
for malfunction by jumpering. Look for reason device tripped (high
head, low suction, oil loss). Correct any malfunctions such as
dirty condenser, high ambient, overloads. Replace faulty controls.
Starter coils open or contact burnt. Replace coils and/or contacts.
COMPRESSOR WILL NOT START, HUMS, (Trips overload protector.)
Loose or improper wiring
Low line voltage, 10% of nameplate rating. Check line voltage with
voltmeter. Correct condition.
Start winding open or shorted. Check with ohmmeter, referring to
motor schematic for correct value. Replace motor.
Open or unbalanced phase ( 3 phase units). Check phases for
equal voltages (+/- 10%).
Relay or contactor not closing. Examine contacts and coils for
burning, opens, shorts or sticking. Correct conditions.
Compressor internal mechanical failure. Loss of oil may have
locked up compressor. If above steps do not apply, this may be
the cause. Replace compressor.
UNIT SHORT-CYCLES:
Motor overload cutting out. Check for high head pressure air
overload, high ambient clogged condenser.
Defective overload protectors. Check currents. Replace if neces-
sary.
Low voltage or 3 phase unbalance. Voltages must be within 10%
on nameplate rating. Correct off specification conditions.
Refrigerant shortage. Check for leaks. Repair and recharge.
Low suction pressure or sticking expansion valve. Check valve
setting and operation. Adjust, repair or replace.
Shorted motor winding.
LOW OR NO OUTLET AIR PRESSURE:
Incorrect or restricted piping. Look for restrictions in lines or too
small pipe sizes. Replace piping if needed.
Evaporator and/or precooler clogged. If clogged, reverse flow and
flush with mild detergent. Evaporator frozen. Turn unit off to thaw.
13
WATER DOWNSTREAM OF DRYER:
Test drain. Check the output for power from relay marked “drain” on
control board. If no output, then replace board. If power is present
check wiring to solenoid and status of coil. If energized and valve is
not open clean valve or replace if needed.
Check for blockage in drain line.
Clean “Y” strainer
DRAIN STAYS OPEN ALL THE TIME (DRAIN ALARM)
Check the valve for debris. Clean if required.
Check float switch. Dirty or defective.
Check board. Relay stuck or defective.
14
INSTRUCTIONS FOR ORDERING REPAIR PARTS
When ordering parts, specify dryer model and serial
number. (See name plate of the unit).
All orders for parts should be placed with your local
Ingersoll-Rand Service Provider. Should you not know the
dealer in your area, contact IR at (800) 526-3615.
8. IR WARRANTY
The IR Warranty Philosophy…..
Warranty can be defined as a protection of investment.
Warranty policies can come in all different shapes and
sizes, however, the most important attribute to a successful
policy is its fairness to all parties involved. This brings us to
the explanation of components that make up the IR War-
ranty Philosophy.
Warranty Procedure
IR believes in giving the most expedient service possible to
our customers. In order to accomplish this the most
important step for our customer is to call us (1-800-526-
3615) immediately in the event of a potential warranty
situation. The phone call serves several purposes:
It puts the customer in direct communication with the
factory assures them of factory support.
It helps us to diagnose the problem and perhaps
remedy it over the phone. This saves everyone time. In
most cases we can determine the root cause of the
failure through a simple phone call.
It helps us to assess any parts that may be needed for
repair. This eliminates time and travel by a service
company making one trip with parts in hand.
It helps us to determine situations non related to the
dryer. After the phone call has been placed, and if
service is necessary, we will authorize a service house
in close proximity to the customer.
It is important when a call is placed to us for a potential
warranty situation, that the following information be pro-
vided:
Model and serial number.
Start-up date.
Company name.
Dryer location
Phone number
Contact Person
Specific nature of complaint (Diagnostic code, high dew
point, etc..)
Important: IR reserves the right to deny any claim submit-
ted without our knowledge and proper authorization.
Warranty Parts and Returns…
In the event a part is required to complete a warranty repair
the following steps will occur:
1. A standard parts order must be placed with our service
department (1-800-526-3615) along with a purchase
order number.
2. The customer that placed the order will receive an
invoice for the part. This is for memo billing only. The
invoice will also contain a Return Authorization Number
(RMA)
3. After the part has been replaced, the defective part that
was removed must be returned to us. The RMA must
accompany the returning part.
4. Upon receipt of the defective part we will issue a credit
against the original invoice.
5. If the part is not returned within 30 days the invoice will
stand open and chargeable.
Maintenance Records
It is recommended that detailed performance and regular
maintenance records are kept.
Detailed records are very valuable in troubleshooting &
diagnosing issues.
Coverage
Our refrigerated dryers are equipped with a two (2) year
parts & labor warranty. The heat exchangers are covered
by five (5) year warranty.
Our dryers are to be free from defects in material and
workmanship (under proper use, installation and mainte-
nance) for the stated period of two years from the date of
start-up or 30 months from the date of shipment which ever
occurs first.
The heat exchanger warranty covers the first 60 months of
operation or 66 months from date of shipment
What is Not Covered by “Standard Warranty” for all
Dryer Lines
Damage caused by accidents
Damage caused by fire, theft, freezing, vandalism
Damage caused by operation outside the rating
conditions
Operation of the dryer in ambient temperature in
excess of 100ºF
Operation of the dryer with inlet air temperatures in
excess of 100ºF
Operation of the dryer in excess of rated SCFM
Operation of the dryer in excess of rated PSIG (unless
specifically rated for abnormal conditions)
Damage caused by corrosion due to environment and/
or chemical treatments
Damage caused by lack of maintenance
Damage caused by failure to follow requirements of the
maintenance schedule is not covered. Proof of proper
maintenance is the owner’s responsibility. Keep all
records and make them available if questions arise
about maintenance.
15
Freight Damage – Freight damage is not covered
under warranty. Should your dryer incur freight
damage, file a claim with the carrier immediately. At
the option of the claimant, you may contact a local
contractor to do a thorough investigation and repair the
damaged dryer. You may also return the dryer to IR,
freight prepaid. The factory will perform the repairs
chargeable to the original consignee. The customer
would then include these costs on their claim.
Dryer Alteration by Distributor or End User – This
warranty does not cover alteration of the dryer or failure
of dryer components caused by such alterations.
Economic Loss – This warranty does not cover any
economic loss, extra expense including payment for
the loss of time, pay, inconvenience, storage, loss of
dryer use, dryer rental expense, lodging, meals, or
other travel costs.
Maintenance – Performing normal maintenance
services as detailed in the maintenance schedule are
not covered and are at the customers expense includ-
ing cleaning condenser, drains and filters.
Chargeable Service Calls
IR reserves the right to decline any warranty claim, with or
without proper authorization, in which non-warrantable
condition was found. In the event this occurs, the cus-
tomer should be billed for the call as standard service.
Warranty Registration
Each dryer comes with a service manual. In the last
pages of this manual there will be a warranty registration
card. The card must be filled out and returned to us within
30 days of start-up, to receive warranty.
International Warranty
Our policies cover equipment within the United States and
Canada. Any units shipped to or sold outside of the United
States or Canada will carry a two year, parts only warranty.
The IR Disclaimer
IR makes no other warranty of any kind whatsoever,
expressed or implied and all warranties of merchantability
and fitness for a particular purpose are hereby disclaimed
by IR. IR shall in no case be subject to any obligation or
liability whatsoever with respect to product or services
manufactured or furnished by IR or any acts of omission
relating thereto. The remedy provided under this warranty
shall be the sole, exclusive, and only remedy provided
available to the purchaser. Under no circumstances shall
IR be liable for any special, indirect, incidental or conse-
quential damage, losses or delays however caused.
IR reserves the right to make changes in dryers built and/
or sold by them at any time without incurring any obliga-
tion to make the same or similar changes on dryers
previously built and/or sold by them.
In Conclusion
Our philosophy is clear. We will stand behind it and uphold
the most professional and expedient service to our distribu-
tors and ultimately our customers. We are always review-
ing our warranty policy. We feel our policy is as good as
any in the industry. If you feel another manufacturers
warranty policy, as a whole, is better, submit the manufac-
turers literature and we will consider its qualities in our next
policy review.
Thank you for choosing an IR product !!
16
CONTROL PANEL
17
DISPLAYS and ALARMS
1) DEW POINT CONTROLLER AND DISPLAY.
Directly controls dew point and provides constant
digital display of dew point. Factory set at 36ºF.
During ACTUAL display mode, displays the dew
point temperature from 20º to 99º F or -6º to 37º C.
During DP SET mode, the unit displays dew point
set points from 34º to 50ºF in 1º steps, or 1º to
10ºC in 1/2 steps. (Note that the ones digit decimal
point is used to indicate 1/2º when displaying set
point in Celsius scale.) ºC LED- indicates that the
temperature is displayed in Celsius. ºF LED –
indicates that the temperature is displayed in
Fahrenheit. ACTUAL LED – indicates the display
is in ACTUAL mode. Display shows actual
temperature being measured by system. DP SET
LED - Indicates that the display is in programming
mode during which the set point can be changed
and stored. The dew point display also displays
the unit error codes when they occur. (see
Diagnostic codes)
2) ON/OFF BUTTON .LED - Indicates when the unit is
operating.
3) RAISE and LOWER BUTTONS. These are used to
adjust the set point values. The set point will
change once for each time pressed. If the button
is pressed and held, the set point will change one
step per second.
4) SET BUTTON. Toggles between Actual Display
mode and Set point Display mode. During the Set
point Display mode, the Raise and Lower keys are
used to select new set points which are stored in
nonvolatile memory when the mode is set back to
ACTUAL. If no keys are pressed within 15 sec-
onds, the mode is automatically set to “ACTUAL”.
This switch is also used to select the temperature
scale that the unit will operate in. By pressing and
holding for 5 seconds the unit will toggle between
the Fahrenheit and Celsius scale.
5) HIDDEN BUTTON. Positioned in the bottom center
of the Dew Point window between the MODE keys.
When pressed, the display will show the external
suction temperature at the expansion bulb. It has
no further effect on operation. It may also be used
for other diagnostics and factory test purposes
6) POWER SAVER ACTIVE LED. Unit in mode of
minimal power consumption.
7) HIGH DEW POINT ALARM LED. Indicates that the
unit is in the High Dew Point condition. The high
dew point alarm light, with remote dry contacts, will
activate when the actual dew point is 15º F higher
than the dew point set point. Any diagnostic code
will activate the high dew point alarm immediately.
8) DRAIN CONTROL. Will operate by either a ‘LEVEL
FLOAT’ or ‘TIMED’ interval. If the dryer is equipped
with a Level Float (electrical connections to terminal
J9), the drain will respond to the float signal on
demand to operate the drain. The duration that the
drain valve is open, will be the amount of time it
takes for the fluid level to drop and reset the float
signal, plus, a pre-set time of a few seconds
thereafter. The drain valve will also operate auto-
matically once every 30 minutes (independent to the
float signal). The 30 minute timed interval setting
can be adjusted down to 1 minute or raised up to 60
minutes if desired. To adjust the drain ‘Timed
Interval’ setting, press the SET button twice (note
that the Actual and DP Set LED’s will both extin-
guish). The value indicated in the display will be the
Timed Interval setting. Use the UP or DOWN arrow
to the desired timing set point. Pressing the SET
button again will return the display to reading the
dew point and the ‘Actual’ LED will once again
illuminate.
9-10) AIR INLET and AIR OUTLET PSI GAUGES.
Indicates that unit is pressurized. Unit must be
depressurized and bypassed before any service
work is done on air system. Excessive pressure
drop (more than 5 PSIG) across dryer indicates
water may be freezing in the evaporator.
EXTERNAL SENSORS, CONTROLS and RELAYS
DRAIN RELAY (K1) – This onboard relay opens the drain
valve according to drain controls.
SUCTION RELAY (K2) – This onboard relay turns on
according to the mode and dew point conditions and
opens the suction or liquid line valve when active.
UNLOADER RELAY (K3) – not applicable.
COMPRESSOR RELAY (K4) – This onboard relay
controls the compressor according to the mode and dew
point conditions.
HIGH DEW POINT RELAY (K5)This onboard relay and
LED alarm turns on when the dew point is 15º F above
the set point. This is also active during any error
conditions.
DEW POINT SENSOR (Probe 1) – Resistive NTC sensor
for measuring dew point temperature.
SUCTION TEMPERATURE SENSOR (Probe 2) – Resistive
NTC sensor for measuring external suction temperature
at the expansion bulb (E3 Probe).
18
MANUAL
Optional Electronic Panel
19
PREFACE:
This document is intended to make familiar, the Control Center functionality. The ‘manual’, can serve as
a handy guide to quickly move through the operations of the dryer it is controlling. It is not intended to
replace the more comprehensive, specific ‘dryer manual’ that will show all other aspects of operation
and safety. It is IMPORTANT that both manuals be referenced for complete dryer understanding.
MENU TREE
a. STARTUP NULL SCREEN------------------------------------------------------------------------------------ [ 20 ]
VCD - VARIABLE SPEED DRYER
-------------- PRE-STARTUP
--------------------- STARTUP
--------- CHANGE MODES
b. MAIN SCREEN --------------------------------------------------------------------------------------------------- [ 20 ]
DISPLAY ORIENTATION
TYPICAL SCREEN DISPLAYS
c. EVENTS ------------------------------------------------------------------------------------------------------------- [ 21 ]
EMERGENCY STOP
STANDBY
DEWPOINT OPTION (not installed)
ACTIVE ALARMS
DEWPOINT ALARM
NO FLOW
d. REVIEW ALARM LOG (‘J’ Series Menus) ---------------------------------------------------------------- [ 22 ]
e. DISPLAY SENSOR VALUES (‘K’ Series Menus) ------------------------------------------------------ [ 24 ]
FLOW MONITOR (4-20mA / 1 to 5 volt input)
MAIN MENU
1. DEWPOINT SETTINGS (‘D’ Series Menus) ------------------------------------------------------------------------------------ [ 25 ]
DEWPOINT SET
2. SETUP MENU (‘E’ Series Menus) -------------------------------------------------------------------------------------------------- [ 25 ]
COMPANY INFORMATION ----------------------------------------------------------------------------------------------- [ 25 ]
PHONE & www MESSAGE
PRODUCT INFORMATION ------------------------------------------------------------------------------------------------ [ 25 ]
TYPE OF DRYER & SN#
FACTORY DEFAULTS
GOTO ‘NULL STATE
CALIBRATION MENU (‘H’ Series Menus)
INLET PRESSURES
REHEATER PRESSURE
OUTLET PRESSURE
DISCHARGE PRESSURE
SUCTION PRESSURE
ELEMENT DP SETTINGS
FLOW RANGE SETTINGS
DRAINS SETUP MENU (‘I’ Series Menus) ------------------------------------------------------ [ 27 ]
#1 DEMAND or TIMED OPERATIONS
#1 INTERVAL (Timed)
#1 DURATION
#1 AUTOTEST
20
#2 DEMAND or TIMED OPERATIONS
#2 INTERVAL (Timed)
#2 DURATION
#2 AUTOTEST
COMMUNICATIONS MENU (‘F’ & ‘G’ Series Menus) ----------------------------------------- [ 28 ]
ADJUST CLOCK
STAR WATCH -Host to Control: YES
MODEM SETUP
MODEM ENABLE
MODEM TEST
MODEM RESET (Reprogram)
VIEW MODEM SETTINGS
3. SENSOR SETTINGS (‘C’ Series Menus)----------------------------------------------------------------- [ 28 ]
P1: LOW INLET PRESSURE
P1: HIGH INLET PRESSURE
P2: REHEATER PRESSURE
P3: OUTLET PRESSURE
P4: DISCHARGE PRESSURE
P5: SUCTION PRESSURE
P6: SEPARATOR DP
FLOW
4. TEMPERATURE SETTINGS (‘B’ Series Menus) ---------------------------------------------------------[ 29 ]
T1: DRYER INLET SETPOINT
T2: PRECOOLER SETPOINT
T3: DRYER OUTLET SETPOINT
T4: REFRIGERANT SETPOINT
T5: SUCTION SETPOINT
T6: AMBIENT/H2-0 SETPOINT
5. VIEW ALARMS (‘A Series Menus) ---------------------------------------------------------------------------[ 29 ]
HIGH DEWPOINT
LOW FLOW
(E1/E2) DEWPOINT PROBE FAULT (OPEN OR SHORT)
MOTOR OVERLOAD
(E3) SUPERHEAT OUT OF RANGE
(E4) LOW DEWPOINT
(E5) DRYER OVERLOAD
(E6) LOW FREON OR OIL PRESSURE
(E7) HIGH FREON PRESSURE
(WI) LOW AIR-IN PSI
(W2) HIGH AIR-IN PSI
(W3) COALESCER PSID
(W4) HIGH INLET AIR TEMP
(W5) HIGH AMBIENT / H2-0 TEMP
(W6) DRAIN FAULT
MODEM FAULT
/