Ever W/PGRLTO-3340K0/00, W/PGRLTO-3310K0/00, W/PGRLTO-3315K0/00, W/PGRLTO-3320K0/00, W/PGRLTO-3330K0/00, W/PGRLTO-3350K0/00, W/PGRLTO-3360K0/00 User manual

  • Hello! I am an AI chatbot trained to assist you with the Ever W/PGRLTO-3340K0/00 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
2
TABLE OF CONTENTS
TABLE OF CONTENTS .................................................................................................................................................................... 2
INTRODUCTION ............................................................................................................................................................................... 3
GENERAL FEATURES OF THE UPS UNIT .................................................................................................................................. 4
SAFETY INSTRUCTIONS AND RECOMMENDATIONS............................................................................................................ 7
TECHNICAL DESCRIPTION......................................................................................................................................................... 13
THE UPS UNIT DESIGN AND COMPONENTS ........................................................................................................................ 13
THE USER INTERFACE .............................................................................................................................................................. 14
SCREENS ...................................................................................................................................................................................... 17
Main Menu ............................................................................................................................................................................... 18
MEASUREMENTS Sub-menu ................................................................................................................................................... 19
CONTROL Sub-menu ............................................................................................................................................................... 24
CONFIGURATION Sub-menu .................................................................................................................................................. 27
ALARMS Sub-menu .................................................................................................................................................................. 30
STATISTICS Sub-menu ............................................................................................................................................................. 32
PANEL SETTINGS Sub-menu .................................................................................................................................................. 33
IDENTIFICATION Sub-menu ................................................................................................................................................... 35
EVENTS Sub-menu ................................................................................................................................................................... 36
SERVICE Sub-menu ................................................................................................................................................................. 37
SCHEDULE PLANNER Sub-menu ........................................................................................................................................... 37
The RELAYS Sub-menu............................................................................................................................................................. 40
INPUT Sub-menu ...................................................................................................................................................................... 41
MODES OF UPS OPERATION .................................................................................................................................................... 42
PROTECTIONS AND SAFEGUARDS ........................................................................................................................................ 45
Overload protection .................................................................................................................................................................. 45
Short-circuit protection ............................................................................................................................................................ 45
Anti-surge protection ................................................................................................................................................................ 46
Battery protection ..................................................................................................................................................................... 46
Thermal protection ................................................................................................................................................................... 48
EPO .......................................................................................................................................................................................... 48
UPS UNIT INSTALLATION ........................................................................................................................................................... 49
ELECTRICAL SYSTEM ON THE PREMISES............................................................................................................................ 49
UNPACKING THE PRODUCT .................................................................................................................................................... 49
INSTALLING THE UPS UNIT ..................................................................................................................................................... 50
CONNECTING THE UPS TO THE MAINS ................................................................................................................................ 52
Connecting elements ................................................................................................................................................................. 52
Starting-up the UPS unit (power supply from the main line) .................................................................................................... 54
Start-up (no supply in the main lines) “cold start” ................................................................................................................ 54
Switching off and disconnecting the UPS unit .......................................................................................................................... 55
BATTERY PACK (option) ............................................................................................................................................................ 56
Connecting the battery packs .................................................................................................................................................... 57
Disconnecting the packs ........................................................................................................................................................... 58
ADDITIONAL FUNCTIONALITIES OF THE UPS UNIT .......................................................................................................... 59
ADDITIONAL FUNCTIONAL ELEMENTS ............................................................................................................................... 59
Manual bypass function ............................................................................................................................................................ 59
Control input and DC power supply ports ................................................................................................................................ 59
Programmable outputs ............................................................................................................................................................. 60
REACTIVE POWER COMPENSATION ..................................................................................................................................... 61
HYBRID OPERATION ................................................................................................................................................................. 62
PARALLEL SYSTEMS .................................................................................................................................................................... 64
INSTALLATION OF THE SYSTEM ........................................................................................................................................... 66
SYSTEM START-UP .................................................................................................................................................................... 66
SWITCHING OFF THE SYSTEM ................................................................................................................................................ 67
CONNECTING / DISCONNECTING A UPS UNIT TO / FROM THE EXISTING SYSTEM ................................................... 67
COMMUNICATION WITH EXTERNAL MANAGEMENT/CONTROL SYSTEMS .............................................................. 70
COMMUNICATION USING RS232 OR USB PORTS ................................................................................................................ 70
EVER SNMP/HTTP NETWORK MANAGEMENT CARD ........................................................................................................ 71
Installing the management card................................................................................................................................................ 72
COMMUNICATION USING THE MODBUS PROTPCOL ........................................................................................................ 73
OPERATING INSTRUCTIONS ...................................................................................................................................................... 74
UPS OPERATION WITH POWER GENERATORS .................................................................................................................... 75
STORAGE, MAINTENANCE AND TRANSPORT ..................................................................................................................... 75
DISPOSAL .................................................................................................................................................................................... 77
TECHNICAL PARAMETERS ........................................................................................................................................................ 78
LEGAL REGULATIONS AND WARRANTY ............................................................................................................................... 81
DECLARATION OF CONFORMITY .......................................................................................................................................... 81
WARRANTY ................................................................................................................................................................................ 81
APPENDICES.................................................................................................................................................................................... 82
DESCRIPTION OF MODBUS REGISTERS ................................................................................................................................ 82
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
3
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
INTRODUCTION
Thank you for purchasing the EVER POWERLINE GREEN 33 LITE UPS system.
This UPS system has been designed and engineered to meet your expectations and
provide the highest standard of protection against power failure.
This manual contains all relevant information to ensure correct and safe operation of
the unit. Please read this manual carefully and thoroughly prior to using the EVER
POWERLINE GREEN 33 LITE unit. This will help to operate the unit and correctly
and safely. The UPS unit has been designed, engineered and manufactured
in Poland. Its design and construction are fully compliant with the CE marking
standards.
The POWERLINE GREEN 33 LITE units are ONLINE (VFI) class units designed to
work with equipment supplied from three-phase electric power mains. These units
are designed to work with particularly sensitive equipment. It is a range of advanced
power supply units designed mainly for computer servers, computer networks and
data processing systems.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
4
GENERAL FEATURES OF THE UPS UNIT
Alongside their excellent performance and reliability, the POWERLINE GREEN 33
LITE range of UPS units offers a number of other advantages which include:
On-line operation using real double conversion, with sinusoidal output voltage
(with the highest quality VFI-SS-111 parameters).
UPS input reactive power compensation with tangible financial benefits
resulting from reduced bills for reactive power consumption.
High short-circuit current which helps to achieve high selectivity of the
protection available for the power distribution lines.
Hybrid operation mode extending backup time (in BATTERY mode) by
ensuring power is supplied to the inverter concurrently from batteries and from the
power grid with poor/insufficient parameters - this is available for a specific range
of network voltage degradation (very wide input voltage window).
Achieving high efficiency over a wide range of loads thanks to the use of high
quality components.
Dynamic cooling management algorithm designed to allow adaptive
adjustment of the cooling system capacity to the current state of the UPS unit (to
minimize power losses and to reduce the costs associated with the demand for
cooling).
The Intelligent Battery Management technology utilizes the advanced battery
management strategy in order to extend battery life and to optimize the charging
time and charging energy efficiency.
Availability of the ECO mode further improves the efficiency of the power supply
system (through the ability to differentiate between periods with varying degrees
of supply reliability).
Scalability (extending) of the backup operation time thanks to the possibility of
connecting larger number of external battery packs to the UPS unit (optional).
The scalability of the power supplied by the UPS.
The Start-on-battery function enables the UPS unit to be started even if power
supply from the mains is not available (the so-called "Cold start” feature).
Capable of operating in conjunction with external control panels (using the
Android system), and using a RS232, RS485 or USB communication interface,
SNMP/HTTP network management card, control inputs and programmable volt-
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
5
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
free outputs. It uses an integrated LCD operator’s control panel (with adjustable
angle). All these are designed to allow a customised UPS remote control
strategy.
Remote Emergency Power Off (Remote EPO) functionality which interrupts
power supply from the UPS output to loads in extreme situations or in emergency
(e.g. fire).
Obtaining information about temperature and humidity on the basis of
measurements making it possible to analyse the environmental parameters.
Events Log records and stores the data related to the events that have
occurred during the operation of the UPS unit (recording the modes of operation,
alerts and messages related to the device).
“Soft start” ensures correct start of the UPS system (provides protection
against formation of transitional states).
The POWERLINE GREEN 33 LITE UPS systems consists of the following functional
blocks:
rectifier,
inverter,
battery set,
microprocessor-based control system with measurement circuits,
automated by-pass system (static BYPASS),
manual (service) bypass system (UPS/BYPASS manual switch) optional
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
6
Figure 1: Simplified block diagram of the UPS unit
The rectifier transforms the alternating current voltage from the mains into direct
current voltage. It also doubles as a battery charger. The DC voltage bus is the basic
source of power for the inverter system which in turns generates sinusoidal AC
voltage to be used to power the loads. The microprocessor-based control systems
ensure precision and reliability of the entire power supply system.
The automated bypass system helps to increase the overall operating security of the
entire system. In cases where the permissible inverter parameters have been
exceeded, receivers will be supplied directly from the mains. In this way the
automated by-pass system works as an additional passive protection of the power
supply. The manual switching function for the bypass system allows switching over
completely to supplying power to the connected loads from the mains only. In this
way the connected loads are powered from the mains, thus bypassing the internal
UPS modules.
Duration of the power back-up operation depends on the number of loads as well as
the type and number of batteries used with the UPS. Please note that even in case
when batteries from different suppliers have the same rated capacity, the backup
time for the same load may vary.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
7
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
SAFETY INSTRUCTIONS AND RECOMMENDATIONS
A) General information
CAUTION! The unit should be operated and stored in conditions
complying with the requirements set in the specification (technical
documentation).
CAUTION! The UPS is disconnected from the mains only when the
power lead is disconnected removed from the mains socket.
CAUTION! The unit is equipped with an internal power source (batteries)
or it may operate in combination with a fixed, external source of power
(battery packs). Dangerous voltage may be present at the output
terminal(s), even if the unit has been disconnected from the mains.
CAUTION! The user should place warning labels on all remotely
installed primary isolation switches in order to warn electrical service
technicians that the circuit is powered by a UPS unit. The following (or
equivalent) text should be used on such warning labels:
DISCONNECT THE UPS SYSTEM BEFORE STARTING WORK ON THIS
CIRCUIT.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
8
CAUTION! Opening the unit’s casing may result in electric shock.
CAUTION! Do not touch any electrical connectors, terminals and internal
metal elements unless power supply has been properly disconnected.
CAUTION! All openings and spaces designed to provide access to the
unit's electrical connections must remain covered (with applicable
covers). Failure to observe this requirement may create hazard
potentially resulting in injury or death for persons who touch such
connectors. It may also cause damage to the unit.
CAUTION! In the event of a short circuit, the resulting high current may
cause serious burns or scalds.
CAUTION! There are no user-serviceable parts inside the UPS unit.
CAUTION! The POWERLINE GREEN 33 LITE range of UPS units is not
intended to work directly with medical equipment, life-supporting
equipment or any other equipment that may have effect on health.
B) Installation information and requirements
CAUTION! The POWERLINE GREEN 33 LITE range of UPS units may
only be installed and maintained by suitably qualified service technicians.
CAUTION! Before installation of the UPS unit, the staff and users must
become familiar with the Health and Safety regulations when working
and handling electrical equipment up to 1 kV voltage.
CAUTION! Before connecting any cables or making any connections
within the UPS unit or in the electrical system, make sure there is no
dangerous voltage on electrical terminals and cables in the system.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
9
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
CAUTION! The UPS may only be connected to a power system with
indicated rated voltage, with a suitable grounding connection installed.
The facility's electrical system to which the UPS unit is connected must
be fitted with overload and short-circuit protection.
CAUTION! Only TN-S or TN-C-S configuration is allowed on the UPS
unit's input side, and only TN-S configuration is allowed on the UPS
unit's output side.
CAUTION! No extension cords should be used for connecting the UPS
unit.
CAUTION! It is forbidden to install the UPS unit in the vicinity of
flammable materials or substances!
Technicians must not work alone in hazardous conditions that may be dangerous
to health and/or life.
Shortly after the UPS unit has been moved from a cold environment to a warm
environment, moisture condensation may appear. The UPS unit must be
completely dry before installation and operation. The acclimatisation time should
be at least 2 hours.
UPS units and battery packs must not be installed in humid environment.
UPS units and battery packs must not be installed in places where they would be
exposed to direct sunlight. They must not be installed near sources of heat.
Ventilation openings in the UPS unit casing must not be blocked. Always observe
distances to ventilation openings specified in the manual.
Before connecting the units, is necessary to check the condition of all leads,
cables, connectors, sockets and plugs, as well as that of the unit itself.
The unit must be connected to a power circuit with a PE grounding conductor.
Failure to observe this requirement may result in electric shock.
To reduce the risk of electric shock (in case the grounding cannot be checked),
the unit must be disconnected from the mains before installation or connecting to
other equipment. The power lead may only be connected again after making all
required connections.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
10
The electric system's grounding conductor leads the leakage current away from
the receivers. The leakage currents of all loads connected to the UPS unit's
output are totalized in the UPS unit's power lead. The summary leakage current
may trigger protective devices (RCD) and result in disconnecting power to the
loads.
A UPS unit is a fixed connection device; consequently, a breaker should be used
in the fixed cabling.
When connecting and disconnecting signal cables, all actions should be
performed with one hand only (if feasible). This is to avoid electric shock when
touching two surfaces with different electrical potentials.
Connecting leads should be routed in such a way to ensure they are
protected against treading on them or tripping over them.
An emergency power-off button (EPO), dedicated to the UPS system, should be
installed in the building's electrical system. This is to allow disconnecting, in
emergency, the UPS unit from the connected loads regardless of the mode in
which the UPS is operating.
To minimise the risk of fire, connections should only be made to circuits (electrical
systems) whose rating is adequate for the connected loads, with properly selected
overcurrent protection. Additionally, the breaker should feature at least a 3 mm
insulating air gap.
C) Operation of the UPS unit
Health and Safety regulations and guidelines specified in the UPS unit operating
manual must be observed when handling and operating the UPS unit.
All these instructions must be executed step by step. Should any problems
emerge when executing the instructions listed in this manual, please contact
EVER service support (www.ever.eu).
Never disconnect the grounding at the UPS unit or at the terminals of the
building's electrical system, as this will disable the UPS unit's protective
grounding.
There may be voltage on the UPS unit's output terminals, even if the UPS is
disconnected from the building's electrical system (due to presence of power in
the unit's internal batteries and/or battery packs).
Liquids and foreign bodies must not be allowed to penetrate the UPS casing.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
11
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
WARNING: The unit described here is a C3 category UPS. This is a product
designed for commercial and industrial applications, meeting the Second
Environment levels. Additional precautions or restrictions to be observed
during installation may be required to prevent the emission of interferences.
D) Maintenance, repair and breakdown information
Dangerously high voltages are present in the UPS unit. Repairs and maintenance
may only be performed by suitably qualified service technicians.
CAUTION - Risk of electric shock! Even if the unit has been disconnected from
the mains (from terminals of the electrical power supply), parts inside the UPS
unit remain connected to the batteries, which may create hazards. Disconnect the
battery and/or battery packs before carrying out any servicing and/or
maintenance. Make sure there is no dangerous voltage on the DC circuit internal
elements.
WARNING: Batteries may only be replaced by suitably qualified service
technicians holding professional licences and wearing personal protection
equipment required by law.
CAUTION - Risk of electric shock! Dangerous voltage may be present between
the battery circuit and the grounding point!
Batteries have high short-circuit current and pose a risk of electric shock. The
following precautions should be taken when working with batteries:
remove jewellery, watches, rings and other metal items,
only use tools with insulated handles.
When replacing batteries, always use the same type and the same number of
batteries. Using batteries of incorrect type may result in explosion.
Always dispose of used batteries according to relevant instructions.
WARNING: Disposing of batteries in fire is prohibited as this may result in
explosion.
WARNING: Opening or damaging the batteries may cause electrolyte to leak;
electrolyte is harmful to skin and eyes, and may also be toxic.
To avoid the danger of fire and damage to the mains or power supply system,
always replace broken or blown fuses with fuses of the same type and
parameters.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
12
Disconnect the device from the mains before cleaning. Do not use liquid or
sprayed cleaning agents.
UPS units may only be disassembled by suitably qualified service technicians.
E) Transport and packaging requirements
Exercise particular care when transporting the equipment, due to its heavy weight.
Heavy equipment must be moved by at least two or more persons.
UPS units may be transported only in their original packaging boxes to ensure
adequate protection against shocks, vibrations and impact.
The unit is very heavy and has been fitted with a wheel set to facilitate moving.
The unit should be operated and stored in conditions meeting the requirements in
the product specification. UPS units must be stored in a dry room with suitable
ventilation.
If a UPS is to be stored over a longer period of time, its batteries must be
recharged at least every 6 months. The recharging procedure must always be
recorded and documented.
Always make sure to check the date when recharging is due. Do not use the UPS
unit if the deadline has passed and the batteries have not been recharged. In
such cases always contact service support.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
13
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
TECHNICAL DESCRIPTION
THE UPS UNIT DESIGN AND COMPONENTS
a) the 10-20 kVA model
a) the 30-60 kVA model
Figure 2: View of the rear panel.
1) EPO connector, 2) Communication bus connectors for parallel operation,
3) Programmable outputs (non-voltage contacts), 4) Control inputs, 5) USB communication
interface, 6) RS232 communication interface, 7) RS485 communication interface,
8) Adapter/expansion card slot plug, 9) Fans, 10) BYPASS (service) system switch
(optional), 11) Protection, internal batteries (F1, F2), 12) Protection, DC input lines (F5)
optional, 13) Protection, basic input lines (F4) and optionally BYPASS input lines (F3),
14) Cover, terminal connectors, 15) Mounting brackets, 16) Caster wheels to move the UPS,
17) DC power connection (12 V DC / 1A non-stabilised)
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
14
Figure 3: View of the connection terminals (on the rear panel, with the cover removed)
1) Protections and connections, main input lines (F4), 2) Connections, N neutral lines,
3) Connections, output lines, 4) PE protective cable connection point, 5) Tabs for connecting
cable rail, 6) Protections and connections, bypass input lines (F3) (optional), 7) Connections,
external battery pack (optional)
THE USER INTERFACE
The user interface consists of the following control panel (Fig. 4). features the LCD
display and the synoptic block diagram showing the UPS unit’s operation, and a 4-
button keypad.
These controls are used to monitor the UPS unit’s parameters and modes of
operation. They also allow modification of some of those parameters. Correct use of
the interface and the meaning of individual states and parameters are described
below.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
15
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
Figure 4: View of the user interface:
The UPS unit also uses sound chimes for individual device states (see Table 1).
Table 1. Acoustic signal
Action
Acoustic signal
NORMAL mode
None
HYBRID Mode
Intermittent signal; frequency increases proportionally to the level of discharging of the
batteries until it turns into a continuous sound.
BATTERY Mode
Enforced switching to the
STANDBY mode
Intermittent signal - two short signals followed by a pause
EMERGENCY Mode
Depending on the type of event
Overload
Continuous signal
Short circuit
Rapid intermittent 50% / 50% signal
Overheating
Slow intermittent 50% / 50% signal
EPO activation
Intermittent, with signal on/signal off frequency of 1s / 5s
All subsequent screens shown on the LCD display are organised into the tree
hierarchy shown on Fig. 5.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
16
Figure 5: Map of the LCD screens organised into the tree structure.
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
17
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
SCREENS
SCREENSAVER
Description:
The information page/screen starts to be displayed as a
screensaver after 5 minutes of inaction since the last button was
pressed. It also turns off the LCD panel illumination.
Type:
Readout
Parameters:
Q
battery charge level
U+
voltage, hot battery section (+)
U-
voltage, cold battery section (-)
Ld
UPS load level
Tau
expected duration of UPS backup operation
TrybPracy
UPS mode of operation
i: …, A: …
additional information as shown in Table 4
View of the
screen:
General messages (tab. 2) (i:) characterize all the UPS unit operation modes with the
exception of EMERGENCY operation which is signalled with a separate set of alarm
alerts (A:).
Table 2. List of general information messages and alarm alerts and their respective meanings.
General information messages
Alarm alerts
Abbreviation
Meaning
Message
Meaning
i:Charging
Charging
A:ShortCircuit
Short circuit
F)
i:Overload
Overload
A:Overload
Overload
F)
i:RecOverTemperature
Rectifier block overheated
A:RecOverTemperature
Rectifier block overheated
P)
i:InvOverTemperature
Inverter block overheated
A:InvOverTemperature
Inverter block overheated
F)
i:MinChargeWaiting
Waiting to achieve minimum required
battery charge following STANDBY
A:EPO
Emergency EPO
F)
i:LowBattery
90 sec of UPS backup operation
remaining
A:RecInternalError
Internal rectifier block
fault
R)
i:Service
Periodic servicing recommended
A:InvInternalError
Internal inverter block fault
R)
i:Bypass
BYPASS active
A:PO - Fault
An error occurred in one of
the units working in parallel
or redundant system
i:RecCommFail
Lost communications with the rectifier
block
F) Message cancelled by
ClearIncFault (3/4
configuration)
P) Message cancelled by
ClearRecFault (3/4
configuration)
R) After an internal fault has
occurred it is mandatory to
switch off the unit (by
completely cutting off the power
supply) and to contact a service
agent.
⃰ Time duration depends on the
type and number of batteries
installed. See the note in the
description of the Menu
(Battery)
i:InvCommFail
Lost communications with the inverter
block
i:BypPhasesSeqFail
Incorrect phase sequence for the
BYPASS line
i:BypOutOfRange
BYPASS line supply parameters out of
range
i:MainsOutOfRange
Rectifier block supply parameters out of
range
i:MainsPhasesSeqFail
Incorrect phase sequence for the rectifier
supply system
i:PO Master
UPS acts as a system management unit
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
18
i:PO SLAVE
Slave unit in system
i:PO UnitStopped
UPS disconnected from the system
i:PO RedundLost
There is no redundant units. The system
operates as parallel
i:PO UnitNotActive
UPS is not connected to the system
i:NoMinNumberUnits
In the system there is (active and ready
to work) less units than it was defined as
minimum required number of units
i:SchedulerActive
Message indicating that the function is
active scheduler, which allows the user
to program a periodic controlling the
power supply
When the date for the scheduled service approaches, the screensaver turns into a
warning message to remind the user about the need for servicing.. To exit this state
keep the Esc key depressed for the duration of 5 sec.
Main Menu
To jump to the Main Menu press the Esc key. Similarly, it is possible to force the
return to the Screensaver by hitting the Esc key (as shown on Fig. 5, relating to the
screen hierarchy).
The Main Menu uses four screens. Individual Main Menu screens are shown below.
Switching between individual screens is done by using the ▼▲ keys. To confirm the
selection (at each point) press the key. Then, once the selected menu appears,
make the desired sub-menu selection also by using the ▼▲ keys. Pressing the ESC
key takes the user one level up (to the previous screen).
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
19
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
The arrow to the left of the sub-menu name shows the actual position of the selection
check mark. The arrow only appears once the screen has been confirmed by hitting
the key. To jump to the selected submenu or parameter, pressing the key.
Pressing the ESC key takes the user one level up (to the previous screen).
MEASUREMENTS Sub-menu
The MEASUREMENTS Sub-menu uses two screens divided into six subject groups:
RECTIFIER, BYPASS, OUTPUT, BATTERY, TEMPERATURE, ENVIRONMENT.
Navigation within this menu is similar to the way shown earlier.
RECTIFIER 1/5
Description: The UPS unit’s input parameters
Type: Readout
Parameters:
ULn
rectifier input voltage for the n line
ILn
rectifier input current for the n line
View of the
screen:
RECTIFIER 2/5, 3/5, 4/5
Description: The UPS unit’s input parameters
Type: Readout
Parameters:
PLn
rectifier, input active power for the n line
SLn
rectifier, input apparent power for the n line
PFLn
rectifier input power factor for the n line
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
20
View of the
screen:
RECTIFIER 5/5
Description: The UPS unit’s input parameters
Type: Readout
Parameters:
P
summary input active power for rectifier
S
summary input apparent power for rectifier
f
rectifier input frequency (measured for the L1 line)
View of the
screen:
BYPASS 1/5
Description: Input parameters for the BYPASS line
Type: Readout
Parameters:
ULn
BYPASS line voltage (n line)
ILn
BYPASS line current (n line)
View of the
screen:
BYPASS 2/5, 3/5, 4/5
Description: Input parameters for the BYPASS line
Type: Readout
Parameters:
PLn
BYPASS line input active power (n line)
SLn
BYPASS line input apparent power (n line)
PFLn
BYPASS line input power factor (n line)
Percentage values - show the levels for a given n line
/