FScurtis RNP125 User manual

  • Hello! I am an AI chatbot trained to assist you with the FScurtis RNP125 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
F 39° F
C
OFF
ON
33°
C
3227498
Rev. A
AUGUST 2012
RNP SERIES
REFRIGERATED COMPRESSED AIR DRYERS
OPERATOR
MANUAL
RNP75 RNP100 RNP125
RNP150 RNP200 RNP250
RNP300 RNP400 RNP500
2
GENERAL SAFETY INFORMATION
1. PRESSURIZED DEVICES:
This equipment is a pressure containing
device.
• Donotexceedmaximumoperating
pressure as shown on equipment
serial number tag.
• Makesureequipmentisdepressurizedbefore
workingonordisassemblingitforservice.
2. ELECTRICAL:
This equipment requires electricity to
operate.
• Installequipmentincompliancewith
all applicable electrical codes.
• Standardequipmentissuppliedwithelectrical
enclosuresnotintendedforinstallationinhazardous
environments.
• Disconnectpowersupplytoequipmentwhen
performinganyelectricalservicework.
3. BREATHING AIR:
• Airtreatedbythisequipmentmay
notbesuitableforbreathingwithout
furtherpurication.
Refertoapplicablestandardsand
specicationsfortherequirements
forbreathingqualityair.
RECEIVING, MOVING, AND UNPACKING
A. RECEIVING
Thisshipmenthasbeenthoroughlychecked,packedand
inspectedbeforeleavingourplant.Itwasreceivedin
goodconditionbythecarrierandwassoacknowledged.
CheckforVisibleLossorDamage.Ifthisshipmentshows
evidenceoflossordamageattimeofdeliverytoyou,
insistthatanotationofthislossordamagebemadeon
the delivery receipt by the carrier’s agent.
B. UNPACKING
Checkforconcealedlossordamage.Whenashipment
hasbeendeliveredtoyouinapparentgoodorder,but
concealeddamageisfounduponunpacking,notifythe
carrier immediately and insist on his agent inspecting
the shipment. Concealed damage claims are not our
responsibilityasourtermsareF.O.B.pointofshipment.
C. MOVING
Inmovingortransportingdryer,donottipdryerontoits
side.
D. STORAGE
IMPORTANT:Donotstoredryerintemperaturesabove
130°F (54.4°C).
3
Compressor
Oil Removal
Filter
Aftercooler
Automatic Drain
Dryer
Separator
Receiver
TYPICAL COMPRESSED AIR SYSTEM
INSTALLATION
Ambient Air Temperature
Locatethedryerindoorswheretheambientairtemperature
willbebetween45°Fand110°F.Intermittentoperationat
ambient temperatures up to 113°F will not damage the dryer
but may result in a higher dew point or dryer shutdown
duetohighrefrigerantdischargepressure(seeFieldService
Guide).
Donotoperateair-cooleddryersatambientairtemperatures
below40°F.Suchoperationmayresultinlowsuction
pressure,causingfreeze-up.
Location and Clearance
Mountthedryeronalevelbase.Ifthebasevibrates,bolt
theunitdownusingvibrationdampeners.Ifthedryeris
air-cooled,installitinaclean,well-ventilatedareatoreduce
foulingofthecondensercoilswithdirtanddust.Allowat
least24inchesclearanceonthesidesandthefrontofthe
dryerforcoolingairowandforserviceaccess.
System Arrangement
Liquidwaterintheinletairwilladverselyaffectthe
performanceofthedryer.Installthedryerdownstreamofan
aftercoolerorseparatorsothatthetemperatureofthedryer
inletairdoesnotexceed120°Fandtheinletairdoesnot
contain any liquid water.
Ifthecompressedairowisrelativelyconstantanddoesnot
exceedthedryerowrating,itisrecommendedthatthe
dryerbelocateddownstreamofthereceivertank.Ifthe
natureoftheapplicationissuchthattheairdemandregularly
exceedsthedryerowrating,itisrecommendedthatthe
dryerbelocatedupstreamofthereceiver.
Forsafetyandconvenience,installinletandoutletshutoff
valvesanddepressurizationvalves.Thesevalvesallowthe
dryertobeisolatedanddepressurizedforservicing.Bypass
pipingmaybeinstalledaroundthedryerforuninterrupted
airowwhenthedryerisserviced.Ifthecompressedair
operationcannottolerateundriedairforshortperiods,install
a second dryer in the bypass line.
Compressedairsystemscommonlyrequirelterstoremove
compressoroils,particulates,condensedliquidsandother
contaminants.Whenanoil-removallterisused,itshould
beinstalleddownstreamoftherefrigerateddryer.At
thislocation,thelifeofthereplaceablelterelementis
prolongedsincesomeoftheentrainedoilisremovedbythe
dryer and drained through the separator.
Piping and Connections
Pipingmustbefurnishedbytheuserunlessotherwise
specied.Connectionsandttingsmustberatedforthe
maximumoperatingpressuregivenonthedryerdataplate
andmustbeinaccordancewithapplicablecodes.Support
allpiping;donotallowtheweightofanypipingtostressthe
dryerorlterconnections.Inletandoutletshutoffvalvesand
avalvedbypassvalvearerecommended.Pipingshouldbeat
leastthesizeoftheinletandoutletconnectionstominimize
pressuredropintheairsystem.SeeEngineeringDatasection
fordryerinletandoutletconnections.
Removing Condensate
Condensatemustbedrainedfromthedryertopreventre-
entrainment. The dryers are equipped with automatic drain
valves and internal drain hoses up to the drain connections
on the dryer cabinets. The user must install a separate
dischargelineatthedrainconnectiontocarryoffcondensate
to an environmentally approved condensate collection/
disposalsystem.Pipingorcoppertubing1/2inchorlarger
isrecommendedforcondensatedischargelines.Installthe
drain lines so that condensate can be seen as it drains.
Electrical Connections
ThedryersareconstructedaccordingtoNEMAType1
electrical standards. Field wiring must comply with local and
nationalre,safetyandelectricalcodes.Installationmust
beinaccordancewiththeNationalElectricalCode.Conrm
that your line voltage is the same as the voltage listed on the
dryerdataplate.RefertoFigure1forelectricalschematics.
Operation of dryers with improper line
voltage constitutes abuse and could affect the dryer
warranty.
4
INSTRUMENTATION
ON/OFF Switch
ThedryerisequippedwithanON/OFFswitchonthefront
panel.Alightsignalswhenthedryerison.
Dew Point Indicator
(75 through 150 scfm models)
Alldryersareequippedwithadewpointindicatorwhich
indicatesdryerconditionsasfollows:
Itisnormalforthedewpointindicatortobeintheredzone
whenthedryerisrstturnedonandthenmovetothe
greenzonewhenthedryerreachesitsnormaloperating
temperature.Ifthisindicatorisintheredzoneduring
normaloperation,turnthedryerofftoavoidcompressor
damage.RefertotheFieldServiceGuideforadditional
information,orcallyourlocaldistributor.
Dryer System Monitor (DSM)
(200 through 5000 scfm models)
TheDryerSystemMonitor(DSM)hasLEDtypedewpoint
temperature indicators and electronic drain valve timing
controls.Whenthedryerisrunningnormally,thegreenLEDs
willilluminate.IftheredLEDisilluminated,thereisaneed
forthedryer'soperatingconditiontobechecked.
NOTE:Whenthedryeristurnedon,allLEDswillbe
illuminated.Allow15minutesfortheredandyellowLEDsto
beextinguished.
Theautomaticdrainvalvecontrolsallowtheperiodofdrain
openingtobesetfrom0.5secondsto9secondsanddrain
valveclosedtimetobesetfrom0.5minutesto9minutes.
Whenthe"PUHTOTEST"buttonispushed,thedrainvalve
opensandremainsopenfortheadjusted"open"time.
Automatic Drain Valve
Allmodelsareequippedwithanelectronicdrainvalvethat
automaticallydischargescondensatefromthedryer.Drain
valve operation is controlled by a drain valve timer. The drain
openingcanbesetfrom0.5secondsto9seconds.Thedrain
cyclecanbesetfrom0.5minutesto9minutes.
Models75through150havethetimermounteddirectlyon
thedrainvalve.Formodels200through500,drainvalve
adjustmentsaremadeontheDryerSystemMonitor(DSM).
Electronic Drain Valve Adjustment
Tominimizeairlosses,thedrainvalvecontroltimeshould
beadjustedtoopenthedrainportjustlongenoughto
dischargeaccumulatedcondensate.Setthedrainvalve
operatingtimesothatonlyairdischargesattheendofthe
open period. Recommended initial settings are a 1 to 2
seconddrainopeningand30secondsdrainclosedtime.If
liquidstilldischargesastheportisclosing,setthetimerfora
shorter cycle or a longer opening.
timershouldbeadjustedtoopenthedrainportjustlong
enoughtodischargeaccumulatedcondensate.Setthetimer
sothatonlyairdischargesattheendoftheopenperiod.
Dew Point Indicator
(Models RNP75, RNP100, RNP125 and RNP150)
3 4
2
1
5
Drain Timer
(Models RNP75, RNP100, RNP125 and RNP150)
1. Adjustmentknobforthedrainvalveopentime.The
values on the dial correspond to the time in seconds
that the valve is open in each drain cycle.
2. Adjustmentknobforthedrainvalveclosedtime.The
values on the dial correspond to the time in minutes
that the valve is closed in each drain cycle.
3. LEDtoindicatewhenthedrainvalveisopen.
4. Draintestbutton.Whenthebuttonispressed,the
drainvalveopensforthetimecorrespondingtothe
setting on item 1.
5.LEDtoindicatewhenthedrainvalveisclosed.
5
2
1
10 9 8
7
6
543
Dryer System Monitor
(Models RNP200, RNP250, RNP300, RNP400 and RNP500)
1. On/OffSwitch:Pressthetopoftheswitch(I)toturn
thedryeron.Pressthebottomoftheswitch(O)to
turnthedryeroff.Whenthedryerison,theswitchis
illuminated.
2. ThisisagraphicsymbolfortheAirDryercompressor.
Itsimplyindicatesthattheswitchisusedtoturnthe
compressor(dryer)onandoff.
3. Partofthegraphicforthedewpointtemperature
scale.Thesnowflakeindicatesthelow(cold)endof
the scale.
4. Mainportionofthegraphicforthedewpoint
temperaturescale.Greenindicateslow,orange
indicatesmedium,redindicateshigh.
5. Partofthegraphicforthedewpointtemperature
scale. The thermometer indicates the high (hot) end
ofthescale.
6. Six(6)LEDsthatindicatedewpointtemperature
accordingtothegraphicscaleabovetheLEDs.The
colorofeachLEDmatchesthecoloredbars
7. Adjustmentknobforthedrainvalveopentime.The
values on the dial correspond to the time in seconds
that the valve is open in each drain cycle.
8. Adjustmentknobforthedrainvalveclosedtime.The
values on the dial correspond to the time in minutes
that the valve is closed in each drain cycle.
9. LEDtoindicatewhenthedrainvalveisopen.
10. Draintestbutton.Whenthebuttonispressed,the
drainvalveopensforthetimecorrespondingtothe
settingonitem7.
6
START-UP/OPERATION
Follow the procedure below to start your dryer. Failure
tofollowtheprescribedstart-upprocedurewillinvalidate
thewarranty.Ifproblemsariseduringstart-up,callyour
distributor.
RefertoSerialNumberTagfordryeroperating
capacity.Donotexceedrecommendedcapacity.
Drainconnectionsmustbemadebeforethedryercanbe
operated.Thedryersarefullyautomaticandrequireno
auxiliarycontrols.
1. TurnthedryerON/OFFswitchtoOFF.
2. Checkthatthemainelectricalsupplyvoltagematches
thevoltagespeciedonthedryerdataplate.
3. Checkproperconnectionandsupportofcompressedair
linestothedryer;checkbypassvalvesystem,ifinstalled.
4. SLOWLYpressurizethedryer.Theoutletvalvesofthe
dryershouldbeclosedtopreventowthroughthe
dryer.
5. Turn on the main electrical power to the dryer.
6. Ensureadequateventilationforair-cooleddryers.
To start dryer:
1. Turn the power switch to ON.Therefrigerantcompressor
will turn on.
2. Allowthedryertorun15minutes.Conrmthatthe
temperatureindicatorsareinthegreenzone.
3. SLOWLYopenthedryeroutletvalvespermittingow
through the dryer.
4. Conrmthatcondensateisdischargingfromthedrain
valvebypressingthe"TEST"button.
5. Checkdrainvalvetiming.SeeAUTOMATICDRAINVALVE
sectionfordrainvalveadjustmentprocedure.
6. Conrmthattheinletairtemperature,pressureand
airowtothedryermeetthespeciedrequirements(see
EngineeringDatasection).
7. Conrmthatthecondensatelinesfromthedrainvalve
dischargeintoacollectiontankoranenvironmentally-
approved disposal system.
Thedryerisdesignedtoruncontinuously.Letthedryerrun
evenwhenthedemandforcompressedairisinterrupted;
thedryerwillnotfreezeup.
SHUTDOWN
Whenthedryermustbeshutdownformaintenanceorother
reasons,usethefollowingprocedure.
Ifelectricalrepairsmustbemade:
1. Turnoffthepowerswitch.
2. Disconnectthemainpowersupply.
3. Lockoutandtagthepowersupplyinaccordancewith
OSHArequirements.
Ifmechanicalrepairsaretobemadeorserviceisperformed,
venttheinternalpressureofthedryertoatmospheric
pressure.Restartthedryeraccordingtothestart-up
instructions.
Disconnectpowersupplyanddepressurize
dryerbeforeservicing.Dismantlingorworkingonany
componentofthecompressedairsystemunderpressure
maycauseequipmentfailureandseriouspersonalinjury.
MAINTENANCE
Thedryersrequirelittlemaintenanceforsatisfactory
operation.Gooddryerperformancecanbeexpectedifthe
followingroutinemaintenancestepsaretaken.
Dismantlingorworkingonanycomponent
ofthecompressedairsystemunderpressuremaycause
equipmentfailureandseriouspersonalinjury.Before
dismantlinganypartofthedryerorcompressedairsystem,
completely vent the internal pressure to the atmosphere.
General
Forcontinuedgoodperformanceofyourrefrigerateddryer,
allrefrigerationsystemmaintenanceshouldbeperformedby
acompetentrefrigerationmechanic.
NOTE:Beforecorrectivemaintenanceisdoneduringthe
warrantyperiod,callyourlocaldistributorandproceed
accordingtoinstructions.Refertothewarrantyforlimitsof
your coverage.
Daily Maintenance
Checktheoperationoftheautomaticdrainvalveatleast
oncedaily.SeetheFieldServiceGuideforremediestodrain
valvemalfunctions.SeetheAUTOMATICDRAINVALVE section
fordrainvalveadjustment.
7
Weekly Maintenance
Inspecttheambientairlterweeklyandcleanitifnecessary.
Dirtyairlterscauselossofefciencyandmayresultin
damage to the product.
AirFilter—Cleanaccumulateddustanddirtfromairlter
weeklyasrequired.
1. Openambientltersidedoor.
2. Removeairlterbyslidingupwards.
3. Washwithsoapandwaterandallowtodrybefore
reinstalling.
NOTE:Donotusesolventstocleanlter.
4. Reinstallairlterandrightsidedoor.
5. Ifthelterisdamaged,replaceitwithanewlter.
Contact your distributor.
Donotoperatethedryerwithouttheambient
airlter.Permanentcondenserdamagemayresult.
Monthly Maintenance
Forair-cooledcondensers,itisrecommendedtoinspect
thecondensercoilsmonthly.Ifnecessary,removedirtor
otherparticleswithcompressedairfromanOSHA-approved
airnozzlethatlimitsitsdischargepressureto30psig
(2.1kgf/cm²).
Electronic Drain Valve Disassembly and Servicing
Donotdisassembledrainvalvetimerorattempt
torepairelectricalparts.Replacetimerifdefective.
Thedrainvalvedischargecondensatethroughafull-port
drain opening. The valve body may need to be cleaned under
conditionsofgrossparticulatecontamination.
Todisassemblethedrainvalvebodyforcleaningandother
maintenance:
1. Turnpowerswitchoff.
2. Disconnectmainpowersupplytodryer.
3. Depressurizeunit.
4. LockoutandtagpowersupplyinaccordancewithOSHA
requirements.
Ifpowersupplyisnotconnectedandunitis
notdepressurizedbeforedisassembly,seriouspersonalinjury
and valve damage may result.
5. Removes hoses that connect the drain valve to the drain
valve strainer.
6. Removescrewandwasherfromfrontofthedrainvalve.
7. Removethepowersupplyconnectorandgasket(with
thetimerassemblyifattached)fromthesolenoidcoil
housing.Donotdamageorlosethegasket.
8. Removecoilxingnutandspringwasherfromtopof
solenoid coil housing.
9. Liftsolenoidcoilhousingoffsolenoidcoreinvalvebody.
10. Unscrewsolenoidcorefromvalvebody.
Oncethedrainvalveisdisassembled,thefollowing
maintenancecanbeperformed.
1. Inspectinternalpartsofvalvebody;cleanorreplaceas
required.
NOTE:Replacesolenoidvalveifcomponentdamageis
observed.
2. Removedebrisfromvalvebody.
3. Wipesolenoidcorecomponentswithacleanclothor
blowoutdebriswithcompressedairfromanOSHA-
approvedairnozzlethatlimitsitsdischargepressureto
30 psig.
4. Checkthattheplungerassemblyiscleanandmoves
freelyinhousing.
5. Iftimerisattachedtovalvebody,checkelectrical
continuity across timer assembly.
Toreassemblethedrainvalve,reversethesequence
oftheprecedingsteps.Afterthedrainvalveis
reassembled,connectthemainpowersupplytothe
dryer.Whenthedryerisreturnedtoservice,check
thedrainvalveforairorcondensateleaks;tighten
connectionsasrequiredtocorrectleaks.Checkthedrain
cycle;adjustthetimeraccordingtotheprocedureinthe
drainvalveadjustmentsection.
Returns to Manufacturer
Ifthedryeroracomponentofthedryermustbereturnedto
themanufacturer,rstcallyourlocaldistributorforareturn
authorizationnumberandshippingaddress.Yourdistributor
willinformyouwhetherthedryeroronlyacomponentmust
bereturned.Markthepackagewiththereturnauthorization
numberandshipfreightprepaidasdirectedbyyourlocal
distributor.
8
FIELD SERVICE GUIDE
Problemsmostfrequentlyencounteredwithrefrigerated
dryersarewaterdownstreamofthedryerandexcessive
pressuredrop.Mostcausescanbeidentiedandremedied
byfollowingthisguide.
Closedrefrigerationsystemsarepotentially
dangerous.Workontherefrigerationsystemmustbedone
onlybyacompetentlicensedrefrigerationmechanic.Donot
releaseuorocarbonrefrigerantstotheatmosphere.Donot
dischargeliquidrefrigerantsintooordrains.Refrigerant
vaporsmayaccumulateinlowplaces.Inhalationofhigh
concentrationsmaybefatal.Allrefrigerantsmustbe
recoveredperEPArequirements.
Donotsmokewhenarefrigerationleakissuspected.Burning
materialsmaydecomposerefrigerants,formingatoxicgasor
acidsthatmaycauseseriousinjuryandpropertydamage.
Beforedismantlinganypartofthedryerorcompressed
airsystem,completelyventtheinternalpressuretothe
atmosphere.
PROBLEM SYMPTOM POSSIBLE CAUSE REMEDY
Water Downstream of
Dryer
Refrigerantcompressornot
running.
Lossofpowertodryer Checkpowersupply,fusesand/orbreakers.Check
forlooseconnections.
Dryerturnedoff. CheckOn/Offswitchposition.
Dryeroverloaded. Conrmthatinletow,inlettemperatureandinlet
pressurearewithinacceptablerangeofdryer.
Condenser clogged with debris. Check/cleanambientairlterandcondenser.
Fan motor inoperative Checkfanmotoroperation.Replaceifnecessary.
Ambienttemperaturetoohigh. Verifyambienttemperaturethroughoutday.
Highpressureswitchactivated
(models 200 to 500 only)
Pressmanualresetbuttontoswitchtoresetbutton.
Compressor overheated. Turndryeroff.Contactlocaldistributor.
Compressordefective. Turndryeroff.Contactlocaldistributor.
Nocondensatedischargingfrom
dryer.
Drainstrainerclogged. Clean drain strainer.
Drainvalveinoperative. Check/rebuilddrainvalve.
DraintimerorDSMinoperative. ConrmthereispowertothetimerorDSM.
ReplacetimerorDSM,ifnecessary.
Drainsolenoidinoperative. Conrmthereispowertothecoil.Replacecoil,if
necessary.
Condensatedischargingfromdryer. Incorrectdraintimersetting. Adjustdraintimer-increaseopentimeand/or
decrease closed time.
Liquidwaterenteringdryer. Aftercoolerdrainvalvemalfunction. Check,repairaftercoolerdrainvalve.
Excessive Pressure
Drop Across Dryer
Frozencondensateinevaporator. Incorrecthotgasbypassvalve
setting.
Contact local distributor.
Inletairpressurelow. Upstreamrestrictioninairsystem. Checkallupstreamairsystemcomponents(valves,
regulators,etc.)
Dryerundersized. Excessivecompressedairow. Resizedryer.
Dew Point Indicator
Out of Green Zone
Dryeroverloaded. Conrmthatinletow,inlettemperatureandinlet
pressurearewithinacceptablerangeofdryer.
Condenser clogged with debris. Check/cleanambientairlterandcondenser.
Loosesensorconnection. ConrmgaugeorDSMsensoristightlyconnected
to dryer tubing.
Defectivegauge,DSMorDSM
sensor.
Replacegauge,DSMorDSMsensor.
9
ENGINEERING DATA
MODEL 75 100 125 150 200 250 300 400 500
SPECIFICATIONS
Rated Capacity
a
-(scfm) 75 100 125 150 200 250 300 400 500
Inlet/OutletConnections-(inches) 3/4 1 1 1 1-1/2 1-1/2 1-1/2 2 2
Dimensions
Height-(inches) 20.1 20.6 20.6 20.6 30.0 30.0 29.9 29.9 31.5
Length-(inches) 19.7 28.3 28.3 28.3 35.4 35.4 37.4 37.4 41.3
Width-(inches) 18.9 13 13 13 16.1 16.1 19.3 19.3 23.2
PowerSupply-(V/Ph/Hz) 115/1/60 115/1/60 115/1/60 115/1/60 460/3/60 460/3/60 460/3/60 460/3/60 460/3/60
RefrigerantCompressorCapacity
c
-
(BTU/hr)
3,414 3,953 3,953 5,406 8,787 13,969 13,969 17,574 22,151
InputPower-(kW) 0.72 0.74 0.76 1.11 1.42 1.98 2.05 2.50 3.06
RefrigerantType
b
R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a
a
Rating conditionsare100°Finlettemperature,100psiginletpressure,100%inletrelativehumidity,100°Fambienttemperature@60Hz.PerCAGIADF-100.
b
Refertodryerdataplateforrefrigerantcharge.
c
Compressorcapacity@35°Fevaporatingtemperature,130°Fcondensingtemperature.
MINIMUM - MAXIMUM OPERATING CONDITIONS ALL MODELS
Min.-Max.InletAirPressure(compressedairatinlettodryer) 10-232psig
Min.-Max.InletAirTemperature(compressedairatinlettodryer) 40°F-120°F
Min.-Max.AmbientTemperature 40°F-110°F
NOTE:Continuousoperationintheabovemaximumandminimumoperationconditionsisnotallowable.
SUCTION PRESSURE REFRIGERANT PRESSURE SWITCH SETTINGS
Refrigerant Without Airflow
Models75to500
R-134a 31 psig
Fan Cycle Control
FanPressureSwitchSetting
R-134a
Cut-In Cut-Out
199psig 142 psig
Models200to500
RefrigerantCompressorControl
HighPressureSwitchSetting
SensorLocation
R-134a
Cut-Out Cut-In
CompressorDischarge
298psig
Manual Reset
201 psig
10
ELECTRICAL SCHEMATICS
Figure 1b
100 to 125 scfm models
115V / 1PH / 60Hz
ON/OFF SWITCH
WITH RUNNING LAMP
R
2
5
CS CR
1
3
6
PTC STARTER
F. P. S.
FAN
MOTOR
T
ELECTRONIC AUTO DRAIN VALVE
OVERLOAD
PROTECTOR
COMP.
1PH
S
M
C
Figure 1a
75 scfm models
115V/1PH/60Hz
5
6
ON/OFF SWITCH
WITH RUNNING LAMP
R
2
F. P. S
MS
C
COMP.
1PH
OVERLOAD
PROTECTOR
PTC STARTER
FAN
MOTOR
ELECTRONIC
AUTO DRAIN
VALVE
T
11
ELECTRICAL SCHEMATICS
Figure 1d
200 to 500 scfm models
Figure 1c
150 scfm models
115V/1PH/60Hz
R
ON/OFF SWITCH
WITH RUNNING LAMP
ELECTRONIC
AUTO DRAIN
VALVE
Starting
Capacitor
S
R
COMP.
1~
C
P.R-b
Potential
Relay
FAN
MOTOR
Overload
protector
(OLP)
P. R
T
F. P. S
H.P. S
* FUSE FOR ELECTRO
AUTO DRAIN VALVE
SENSORELECTRO AUTO
DRAIN VALVE
* FUSE
U1
RL1
DSM
SOL
21
21
24
3
F1(2A)
ON/OFF SWITCH
WITH RUNNING LAMP
SRT
0V
R
440V
T
380V
TR 150VA
115V
0V
MC1
11
460V/3Ø/60Hz
F. P. S
31
21
24 24
1
2
3
4
5
6
7
o
o
o
o
o
o
o
R
MC1
REF. COMP.
With internal T.P
M
FAN MOTOR
With internal T.P
12
Figure 2a
75 to 150 scfm models
AIR AND REFRIGERANT FLOW SCHEMATICS
DRAIN VALVE
STRAINER
FAN PRESSURE SWITCH
FILTER/DRYER
REFRIGERANT
COMPRESSOR
CONDENSER
FAN BLADES
& FAN MOTOR
AIR FLOW
CHILLER
(REF TO AIR HEAT EXCHANGER)
REHEATER
(AIR TO AIR HEAT EXCHANGER)
COMPRESSED AIR INLET
COMPRESSED AIR OUTLET
S
MOISTURE SEPARATOR INTEGRATED BRAZED PLATE HEAT EXCHANGER
ELECTRONIC AUTO
DRAIN VALVE WITH TIMER
CAPILLARY TUBE
HOT GAS
BY-PASS VALVE
F. P. S
13
Figure 2b
200 to 500 scfm models
AIR AND REFRIGERANT FLOW SCHEMATICS
DRAIN VALVE
STRAINER
FILTER/DRYER
REFRIGERANT
COMPRESSOR
CONDENSER
FAN BLADES
& FAN MOTOR
AIR FLOW
CHILLER
(REF TO AIR HEAT EXCHANGER)
REHEATER
(AIR TO AIR HEAT EXCHANGER)
COMPRESSED AIR INLET
COMPRESSED AIR OUTLET
S
MOISTURE SEPARATOR INTEGRATED BRAZED PLATE HEAT EXCHANGER
ELECTRONIC AUTO
DRAIN VALVE
HIGH PRESSURE SWITCH
HOT GAS BY-PASS VALVE
CAPILLARY TUBE
FAN PRESSURE SWITCH
H.P. SF. P. S
14
REPLACEMENT PARTS
Item Description 75 scfm 100 scfm 125 scfm 150 scfm
1 RefrigerantCompressor 3149274 3161249 3161249 3161250
2 Condenser(air-cooled 1283269 3161253 3161253 3161254
3 Fan Blades 3041954 3041954 3041954 3041954
4 FanMotor 3161257 3161257 3161257 3161257
5 FilterDryer 3161259 1283273 1283273 1283273
6 SolenoidValveAssembly 3161263 3161263 3161263 3161263
7 SolenoidValveTimer 3161264 3161264 3161264 3161264
8 SolenoidValveStrainer 3161265 3161265 3161265 3161265
9 DINSocket 3161266 3161266 3161266 3161266
10 On/OffSwitchwithRunningLamp 3161244 3161244 3161244 3161244
11 DewPointIndicator 3041493 3041493 3041493 3041493
12 HotGasBypassValve 3161268 3161268 3161269 3161270
13 HeatExchanger 3161275 3161276 3161277 3161277
14 AmbientAirFilter 3161260 3161260 3161260
15 FanPressureSwitch 3161274 3161274 3161274 3161274
16 MaintenanceKits RNPJMK3 RNPJMK3 RNPJMK3 RNPJMK3
Item Description 200 scfm 250 scfm 300 scfm 400 scfm 500 scfm
1 RefrigerantCompressor 3161251 3093041 3137014 3090708 3161242
2 Condenser(air-cooled) 3161255 3161255 3161256 3161256 3161245
3 Fan Blades 3041955 3041955 3041957 3041957 3041957
4 FanMotor 5000011 5000011 5000011 5000011 5000011
5 FilterDryer 1283273 1283273 1283369 1283369 1283369
6 SolenoidValveAssembly 3161248 3161248 3161248 3161248 3161248
7 SolenoidValveTimer
8 SolenoidValveStrainer 3146976 3146976 3146976 3146976 3146976
9 DINSocket 3161267 3161267 3161267 3161267 3161267
10 On/OffSwitchwithRunningLamp 3161244 3161244 3161244 3161244 3161244
11 DryerSystemMonitor(DSM) 3161282 3161282 3161282 3161282 3161282
12 HotGasBypassValve 3161271 3161271 3161271 3161272 3161272
13 HeatExchanger 3161278 3161279 3161280 3161281 3161246
14 AmbientAirFilter 3161261 3161261 3161262 3161262 3161247
15 FanPressureSwitch 3161274 3161274 3161274 3161274 3161274
16 HighPressureSwitch 3161273 3161273 3161273 3161273 3161273
17 MaintenanceKits RNPJMK4 RNPJMK4 RNPJMK5 RNPJMK5 RNPJMK6
15
AUTHORIZATION FROM THE SERVICE DEPARTMENT IS NECESSARY BEFORE MATERIAL IS
RETURNED TO THE FACTORY OR IN-WARRANTY REPAIRS ARE MADE.
WARRANTY
Themanufacturerwarrantstheproductmanufacturedbyit,whenproperlyinstalled,operated,applied,andmaintainedinaccordancewithproce-
duresandrecommendationsoutlinedinmanufacturer’sinstructionmanuals,tobefreefromdefectsinmaterialorworkmanshipforaperiodas
speciedbelow,providedsuchdefectisdiscoveredandbroughttothemanufacturer’sattentionwithintheaforesaidwarrantyperiod.
Themanufacturerwillrepairorreplaceanyproductorpartdeterminedtobedefectivebythemanufacturerwithinthewarrantyperiod,provided
suchdefectoccurredinnormalserviceandnotasaresultofmisuse,abuse,neglectoraccident.Normalmaintenanceitemsrequiringroutinereplace-
mentarenotwarranted.Thewarrantycoverspartsandlaborforthewarrantyperiodunlessotherwisespecied.Repairorreplacementshallbemade
atthefactoryortheinstallationsite,atthesoleoptionofthemanufacturer.Anyserviceperformedontheproductbyanyoneotherthanthemanu-
facturermustrstbeauthorizedbythemanufacturer.
Unauthorizedservicevoidsthewarrantyandanyresultingchargeorsubsequentclaimwillnotbepaid.Productsrepairedorreplacedunderwarranty
shallbewarrantedfortheunexpiredportionofthewarrantyapplyingtotheoriginalproduct.
Theforegoingistheexclusiveremedyofanybuyerofthemanufacturer’sproduct.Themaximumdamagesliabilityofthemanufactureristheoriginal
purchasepriceoftheproductorpart.
THEFOREGOINGWARRANTYISEXCLUSIVEANDINLIEUOFALLOTHERWARRANTIES,WHETHERWRITTEN,ORAL,ORSTATUTORY,ANDISEXPRESSLYINLIEU
OFTHEIMPLIEDWARRANTYOFMERCHANTABILITYANDTHEIMPLIEDWARRANTYOFFITNESSFORAPARTICULARPURPOSE.THEMANUFACTURERSHALL
NOTBELIABLEFORLOSSORDAMAGEBYREASONOFSTRICTLIABILITYINTORTORITSNEGLIGENCEINWHATEVERMANNERINCLUDINGDESIGN,MANUFAC-
TUREORINSPECTIONOFTHEEQUIPMENTORITSFAILURETODISCOVER,REPORT,REPAIR,ORMODIFYLATENTDEFECTSINHERENTTHEREIN.
THEMANUFACTURER,HISREPRESENTATIVEORDISTRIBUTORSHALLNOTBELIABLEFORLOSSOFUSEOFTHEPRODUCTOROTHERINCIDENTALORCONSE-
QUENTIALCOSTS,EXPENSES,ORDAMAGESINCURREDBYTHEBUYER,WHETHERARISINGFROMBREACHOFWARRANTY,NEGLIGENCEORSTRICTLIABILITY
INTORT.
Themanufacturerdoesnotwarrantanyproduct,part,material,component,oraccessorymanufacturedbyothersandsoldorsuppliedinconnection
withthesaleofmanufacturer’sproducts.
Warranty Period
Partsandlaborfortwo(2)yearsfromthedateofshipmentfromthefactory;heatexchangersarecovered(partsonly)foranadditionalthree(3)
years(totalofve[5]).Onunitsthatmanufacturerrequestsbereturnedtothefactory,aonetimeremoval/reinstallationlaborallowanceasnotedin
theServiceWarrantyPoliciesandProceduresHandbookwillapply.Freighttothefactoryfromtheinstallationsiteandtotheinstallationsitefromthe
factorywillbepaidbythemanufacturer;meansoftransportationtobespeciedbymanufacturer.
SERVICE DEPARTMENT: (724) 746-1100
Curtis-Toledo, Inc.
1905 Kienlen Avenue, St. Louis Missouri 63133
phone: 314-383-1300 fax: 314-381-1439 email: [email protected]
WWW.FSCURTIS.COM
/