Altronix T2MK3F4D User manual

Category
Security device components
Type
User manual

Altronix T2MK3F4D is a fully assembled kit that includes a Trove2 enclosure with TM2 Altronix/Mercury backplane, eFlow6NB Power Supply/Charger, ACM4CB PTC Access Power Controller, VR6 Voltage Regulator, and PDS8CB Dual Input PTC Power Distribution Module. This kit is ideal for access control applications requiring up to four doors and provides a reliable and efficient power solution for various Mercury boards.

Altronix T2MK3F4D is a fully assembled kit that includes a Trove2 enclosure with TM2 Altronix/Mercury backplane, eFlow6NB Power Supply/Charger, ACM4CB PTC Access Power Controller, VR6 Voltage Regulator, and PDS8CB Dual Input PTC Power Distribution Module. This kit is ideal for access control applications requiring up to four doors and provides a reliable and efficient power solution for various Mercury boards.

4 Door Kits:
T2MK3F4D
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) ACM4CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input PTC
Power Distribution Module
T2MK3F4DQ
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM4CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input PTC
Power Distribution Module
8 Door Kits:
T2MK3F8D
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) ACM8CB - PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input PTC
Power Distribution Module
T2MK3F8DQ
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow6NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM8CB- PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input PTC
Power Distribution Module
T2MK7F8D
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow104NB - Power Supply/Charger
- (1) ACM8CB- PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input PTC
Power Distribution Module
T2MK7F8DQ
Fully assembled kit includes:
- Trove2 enclosure with
TM2 Altronix/Mercury backplane
- (1) eFlow104NB - Power Supply/Charger
- (1) LINQ2 - Network Communications Module
- (1) ACM8CB- PTC Access Power Controller
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input PTC
Power Distribution Module
16 Door Kits:
T2MK75F16D
Fully assembled kit includes:
- Trove2 enclosure with TM2 Altronix/Mercury
backplane and TMV2 door backplane
- (1) eFlow104NB and (1) eFlow102NB -
Power Supply/Chargers
- (2) ACM8CB - PTC Access Power Controllers
- (1) PD16WCB - PTC Power Distribution Module
T2MK75F16DQ
Fully assembled kit includes:
- Trove2 enclosure with TM2 Altronix/Mercury
backplane and TMV2 door backplane
- (1) eFlow104NB and (1) eFlow102NB -
Power Supply/Chargers
- (1) LINQ2 - Network Communications Module
- (2) ACM8CB - PTC Access Power Controllers
- (1) PD16WCB - PTC Power Distribution Module
T2MK77F16D
Fully assembled kit includes:
- Trove2 enclosure with TM2 Altronix/Mercury
backplane and TMV2 door backplane
- (2) eFlow104NB - Power Supply/Chargers
- (2) ACM8CB - PTC Access Power Controllers
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input PTC
Power Distribution Module
T2MK77F16DQ
Fully assembled kit includes:
- Trove2 enclosure with TM2 Altronix/Mercury
backplane and TMV2 door backplane
- (2) eFlow104NB - Power Supply/Chargers
- (1) LINQ2 - Network Communications Module
- (2) ACM8CB - PTC Access Power Controllers
- (1) VR6 - Voltage Regulator
- (1) PDS8CB - Dual Input PTC
Power Distribution Module
Rev. TMKD060117
Installing Company: _________________________ Service Rep. Name: __________________________________________
Address: _________________________________________________________ Phone #: _________________________
All registered trademarks are property of their respective owners. More than just power.™
Installation Guide
Access & Power Integration
Altronix Trove2/Mercury Kits with PTC Outputs
All components of these Trove kits are UL Listed sub-assemblies.
Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
- 2 - Trove2/Mercury PTC Kits Installation Guide
Overview:
Altronix Trove Mercury kits are pre-assembled and consist of Trove2M2 enclosure with factory installed Altronix power supply/charger(s) and sub-assemblies.
These kits also accommodate various combinations of Mercury boards for up to sixteen (16) doors in a single enclosure.
Configuration Chart:
Altronix
Model Number
Networkable
120VAC 60Hz
Input Current (A)
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
Nominal DC Output Voltage
Maximum Supply
Current for Main
and Aux. Outputs
on Power Supply
board and ACM4CB/
ACM8CB Access Power
Controller’s
outputs
Fail-Safe/Fail-Secure
Auto-Resettable Outputs
Current Per ACM4CB/ACM8CB
Output (A)
ACM4CB/ACM8CB
Board Input Fuse Rating
ACM4CB/ACM8CB Board
Output PTC Rating
PDS8CB Board
Input Fuse Rating
PDS8CB Board
Output PTC Rating
PD8ULCB/PD16WCB
Board Output PTC Rating
Power Supply
1
Power Supply
2
[DC] [Aux] [DC] [Aux]
Output Range
(VDC)
Output Range
(VDC)
Output Range
(VDC)
Output Range
(VDC)
T2MK3F4D – 3.5 5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4 – – 24VDC @ 5.8A 4 2.0 10A/
250V 2A 10A/
250V 2A –
T2MK3F4DQ P3.5 5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4 – – 24VDC @ 5.8A 4 2.0 10A/
250V 2A 10A/
250V 2A –
T2MK3F8D – 3.5 5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4 – – 24VDC @ 5.8A 8 2.0 10A/
250V 2A 10A/
250V 2A –
T2MK3F8DQ P3.5 5A/
250V
10A/
32V
20.19-
26.4
20.19-
26.4 – – 24VDC @ 5.8A 8 2.0 10A/
250V 2A 10A/
250V 2A –
T2MK7F8D 4.5 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4 – – 24VDC @ 9.2A 8 2.0 10A/
250V 2A 10A/
250V 2A –
T2MK7F8DQ P4.5 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4 – – 24VDC @ 9.2A 8 2.0 10A/
250V 2A 10A/
250V 2A –
T2MK75F16D – 8
6.3A/
250V 15A/
32V
20.17-
26.4
20.28-
26.4
9.7-
13.2
10.03-
13.2
12VDC @ 9.3A
24VDC @ 9.2A 16 2.0 10A/
250V 2A – – 2A
5A/
250V
T2MK75F16DQ P8
6.3A/
250V 15A/
32V
20.17-
26.4
20.28-
26.4
9.7-
13.2
10.03-
13.2
12VDC @ 9.3A
24VDC @ 9.2A 16 2.0 10A/
250V 2A – – 2A
5A/
250V
T2MK77F16D 9 6.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
20.17-
26.4
20.28-
26.4 24VDC @ 9.2A 16 2.0 10A/
250V 2A 10A/
250V 2A –
T2MK77F16DQ P96.3A/
250V
15A/
32V
20.17-
26.4
20.28-
26.4
20.17-
26.4
20.28-
26.4 24VDC @ 9.2A 16 2.0 10A/
250V 2A 10A/
250V 2A –
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product
is intended for indoor use only.
1. Remove backplane(s) from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners
and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper
screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes
and install the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three
lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location, opposite
hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side
(Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed
reporting device. To activate alarm signal open the door of the enclosure.
4. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB, eFlow102NB, eFlow104NB and
Sub-Assembly Installation Guide for the following models: ACM4CB, ACM8CB, LINQ2, PDS8CB, VR6 for
further installation instructions.
5. Fasten snap on spacers onto metal pems configuration of backplane depending on the Mercury access controller
(Fig. 2-5, pg. 3-6).
6. Position Mercury access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2-5, pg. 3-6).
7. Mount backplane to enclosure with hardware.
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Trove2/Mercury PTC Kits Installation Guide - 3 -
T2MK3F4D, T2MK3F4DQ, T2MK3F8D, T2MK3F8DQ: Configuration of Mercury Boards:
1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 2, pg. 3).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2a, pg. 3).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
EP1501, MR51e C
MR50 D
Fig. 2
B
B
AB
CC
CC
C
D
D
B
A
A
A
Altronix LINQ2 Module (T2MK3F4DQ, T2MK3F8DQ)
NC C NO NC C NO
AC FAIL BAT FAIL
TRIGGER
AC DCAC1
EOLNOGND
SUPERVISED RESET +AUX-
- BAT +- DC +
L G N
OFF - 24V
ON - 12V
ON
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
TRG
TRIGGER
INPUT
ACM4
ACCESS POWER
CONTROLLER
LED1 LED2 LED3 LED4
MAIN
OUTPUT 1
NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 2 OUTPUT 3
IN GND
1
IN GND
2
IN GND
3
IN GND
4
OUTPUT 4
-- +
CONTROL
-- +
POWER
+INP- T +RET-
INTERFACE
NO C NC
FACP
+ INP1 --
DM1 +OFF
IN1
IN2
Out1
<1 off 2>
DM1 +
DM2 +
DM2 +
Common (--- )
Common (--- )
+ INP2 --
IN2 Fuse
IN1 Fuse
Common Power Outputs (NEG)
N
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
1 2 3 4 5 6 7 8
Out2
<1 off 2>
Out3
<1 off 2>
Out4
<1 off 2>
Out5
<1 off 2>
Out6
<1 off 2>
Out7
<1 off 2>
Out8
<1 off 2>
Altronix - eFlow6NB
Altronix ACM4CB
(T2MK3F4D, T2MK3F4DQ)
Altronix ACM8CB
(T2MK3F8D, T2MK3F8DQ)
Altronix - PDS8CB
Altronix VR6 is mounted under PDS8CB
Snap On
Spacer
Mercury Board
Backplane
Pem
Fig. 2a
- 4 - Trove2/Mercury PTC Kits Installation Guide
T2MK7F8D, T2MK7F8Q: Configuration of Mercury Boards:
1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 3, pg. 4).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 3a, pg. 4).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
EP1501, MR51e C
MR50 D
Fig. 3
Altronix - eFlow104NB
– DC +– BAT +
L G N
Altronix VR6 is mounted under PDS8CB
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix PDS8CB
+ INP1 --
DM1 +OFF
IN1
IN2
Out1
<1 off 2>
DM1 +
DM2 +
DM2 +
Common (--- )
Common (--- )
+ INP2 --
IN2 Fuse
IN1 Fuse
Common Power Outputs (NEG)
N
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
1 2 3 4 5 6 7 8
Out2
<1 off 2>
Out3
<1 off 2>
Out4
<1 off 2>
Out5
<1 off 2>
Out6
<1 off 2>
Out7
<1 off 2>
Out8
<1 off 2>
Altronix - ACM8CB
Altronix LINQ2 Module (T2MK7F8DQ)
B
B
AB
CC
CC
C
D
D
B
A
A
A
Snap On
Spacer
Mercury Board
Backplane
Pem
Fig. 3a
Trove2/Mercury PTC Kits Installation Guide - 5 -
T2MK75F16D, T2MK75F16DQ: Configuration of Mercury Boards:
1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 4, pg. 5).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 4a, pg. 5).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
EP1501, MR51e C
MR50 D
Fig. 4
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix - ACM8CB
Altronix - ACM8CB
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix PD16WCB
N
XFMR INPUT SP
P N
1 2 3 4 5 6 7 89 10 11 12 13 14 15 16
PROTECTED
OUTPUTS
COMMON
OUTPUTS
P
N
Altronix - eFlow104NB
– DC +– BAT +
L G N
NC C NO NC C NO
AC FAIL BAT FAIL
TRIGGER EOL
SUPERVISED
AC DCAC1 NO GND
RESET + AUX -
--- BAT +
Altronix - eFlow102NB
L G N
1 min enable
2 hr disable
--- DC +
Altronix LINQ2 Module (T2MK75F16DQ)
B
CC
C
D
D
B A
A
Snap On
Spacer
Mercury Board
Backplane
Pem
Fig. 4a
- 6 - Trove2/Mercury PTC Kits Installation Guide
T2MK77F16D, T2MK77F16DQ: Configuration of Mercury Boards:
1. Fasten snap on spacers onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 5, pg. 6).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 5a, pg. 6).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
EP1501, MR51e C
MR50 D
Fig. 5
Altronix - eFlow104NB
– DC +– BAT +
L G N
– DC +– BAT +
L G N
Altronix - eFlow104NB
Altronix VR6 is mounted under PDS8CB
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM
IN GND IN GND IN GND IN GNDIN GND IN GND IN GND IN GND
1 2 3 4 5 6 7 8
INPUT
TRIGGER
10A 250V
+INP- T + RET-
NO C NC
FACP INTERFACE
Power Control
- + - +
F1 F2 F3 F4 F5 F6 F7 F8
MAIN
TRG
FACP
1 2 3 4
1 2 3 4
ON
ON
1 2 3 4
1 2 3 4
ON
ON
Altronix PDS8CB
+ INP1 --
DM1 +OFF
IN1
IN2
Out1
<1 off 2>
DM1 +
DM2 +
DM2 +
Common (--- )
Common (--- )
+ INP2 --
IN2 Fuse
IN1 Fuse
Common Power Outputs (NEG)
N
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
1 2 3 4 5 6 7 8
Out2
<1 off 2>
Out3
<1 off 2>
Out4
<1 off 2>
Out5
<1 off 2>
Out6
<1 off 2>
Out7
<1 off 2>
Out8
<1 off 2>
Altronix LINQ2 Module (T2MK77F16DQ)
Altronix - ACM8CB
Altronix - ACM8CB
B
CC
C
D
D
B A
A
Snap On
Spacer
Mercury Board
Backplane
Pem
Fig. 5a
Trove2/Mercury PTC Kits Installation Guide - 7 -
Snap on
Spacer
Nylon
Spacer
Sub-Assembly
Backplane
Pem
A
A
A
A
A
A
B
B
B
B
B
B
C
C
C
TMV2 (T2MK75F16D, T2MK75F16DQ, T2MK77F16D, and T2MK77F16DQ):
TMV2 accommodates a variety of Mercury boards with or without Altronix sub-assemblies for access systems.
Configuration of Mercury and/or Altronix Boards
Mercury Access Controllers:
1. Fasten spacers onto metal pems configuration (A) (B) of backplane depending on the access controller (Fig. 6, pg. 7).
2. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 6a, pg. 7).
3. Mount backplane to enclosure with hardware.
Altronix Sub-Assemblies and/or Adapters:
1. Fasten spacers to pems which match the hole pattern (C) for Altronix Sub-Assemblies (Fig. 6, 6a, pg. 7).
2. Mount boards to spacers utilizing pan head screws provided with the product (Fig. 6, pg. 7).
Access Controller Position Chart for the Following Models:
Mercury
Access Controller Pem Mounting
EP1502, MR52, MR16IN, MR16OUT A
EP2500, MUX8 B
Altronix
Sub-Assembly or Adapter Pem Mounting
ACM4(CB), MOM5, PD4UL(CB), PD8UL(CB), PDS8(CB), VR6, GB1 (Genetec Synergis Cloud Link adapter plate) C
Fig. 6
Fig. 6a
- 8 - Trove2/Mercury PTC Kits Installation Guide
Enclosure Dimensions (H x W x D approximate):
27.25” x 21.5” x 6.5” (692.2mm x 552.5mm x 165.1mm)
6.75” (171.5mm)8.25” (209.5mm)
8.00” (203.2mm)
2.00” (50.8mm)
2.00” (50.8mm)
1.25” (31.8mm)
1.25” (31.8mm)
5.25” (133.4mm) 5.25” (133.4mm)7.00” (177.8mm)
1.25” (31.8mm)
6.25” (158.8mm) 19.80” (502.9mm)
1.00” (25.4mm)
27” (685.8mm)
1.5”
(38.1mm)
2.00” (50.8mm) 2.00” (50.8mm)
3.5”(88.9mm) 3.5”(88.9mm)
21.50” (546.1mm)
5.25” (133.35mm) 5.25” (133.35mm)
6.25” (158.8mm)
1.25”
(31.8mm)
0.85” (21.6mm)
0.5625” (14.3mm)
2.415” (61.3mm)
0.685” (17.4mm)
1.77”
(45mm)
0.885” (22.5mm)
1.125” (28.3mm)
Knockouts
2.00” (50.8mm) 2.00” (50.8mm)
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
web site: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IITrove2/Mercury PTC Kits I30U
MEMBER
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Altronix T2MK3F4D User manual

Category
Security device components
Type
User manual

Altronix T2MK3F4D is a fully assembled kit that includes a Trove2 enclosure with TM2 Altronix/Mercury backplane, eFlow6NB Power Supply/Charger, ACM4CB PTC Access Power Controller, VR6 Voltage Regulator, and PDS8CB Dual Input PTC Power Distribution Module. This kit is ideal for access control applications requiring up to four doors and provides a reliable and efficient power solution for various Mercury boards.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI