Altronix T2MK3F4 Installation guide

Category
Security device components
Type
Installation guide

Altronix T2MK3F4 is a fully assembled kit designed to provide power and access control in various security applications. It includes an eFlow6NB Power Supply/Charger, an ACM4 Fused Access Power Controller, a VR6 Voltage Regulator, and a PDS8 Dual Input Power Distribution Module. This kit offers protection to support up to four doors and features fail-safe or fail-secure outputs and dry form "C" outputs. The Altronix T2MK3F4 is suitable for indoor use and comes with a comprehensive installation guide.

Altronix T2MK3F4 is a fully assembled kit designed to provide power and access control in various security applications. It includes an eFlow6NB Power Supply/Charger, an ACM4 Fused Access Power Controller, a VR6 Voltage Regulator, and a PDS8 Dual Input Power Distribution Module. This kit offers protection to support up to four doors and features fail-safe or fail-secure outputs and dry form "C" outputs. The Altronix T2MK3F4 is suitable for indoor use and comes with a comprehensive installation guide.

4 Door Kits:
T2MK3F4
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) ACM4 - Fused Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
T2MK3F4Q
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM4 - Fused Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
8 Door Kits:
T2MK3F8
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) ACM8 - Fused Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
T2MK3F8Q
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM8 - Fused Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
T2MK7F8
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow104NB - Power Supply/Charger
- (1) ACM8 - Fused Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
T2MK7F8Q
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow104NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM8 - Fused Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
16 Door Kits:
T2MK75F16
Fully assembled kit includes:
- Trove2 enclosure with TM2 Altronix/Mercury
backplane and TMV2 door backplane
- (1) eFlow104NB and (1) eFlow102NB -
Power Supply/Chargers
- (2) ACM8 - Fused Access Power Controllers
- (1) PD16W - Power Distribution Module
T2MK75F16Q
Fully assembled kit includes:
- Trove2 enclosure with TM2 Altronix/Mercury
backplane and TMV2 door backplane
- (1) eFlow104NB and (1) eFlow102NB -
Power Supply/Chargers
- (1) LINQ2 - Network Communications Module
- (2) ACM8 - Fused Access Power Controllers
- (1) PD16W - Power Distribution Module
T2MK77F16
Fully assembled kit includes:
- Trove2 enclosure with TM2 Altronix/Mercury
backplane and TMV2 door backplane
- (2) eFlow104NB - Power Supply/Chargers
- (2) ACM8 - Fused Access Power Controllers
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
T2MK77F16Q
Fully assembled kit includes:
- Trove2 enclosure with TM2 Altronix/Mercury
backplane and TMV2 door backplane
- (2) eFlow104NB - Power Supply/Chargers
- (1) LINQ2 - Network Communications Module
- (2) ACM8 - Fused Access Power Controllers
- (1) VR6 - Voltage Regulator
- (1) PDS8 - Dual Input Power Distribution Module
Rev. TMK051217
Installing Company: _________________________ Service Rep. Name: __________________________________________
Address: _________________________________________________________ Phone #: _________________________
All registered trademarks are property of their respective owners. More than just power.™
Installation Guide
Access & Power Integration
Altronix Trove2/Mercury Kits with Fused Outputs
All components of these Trove kits are UL Listed sub-assemblies.
Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
- 2 - Trove2/Mercury Fused Kits Installation Guide
Overview:
Altronix Trove Mercury kits are pre-assembled and consist of Trove2M2 enclosure/backplane with factory installed Altronix power supply/charger(s) and sub-
assemblies. These kits also accommodate various combinations of Mercury boards for up to sixteen (16) doors in a single enclosure.
Configuration Chart:
Altronix
Model Number
Networkable
120VAC 60Hz
Input Current (A)
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
Nominal DC Output Voltage
Maximum Supply
Current for Main and
Aux. Outputs on Power
Supply board and
ACM4/ACM8 Access
Power Controller’s
outputs
Fail-Safe/Fail-Secure or
Dry Form “C” Outputs
Current Per
ACM4/ACM8 Output (A)
ACM4/ACM8 Board
Input Fuse Rating
ACM4/ACM8 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
PDS8 Board
Output Fuse Rating
PD8UL/PD16W Board
Output Fuse Rating
Power Supply
1
Power Supply
2
[DC] [Aux] [DC] [Aux]
Output Range
(VDC)
Output Range
(VDC)
Output Range
(VDC)
Output Range
(VDC)
T2MK3F4 – 3.5 5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4 – – 24VDC @ 5.8A 4 2.5 10A/
250V
3A/
250V
10A/
250V
3A/
250V
T2MK3F4Q P3.5 5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4 – – 24VDC @ 5.8A 4 2.5 10A/
250V
3A/
250V
10A/
250V
3A/
250V
T2MK3F8 – 3.5 5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4 – – 24VDC @ 5.8A 8 2.5 10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
T2MK3F8Q P3.5 5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4 – – 24VDC @ 5.8A 8 2.5 10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
T2MK7F8 4.5 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4 – – 24VDC @ 9.2A 8 2.5 10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
T2MK7F8Q P4.5 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4 – – 24VDC @ 9.2A 8 2.5 10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
T2MK75F16 – 8
6.3A/
250V 15A/
32V
20.17-
26.4
20.28-
26.4
9.7-
13.2
10.03-
13.2
12VDC @ 9.3A
24VDC @ 9.2A 16 2.5 10A/
250V
2.5A/
250V 3.5A/
250V
5A/
250V
T2MK75F16Q P8
6.3A/
250V 15A/
32V
20.17-
26.4
20.28-
26.4
9.7-
13.2
10.03-
13.2
12VDC @ 9.3A
24VDC @ 9.2A 16 2.5 10A/
250V
2.5A/
250V 3.5A/
250V
5A/
250V
T2MK77F16 9 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
20.17-
26.4
20.28-
26.4 24VDC @ 9.2A 16 2.5 10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
T2MK77F16Q P96.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
20.17-
26.4
20.28-
26.4 24VDC @ 9.2A 16 2.5 10A/
250V
2.5A/
250V
10A/
250V
3A/
250V
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane(s) from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners
and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper
screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes
and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three
lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite
hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side
(Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed
reporting device. To activate alarm signal open the door of the enclosure.
4. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB, eFlow102NB, eFlow104NB and
Sub-Assembly Installation Guide for the following models: ACM4, ACM8, LINQ2, PDS8, VR6 for further
installation instructions.
5. Fasten snap on spacers onto metal pems configuration of backplane depending on the Mercury access controller
(Fig. 2-5, pg. 3-6).
6. Position Mercury access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2-5, pg. 3-6).
7. Mount backplane to enclosure with hardware.
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Trove2/Mercury Fused Kits Installation Guide - 3 -
T2MK3F4, T2MK3F4Q, T2MK3F8, T2MK3F8Q: Configuration of Mercury Boards:
1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 2, pg. 3).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2a, pg. 3).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
EP1501, MR51e C
MR50 D
Fig. 2
B
B
AB
CC
C
C
C
D
D
B
A
A
A
Altronix LINQ2 Module (T2MK3F4Q, T2MK3F8Q)
NC C NO NC C NO
AC FAIL BAT FAIL
TRIGGER
AC DCAC1
EOLNOGND
SUPERVISED RESET
+AUX-
- BAT +- DC +
L G N
OFF - 24V
ON - 12V
ON
Altronix - eFlow6NB
Altronix ACM4
(T2MK3F4, T2MK3F4Q)
+ INP1 --
PWR1 +
PWR1 +
OFF
IN1
IN2
Out1
<1 off 2>
PWR2 +PWR2 +
COM ---
+ INP2 --
IN2 Fuse
IN1 Fuse
Common Power Outputs (NEG)
N
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
1 2 3 4 5 6 7 8
10
10
3
3
3333 33
Out2
<1 off 2>
Out3
<1 off 2>
Out4
<1 off 2>
Out5
<1 off 2>
Out6
<1 off 2>
Out7
<1 off 2>
Out8
<1 off 2>
Altronix - PDS8
Altronix VR6 is mounted under PDS8
TRG
TRIGGER
INPUT
ACM4
ACCESS POWER
CONTROLLER
LED1 LED2 LED3 LED4
MAIN
OUTPUT 1
NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 2 OUTPUT 3
IN GND
1
IN GND
2
IN GND
3
IN GND
4
OUTPUT 4
-- +
CONTROL
-- +
POWER
+INP- T +RET-
INTERFACE
NO C NC
FACP
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix ACM8
(T2MK3F8, T2MK3F8Q)
Snap On
Spacer
Mercury Board
Backplane
Pem
Fig. 2a
- 4 - Trove2/Mercury Fused Kits Installation Guide
T2MK7F8, T2MK7F8Q: Configuration of Mercury Boards:
1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 3, pg. 4).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 3a, pg. 4).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
EP1501, MR51e C
MR50 D
Fig. 3
B
B
AB
CC
C
C
C
D
D
B
A
A
A
Altronix LINQ2 Module (T2MK3F8Q)
NC C NO NC C NO
AC FAIL BAT FAIL
TRIGGER
AC DCAC1
EOLNOGND
SUPERVISED RESET
+AUX-
- BAT +- DC +
L G N
OFF - 24V
ON - 12V
ON
Altronix - eFlow104NB
+ INP1 --
PWR1 +
PWR1 +
OFF
IN1
IN2
Out1
<1 off 2>
PWR2 +PWR2 +
COM ---
+ INP2 --
IN2 Fuse
IN1 Fuse
Common Power Outputs (NEG)
N
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
1 2 3 4 5 6 7 8
10
10
3
3
3333 33
Out2
<1 off 2>
Out3
<1 off 2>
Out4
<1 off 2>
Out5
<1 off 2>
Out6
<1 off 2>
Out7
<1 off 2>
Out8
<1 off 2>
Altronix - PDS8
Altronix VR6 is mounted under PDS8
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix - ACM8
Snap On
Spacer
Mercury Board
Backplane
Pem
Fig. 3a
Trove2/Mercury Fused Kits Installation Guide - 5 -
T2MK75F16, T2MK75F16Q: Configuration of Mercury Boards:
1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 4, pg. 5).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 4a, pg. 5).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
EP1501, MR51e C
MR50 D
Fig. 4
B
C
C
C
D
D
B A
A
Altronix LINQ2 Module (T2MK75F16Q, T2MK75F16DQ)
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix - ACM8
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix - ACM8
Altronix - eFlow104NB
– DC +– BAT +
L G N
NC C NO NC C NO
AC FAIL BAT FAIL
TRIGGER EOL
SUPERVISED
AC DCAC1 NO GND
RESET + AUX -
--- BAT +
Altronix - eFlow102NB
L G N
1 min enable
2 hr disable
--- DC +
N
Altronix - PD16W
XFMR INPUT SP
P N
1 2 3 4 5 6 7 89 10 11 12 13 14 15 16
PROTECTED
OUTPUTS
COMMON
OUTPUTS
P
N
Snap On
Spacer
Mercury Board
Backplane
Pem
Fig. 4a
- 6 - Trove2/Mercury Fused Kits Installation Guide
T2MK77F16, T2MK77F16Q: Configuration of Mercury Boards:
1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 5, pg. 6).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 5a, pg. 6).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
EP1501, MR51e C
MR50 D
Fig. 5
B
C
C
C
D
D
B A
A
Altronix LINQ2 Module (T2MK77F16Q, T2MK77F16DQ)
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix - ACM8
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix - ACM8
Altronix - eFlow104NB
– DC +– BAT +
L G N
Altronix - eFlow104NB
– DC +– BAT +
L G N
+ INP1 --
PWR1 +
PWR1 +
OFF
IN1
IN2
Out1
<1 off 2>
PWR2 +PWR2 +
COM ---
+ INP2 --
IN2 Fuse
IN1 Fuse
Common Power Outputs (NEG)
N
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
1 2 3 4 5 6 7 8
10
10
3
3
3333 33
Out2
<1 off 2>
Out3
<1 off 2>
Out4
<1 off 2>
Out5
<1 off 2>
Out6
<1 off 2>
Out7
<1 off 2>
Out8
<1 off 2>
Altronix - PDS8
Altronix VR6 is mounted under PDS8
Snap On
Spacer
Mercury Board
Backplane
Pem
Fig. 5a
Trove2/Mercury Fused Kits Installation Guide - 7 -
Snap on
Spacer
Nylon
Spacer
Sub-Assembly
Backplane
Pem
A
A
A
A
A
A
B
B
B
B
B
B
C
C
C
TMV2 (T2MK75F16, T2MK75F16Q, T2MK77F16, and T2MK77F16Q):
TMV2 accommodates a variety of Mercury boards with or without Altronix sub-assemblies for access systems.
Configuration of Mercury and/or Altronix Boards
Mercury Access Controllers:
1. Fasten spacers onto metal pems configuration (A) (B) of backplane depending on the access controller (Fig. 6, pg. 7).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 6a, pg. 7).
3. Mount backplane to enclosure with hardware.
Altronix Sub-Assemblies and/or Adapters:
1. Fasten spacers to pems which match the hole pattern (C) for Altronix Sub-Assemblies (Fig. 6, 6a, pg. 7).
2. Mount boards to spacers utilizing pan head screws provided with the product (Fig. 6, pg. 7).
Access Controller Position Chart for the Following Models:
Mercury
Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
Altronix
Sub-Assembly or Adapter Pem Mounting
ACM4(CB), MOM5, PD4UL(CB), PD8UL(CB), PDS8(CB), VR6, GB1 (Genetec Synergis Cloud Link adapter plate) C
Fig. 6
Fig. 6a
- 8 - Trove2/Mercury Fused Kits Installation Guide
Enclosure Dimensions (H x W x D approximate):
27.25” x 21.5” x 6.5” (692.2mm x 552.5mm x 165.1mm)
6.75” (171.5mm)8.25” (209.5mm)
8.00” (203.2mm)
2.00” (50.8mm)
2.00” (50.8mm)
1.25” (31.8mm)
1.25” (31.8mm)
5.25” (133.4mm) 5.25” (133.4mm)7.00” (177.8mm)
1.25” (31.8mm)
6.25” (158.8mm) 19.80” (502.9mm)
1.00” (25.4mm)
27” (685.8mm)
1.5”
(38.1mm)
2.00” (50.8mm) 2.00” (50.8mm)
3.5”(88.9mm) 3.5”(88.9mm)
21.50” (546.1mm)
5.25” (133.35mm) 5.25” (133.35mm)
6.25” (158.8mm)
1.25”
(31.8mm)
0.85” (21.6mm)
0.5625” (14.3mm)
2.415” (61.3mm)
0.685” (17.4mm)
1.77”
(45mm)
0.885” (22.5mm)
1.125” (28.3mm)
Knockouts
2.00” (50.8mm) 2.00” (50.8mm)
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
web site: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IITrove2/Mercury Fused Kits I30U
MEMBER
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Altronix T2MK3F4 Installation guide

Category
Security device components
Type
Installation guide

Altronix T2MK3F4 is a fully assembled kit designed to provide power and access control in various security applications. It includes an eFlow6NB Power Supply/Charger, an ACM4 Fused Access Power Controller, a VR6 Voltage Regulator, and a PDS8 Dual Input Power Distribution Module. This kit offers protection to support up to four doors and features fail-safe or fail-secure outputs and dry form "C" outputs. The Altronix T2MK3F4 is suitable for indoor use and comes with a comprehensive installation guide.