RAB Lighting PRT105/D10/LC Operating instructions

Type
Operating instructions
INSTRUCTIONS
PORTO® and PORTO® XL INSTALLATION
RAB Lighting is committed to creating high-quality, aordable, well-designed and energy-ecient LED lighting and controls that make it easy for electricians to install
and end users to save energy. Wed love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
Page 1
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB xtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining xture. No user serviceable parts inside.
CAUTION: For proper weatherproof function all gaskets must be seated properly and all screws inserted and tightened
rmly. Apply weatherproof silicone sealant around the edge of the ceiling mounting box and/or junction box. This is
especially important with an uneven ceiling surface. Silicone all plugs and unused conduit entries.
PORTO® PORTO® XL
Junction
Box
Plugs (4)
Gaskets
Screws (2)
LED
Housing
Screws (2)
Screws (2)
EZ Hang Hook
Gaskets
Fixture
Wires
Screws (2)
Junction
Box
NPS Adaptor
Fig: 1
Fig: 2
CEILING MOUNTING
PENDANT MOUNTING
The xture is suitable for outdoor applications in wet locations.
1. Loosen Screws (2) to free Junction Box from LED Housing.
Remove NPS Adaptor as marked (Fig. 2) if mounting directly to
ceiling surface without junction box.
2. Mount Junction Box to ceiling by knocking out (4) Knock Out
Locations as marked in Fig. 3. Use the appropriate mounting
hardware for the mounting surface. May alternately be mounted
to recessed junction boxes.
3. For hands-free wiring, hang the xture on the EZ Hang Hook as
shown in Fig 1. Connect supply wires to Fixture Wires. Supply
can come from back or through either of four 1/2” Plugs to make
electrical splices. Use appropriate UL approved wire connectors as
required by code to complete wiring.
4. Close xture and tighten Screws (2).
5. If mounting surface is irregular, use caulk to seal any gaps around
Junction Box.
Fixture can be mounted to a 1/2” or 3/4” NPS Pendant. 1/2” to 3/4”
NPS Adaptor is included.
1. Feed supply wires through Pendant (supplied by others)
2. Loosen Screws (2) on LED Housing.
3. Remove 1/2” plug and mount Junction Box to Pendant. For 3/4”
Pendant, remove plug and NPS Adaptor. Hang LED xture with
EZ Hang Hook as shown in Fig. 1
4. Make supply connections wiring sections as shown in Ceiling
Mounting section above.
5. Close xture and tighten Screws (2).
INSTRUCTIONS
PORTO® and PORTO® XL INSTALLATION
RAB Lighting is committed to creating high-quality, aordable, well-designed and energy-ecient LED lighting and controls that make it easy for electricians to install
and end users to save energy. Wed love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
Page 2
CLEANING & MAINTENANCE
CAUTION: Be sure xture temperature is cool enough to
touch. Do not clean or maintain while xture is energized.
ONOFF WIRING TROUBLESHOOTING
0-10V DIMMABLE WIRING
1. Check that the line voltage at the xture is correct.
Refer to wiring directions.
2. Be sure the xture is grounded properly.
3. Is the photocell, if used, functioning properly?
1. Clean polycarbonate lens with non-abrasive cleaning solution.
2. Do not open the xture to clean the LEDs. Do not touch the LEDs.
Universal voltage driver permits operation at 120V thru 277V, 50 or
60 Hz. Units ordered with (/480V) sux are 480V, 50Hz or 60Hz. For
non-dimming, follow the wiring directions in g. 4.
1. Connect the black xture lead to the LINE supply lead.
2. Connect the white xture lead to the COMMON supply lead.
3. Connect the GROUND wire from xture to supply ground.
Universal voltage driver permits operation at 120V thru 277V, 50 or
60 Hz. Units ordered with (/480V) sux are 480V, 50Hz or 60Hz.
For 0-10V Dimming, follow the wiring directions in g. 5.
1. Connect the black xture lead to the LINE supply leads.
2. Connect the white xture lead to the COMMON supply lead
3. Connect the GROUND wire from xture to supply ground. DO
NOT connect the GROUND of the dimming xture to the output.
4. Connect the purple xture lead to the (V+) DIM lead.
5. Connect the gray xture lead to the (V-) DIM leads.
6. Cap the yellow xture lead, if present. Do NOT connect.
4.13”
[104.8 mm]
KNOCK OUT LOCATIONS
3.54”
[89.8 mm]
3.54”
[89.8 mm]
5.25”
[133.4 mm]
PORT-IN-0919
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly - [email protected]
Free Lighting Layouts
Answered online or by request
© 2019 RAB LIGHTING Inc.
Northvale, New Jersey 07647 USA
RAB WARRANTY: RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty PATENT: Patent information can be found at rablighting.com/ip
Fig: 3
Fig: 4
Fig: 5
73131-RAB
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82

RAB Lighting PRT105/D10/LC Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI