Trane BCI-I Integration Manual

Type
Integration Manual
September 2009
ACC-SVP01B-EN
BACnet™ Communication
Interface (BCI-I)
for IntelliPak™ and Commercial Self-contained
Integration Guide
2 ACC-SVP01B-EN • BCI0I Integration Guide
Copyright
© 2009 Trane All rights reserved
This document and the information in it are the property of Trane and may not be used or reproduced in whole
or in part, without the written permission of Trane. Trane reserves the right to revise this publication at any
time and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
IntelliPak, Tracer, Trane, and the Trane logo are trademarks of Trane in the United States and other countries.
All trademarks referenced in this document are the trademarks of their respective owners.
Table of Contents
ACC-SVP01B-EN • BCI-I Integration Guide 3
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ordering Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
BCI-I Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Starting a Session of Tracer TU and Direct Connection . . . . . . . . . . . . . . . . . 5
IP Units Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
BACnet Object Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Change Baud Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Change Device ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Stand-alone or BAS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
IntelliPak Control Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
BAS Unit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Periodic Update of BAS Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
BAS Communication Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Input/Output Commands and Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
System Control Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Filter Timer Reset Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Diagnostics Reset Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Setpoint Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Timestamp Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
BCI IntelliPak Rotary Switches and LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
LEDs Description, Behavior, and Troubleshooting . . . . . . . . . . . . . . . . . . . . . 13
BACnet Data Points and Configuration Property Definitions . . . . . . . . . . . . . . . 17
BACnet Protocol Implementation Conformance Statement (PICS) . . . . . . . 17
Standardized Device Profile (Annex L) . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Interoperability Building Blocks (Annex K) . . . . . . . . . . . . . . . . . . . . . . . . 17
Segmentation Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Object Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
BACnet Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Data Link Layer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Device Address Binding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Networking Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Object Data Points and Diagnostic Data Points . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4 ACC-SVP01B-EN • BCI-I Integration Guide
Overview
The BACnet Communication Interface for IntelliPak (BCI-I) is comprised of a Tracer™ UC400
controller with interface software. It is a non-programmable communications module that allows
heating, ventilation, and air-conditioning (HVAC) equipment to communicate on a BACnet
communications network.
This guide provides:
A list of ordering numbers
A brief overview of the BACnet™ protocol
BCI-I configuration information
A explanation of the BCI-I device rotary switches and LEDs
Data point configuration property definitions
Tables listing object data points
Additional resources
A glossary of terms
Note: Users of this guide should have basic knowledge of BACnet protocol. For more detailed
information about this protocol, visit the company web site listed under Additional
Resources,” p. 44.
Ordering Numbers
BACnet Protocol
The Building Automation and Control Network (BACnet and ANSI/ASHRAE Standard 135-2004)
protocol is a standard that allows building automation systems or components from different
manufacturers to share information and control functions. BACnet provides building owners the
capability to connect various types of building control systems or subsystems together for a variety
of reasons. In addition, multiple vendors can use this protocol to share information for monitoring
and supervisory control between systems and devices in a multi-vendor interconnected system.
The BACnet protocol identifies standard objects (data points) called BACnet objects. Each object
has a defined list of properties that provide information about that object. BACnet also defines a
number of standard application services that are used to access data and manipulate these objects
and provides a client/server communication between devices. For more information on BACnet
protocol, refer to Additional Resources,” p. 44.
BACnet Testing Laboratory (BTL) Certification
The BCI-I supports the BACnet communication protocol and has been designed to meet the
requirements of the application-specific control profile. For more details, refer to the BTL web site
at www.bacnetassociation.org.
Order Number Description
X13651544-010 IntelliPak I; for software and hardware
C175218460010 IntelliPak I, II, and CSC; for field-installed kit
ACC-SVP01B-EN • BCI-I Integration Guide 5
BCI-I Configuration
BCI-I Configuration
This section will provide the following information when configuring the BCI-I:
Overview
Starting a session of Tracer TU and direct connection
Resetting to factory default
Configuring IP units
Configuring BACnet objects
Changing baud rate and device ID
Input/output and equipment functions
Overview
The BCI-I device is designed as a self-configuring controller to accommodate the many possible
equipment configuration options available in the IntelliPak line of equipment. This self-configuring
device eliminates the need for the BAS technician having to create BACnet objects, minimizes the
risk of object configuration errors, and allows the IntelliPak unit to be quickly installed in the BAS.
The self-configuration process only creates objects that are appropriate for the feature set of the
specific IntelliPak unit the BCI-I is connected to. Once this process is complete, the device exits
factory mode and enters the normal mode of operation. At this point, the self-configuration process
will not
start when power is applied to the device.
The set of objects listed in Table 3 , p . 24 through Table 10, p. 31, are the super set of all possible
objects supported by the IntelliPak line of equipment. The BAS technician should query the device
for the list of actual objects that have been created in the device.
Starting a Session of Tracer TU and Direct Connection
Tracer TU is the service tool software that allows the technician to modify the operation of the
device and to discover the BACnet objects present in the device. To modify the device or discover
objects, the user must first connect to Tracer TU as follows:
WARNING: Remove power from the HVAC equipment before opening
electrical control panel.
1. Connect a USB cable directly between the laptop PC and the service port located on the front
of the BCI-I device. When connecting to the controller for the first time, the Found New
Hardware Wizard appears. Follow the wizard instructions to install the USB hardware driver.
2. Click either the Tracer TU desktop icon or the Tracer TU program item in the Tracer TU group
on the Start menu. The Tracer TU splash screen appears briefly followed by the Connect
dialog box.
3. Select the Direct Connection (Via USB cable) radio button if it is not already selected.
4. Click the Connect button and the Tracer TU main page will appear after successful connection.
Note: The BCI-I may be powered via the USB cable or 24 Vac from the HVAC unit. Concurrent
connection of unit power and the USB cable will not harm the BCI-I device.
For more detailed information about direct connection to Tracer TU, refer to the Tracer™ TU Service
Tool Getting Started Guide (TTU-SVN02) (X39641083).
6 ACC-SVP01B-EN • BCI-I Integration Guide
BCI-I Configuration
Reset to Factory Default
Factory default mode is the only mode the technician can use to set the units of measure for the
device or to scan the IntelliPak unit to create BACnet objects. The process of putting the device in
factory default mode must be run prior to executing units of measure configuration or the object
self-configuration process.
WARNING: Remove power from the HVAC equipment before
opening electrical control panel.
To reset the controller to factory default/unconfigured state:
1. Power down the unit. The IMC buss must not be active during reset.
2. Establish the connection between Tracer TU and the device. Follow the procedure, “Starting a
Session of Tracer TU and Direct Connection,” p. 5.
3. From the Utilities menu, select Controller and then Controller Settings. The Controller
Settings page appears.
4. On the controller settings page there is a gray bar at the bottom with Save/Cancel buttons.
Move the cursor near the left edge of the bar, keeping the cursor inside the bar. Click on this area
and a Clear Controller button will appear in the upper right portion of the page.
5. Click the Clear Controller button and a pop-up window will appear asking for confirmation to
reset the device. Click Ye s .
6. After a few seconds a pop-up will appear confirming that the controller has been reset and
indicating that the controller will be rebooted. Click OK.
After the controller boots up, it will be in factory default state. The units of measure is SI (metric),
the MS/TP baud rate is 76,800, and there will be no BACnet objects present in the controller.
The controller must be in this state prior to changing the units of measure or self-configuring
the device. If using inch-pound units of measure, proceed to the next section, “IP Units
Configuration, otherwise, proceed to “BACnet Object Configuration.
IP Units Configuration
The BCI-I supports both inch-pound and SI (metric) units of measure. The factory default units of
measure is SI. The device allows only a change of units for all objects as a whole. Mixed units of
measure is not allowed. If the controller is not in factory default state, follow the previous
procedure, “Reset to Factory Default,” p. 6.
To change the units of measure in the device:
1. Establish the connection between Tracer TU and the BCI-I. Follow the procedure,“Starting a
Session of Tracer TU and Direct Connection,” p. 5.
2. From the Utilities drop-down menu, select Controller and then Controller Settings. The
page contains four configuration frames that are minimized. Expand the Controller Units
frame.
3. In the Device Units box of the frame, select IP units of measure radio button and then click
Save button in the lower right corner of the window. A pop-up will display indicating that
changes were saved to the controller. Select OK.
4. Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then
reconnecting the plug. After the controller boots up, it will be in factory default state, the units
of measure is IP, the MS/TP baud rate is 76,800, and there will be no BACnet objects present in
the controller.
ACC-SVP01B-EN • BCI-I Integration Guide 7
BCI-I Configuration
BACnet Object Configuration
Configuring BACnet objects is a self-configuring process. If the controller is not in factory default
state, follow the previous procedure, “Reset to Factory Default,” p. 6.
1. Remove the USB cable plug from the device.
2. Apply power to the HVAC equipment. After the device boots up, the self-configuration process
will begin. No further user action is required.
Note: Do not remove power while the device is in self-configuration mode. This typically takes
2 to 4 minutes to complete. Once complete, the device enters normal operating mode.
Change Baud Rate
The BCI-I device supports four baud rates: 9600, 19200, 38400, and 76800 baud. The default baud
rate is 76800 baud. The baud rate can be modified with Tracer TU.
WARNING: Remove power from the HVAC equipment before opening
electrical control panel.
To change baud rate:
1. Establish the connection between Tracer TU and the BCI-I. Follow the procedure,“Starting a
Session of Tracer TU and Direct Connection,” p. 5.
2. From the Utilities drop-down menu, select Controller and then Controller Settings. The
page contains four configuration frames that are minimized. Expand the Protocol frame.
3. Click on the drop down arrow for the Baud Rate list and select the desired baud rate.
4. Click Save button in the lower right corner of the window. A pop-up will display indicating that
changes were saved to the controller. Click OK.
5. Exit Tracer TU and disconnect the USB cable plug.
6. Apply power to the HVAC equipment.
Change Device ID
By default, the BCI-I device sets its device ID to the same value as the one defined by the rotary
switches (MS/TP MAC address) on the front of the device. Refer to the section, “Rotary Switches,
p. 12. For simple networks, this is an easy method to guarantee unique device IDs across the link.
The device also supports the full range of device ID values as specified by the BACnet Standard.
Systems that require a more complex device ID convention are supported with Tracer TU, which
has the ability to set the device ID via software configuration.
WARNING: Remove power from the HVAC equipment before opening
electrical control panel.
The process for soft setting the device ID is as follows:
1. Establish the connection between Tracer TU and the BCI-I. Follow the procedure,“Starting a
Session of Tracer TU and Direct Connection,” p. 5.
2. From the Utilities drop-down menu, select Controller and then Controller Settings. The
page contains four configuration frames that are minimized. Expand the Protocol frame.
3. In the device ID box, select the check box next to Use Software Device ID to enable the
functionality. The swipe-and-type box becomes available.
4. Type in the desired device ID.
8 ACC-SVP01B-EN • BCI-I Integration Guide
BCI-I Configuration
5. Click the Save button in the lower right corner of the window. A pop-up will display indicating
that changes were saved to the controller. Click OK.
6. Exit Tracer TU and disconnect the USB service plug.
7. Apply power to the HVAC equipment.
Stand-alone or BAS Operation
The control system on HVAC equipment has the ability to operate the unit as a stand-alone system
or as part of a building automation system. The BCI-I (either factory or field installed), by default,
is configured for stand-alone operation. This configuration enables the HVAC equipment to operate
prior to the commissioning of the unit into the BAS.
IntelliPak Control Configuration
The IntelliPak control system must be configured at the human interface (HI) to support unit control
from the BAS. The technician should set/verify the following configuration properties as illustrated
below. The technician should also verify that the BAS Module Comm Failure diagnostic is not
present.
BAS Unit Control
The BCI-I provides a method for a BAS to control the operation of HVAC equipment. This method
consists of BACnet objects that the BAS can access to control and monitor the status of equipment.
There are two sets of objects:
Output objects; used by the BAS to provide command, setpoint, and sensor information to the
IntelliPak unit.
Input objects; provide IntelliPak status information to the BAS. See tables 3 to 11 for the list of
objects supported.
The system allows the BAS technician to define the amount of control that the BAS system will
apply to the unit. This is done by configuring the state of the Out of Service property of the output
objects. If the property is set to True, the equipment will use a corresponding local value for control.
If the property is set to False, the local value is ignored and the BAS-supplied value is used for
control. The BAS value is provided to the IntelliPak by writing to the present value property of the
corresponding output object. The factory default value for the Out of Service property of these
objects is True.
1. Configuration Menu
2. Setup Menu
3. Diagnostics Menu
Software Revision Number:
BAS Communications: BACnet 18.01
Configuration - Model Num Digit 34
BAS Communication Module Installed
Unit Control: BAS/NETWORK
Active Diagnostic - - Auto Reset
None
Human Interface Representation
ACC-SVP01B-EN • BCI-I Integration Guide 9
BCI-I Configuration
Periodic Update of BAS Values
The BCI-I device requires the BAS system to provide a periodic update to the sensor values. This
is required to protect against a loss of communication between the BAS and the BCI-I. By BACnet
definition, the present value of the object will maintain the last value written to it, regardless of the
amount of time that has elapsed since the last write. If communication is lost for several minutes
or longer, the present value of BAS-supplied sensor objects may no longer represent the current
state of environmental conditions. This may result in decreased occupant comfort and damage to
building systems.
BAS Communication Failure
The BCI-I is designed to minimize communication failure mode. It does this by monitoring the
length of time that has elapsed since the last write to the present value of the sensor object. If the
length of time exceeds a predefined limit, the BCI-I will place the object into the fault state and revert
to a unit-supplied sensor value for control. At power up, the sensor objects are set to a fault state
and they will remain in this state until a write is detected. The minimum periodic refresh rate for
the objects is defined in Ta bl e 3 , p . 24 . The following list is a set of sensor values that can be
supplied by the BAS:
Space Static Pressure BAS
Space Air Temperature BAS
Discharge Air Temperature BAS
Duct Static Air Pressure BAS
Outdoor Air Temperature BAS
Outdoor Air Humidity BAS
Outdoor Airflow BAS
Space CO2 Concentration BAS
Space Humidity BAS
Input/Output Commands and Calculations
This section will provide the following information about certain inputs and outputs that perform
unique control commands and calculations:
System control command
Filter timer and diagnostic reset commands
Setpoint calculations
System Control Command
Binary Output Object 1, has a special importance in the system. The object allows the BAS to
command the unit to run in a local or BAS control mode. When the present value property of the
object is set to Local Control, the IntelliPak unit will enter local control and ignore BAS supplied
values. In this mode, the unit will use local sensor and setpoint values. When the object present
value property is set to BAS Control, the IntelliPak unit will use the values supplied by the BAS
system for unit control.
Filter Timer Reset Command
The BCI-I uses the Filter Runtime Hours object (AI 6) to generate a diagnostic when its present value
is greater than the Filter Runtime Hours Setpoint, (AV 1) present value. The procedure for resetting
the timer is as follows:
10 ACC-SVP01B-EN • BCI-I Integration Guide
BCI-I Configuration
The BAS will change the state of the Filter Timer Reset Command object (BO 13) to the active
state. Upon the change to active state, the BCI-I will set the present value of the Filter Runtime
Hours object to zero and then set the Reset Command object back to the inactive state.
Diagnostics Reset Command
The IntelliPak control system monitors the operation of the HVAC equipment. If an abnormal
condition is detected, a diagnostic message is displayed on the human interface of the equipment
control panel. In addition, the set of internal diagnostics is mapped to the set of BACnet binary input
objects, as listed in Table 9, p. 31. The corresponding BI object will change state from inactive to
active when the diagnostic is detected. The object has been configured to send a BACnet event
message to external BACnet devices as defined by the protocol.
The BAS has the ability to reset internal diagnostics by controlling the state of the Diagnostic Reset
Command object (BO 14). The procedure for resetting diagnostics is as follows:
The BAS will change the state of the Diagnostic Reset to the active state. Upon the change to
active state, the IntelliPak control system will reset all internal diagnostics and set the state of
all of the diagnostic objects to inactive. Upon completion of this action, the BCI-I will set the
present value of the Diagnostic Reset Command object back to the inactive state.
Setpoint Calculations
The equipment has the ability to perform two basic control functions:
Space air temperature control
Discharge air temperature control
When the unit is configured for discharge air control, it controls the temperature of the air leaving
the unit to the discharge air temperature setpoint.
When the unit is configured for space air temperature control, it controls the air temperature of the
space that contains the space air temperature sensor. This value may be provided by wiring the
sensor to the unit or via a sensor value provided by the BAS.
The drawing below describes how the various temperature setpoints are calculated for space
temperature control. When the unit is in an occupied mode the active space temperature setpoint
is calculated based on the space temperature setpoint and the two setpoint offset values. In
unoccupied mode, the unoccupied heating and cooling setpoints are used as the active setpoint.
ACC-SVP01B-EN • BCI-I Integration Guide 11
BCI-I Configuration
Timestamp Configuration
The BCI-C device has a software-derived clock that maintains the time and date. The device requires
the current time to enable it to record a timestamp when an event or a change in state is detected
by a BACnet object. However, in the event of a power loss, the device does not maintain this time
and date information. At powerup, the device time and date will default to 12:00 pm., Jan 1, 1970.
To minimize the possibility that the unit timestamp is not representing the actual time, the BAS
should be setup to periodically synchronize the device time clock with the BAS clock using the
BACnet TimeSynchronization service.
12 ACC-SVP01B-EN • BCI-I Integration Guide
BCI IntelliPak Rotary Switches and LEDs
BCI IntelliPak Rotary Switches and LEDs
This section provides information about the BCI-I rotary switches and LED displays.
Rotary Switches
There are three rotary switches on the front of the BCI-I device that are used to define a three-digit
address when the BCI-I is installed on a BACnet communications network. The three-digit address
setting is the BACnet MAC address.
Note: All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet.
Figure 1. Setting rotary switches
ADDRESS
0
1
2
3
4
5
6
7
8
9
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
x100
Before
After
0
5
1
3
6
2
9
4
8
7
Example of before and
after setting addresses
Use a 1/8 inch
flathead screwdriver
to set rotary switches.
Important: Each device on the BACnet/MSTP link must have a unique rotary switch setting, otherwise, communication problems will occur.
ACC-SVP01B-EN • BCI-I Integration Guide 13
BCI IntelliPak Rotary Switches and LEDs
LEDs Description, Behavior, and Troubleshooting
There are 15 LEDs on the front of the BCI-I unit. However, LEDs BO1 through BO9 are not used for
the BCI-I controller. Figure 2 shows the locations of each LED. The following table provides a
description of each LED activity, an indication or troubleshooting tips for each, and any notes.
Figure 2. LED locations
SERVI
C
E
IM
C
LINK
RX
TX
Marquee LED
Table 1. LED Activities and Troubleshooting Tips
LED Name Activities
Indication or Troubleshooting
Tip (Denoted in Bullets)
Notes
Marquee LED
Shows solid green when the unit is
powered and no problems exist
Indicates normal operation
Shows solid red when the unit is
powered, but represents low power or a
malfunction
If low power; could be under voltage
or the microprocessor has
malfunction. Follow the troubleshoot
procedure “24 Vac Measurement,
p. 15 to measure for the expected
value range.
If malfunction; unpower and then
repower unit to bring the device back
up to normal operation.
Shows blinking red when an a BACnet
object is in a fault condition
Alarm; when an alarm is triggered, for
example, when a point goes into fault
condition because of point failure or
there is an indication of a custom alarm
in TGP2
Shows blinking green when the device
does not detect the IMC buss
Verify that the IPC wiring harness is
connected to the IMC link terminals.
Verify the polarity of the IPC wiring
harness at the unit terminals.
LED not lit
Indicates power is OFF or there is a
malfunction
OFF or malfunction; cycle the power.
14 ACC-SVP01B-EN • BCI-I Integration Guide
BCI IntelliPak Rotary Switches and LEDs
Link and IMC
TX blinks green
Blinks at the data transfer rate when the
unit transfers data to other devices on
the link
TX LED: Regardless of connectivity or
not, this LED will constantly blink as it
continually looks for devices to
communicate to.
LED not lit:
Determine if, for example, a Tracer SC or
BACnet device is trying to talk to the
controller or if it is capable of talking to
the controller. Also determine if the
communication status shows down all of
the time.
Refer to “Ground Measurements,” p. 16
for a check-out procedure.
RX blinks yellow
Blinks at the data transfer rate when the
unit receives data from other devices on
the link
ON solid yellow; indicates there is
reverse polarity
LED not lit
Indicates that the controller is not
detecting communication
Not lit; cycle the power to reestablish
communication
Service
Shows solid green
Indicates someone is pressing this LED
or the controller is not operating
normally
Press and hold during power up to place
controller into boot code or press and
hold for a count of approximately 10
seconds to clear the Device ID.
What is Boot Code? When the UC400
is placed into boot code, the system
will not run any applications such as
trending, scheduling, and TGP2
runtime.
Blinks green
Indicates controllers is not accessing
application software
Restore; using TU service tool
LED not lit
Indicates controller is operating normally
Binary 01 to Binary 09 Not Used
Table 1. LED Activities and Troubleshooting Tips
LED Name Activities
Indication or Troubleshooting
Tip (Denoted in Bullets)
Notes
ACC-SVP01B-EN • BCI-I Integration Guide 15
BCI IntelliPak Rotary Switches and LEDs
24 Vac Measurement
General Information Checkout Procedure Measurement Expected Value
Checking the voltage that is
powering the UC400 is often a
necessary step when commissioning
or troubleshooting. Operational
issues and LED operation may result
in a need to measure the input
power.
When troubleshooting, it is faster to
take measurements while the load is
in place. If Step 1 indicates an out-
of-specification voltage, disconnect
the UC400 and measure the AC
voltage across the transformer.
These measurements can direct the
technician towards the problem
source.
Step 1
Measure AC voltage with the
UC400 connected. Perform this
measurement while the unit is
under load.
20.0 Vac V
ac
30.0 Vac
Step 2
Measure AC voltage with the
UC400 unconnected. Perform this
measurement while the unit is not
under load.
20.0 Vac V
ac
30.0 Vac
16 ACC-SVP01B-EN • BCI-I Integration Guide
BCI IntelliPak Rotary Switches and LEDs
Ground Measurements
General Information and Checkout Procedure Measurement Expected Value
Method 1:
AC voltage between shield conductors and device chassis ground-
the voltage difference between BACnet MS/TP device chassis ground
connections should be close to zero. If the voltage difference is greater that
4.0 Vac, there will be marginal communication or intermittent
communication problems. If the voltage difference is greater that 7.0 Vac,
some devices will no longer communicate.
Measure AC current
across the current
termination and confirm
that only one end of the
shield conductor is tied to
the earth ground
Vac 2.0 V
Method 2:
AC voltage between earth ground and device chassis ground- the
chassis ground of the UC400 needs to be connected to earth ground by
some route.
Note: Do not assume that the building frame is a valid earth ground.
Measure AC current
across the current
termination and confirm
that only one end of the
shield conductor is tied to
the earth ground
Vac 4.0 V
(Must comply with National Electrical
Code™and local electrical codes)
ACC-SVP01B-EN • BCI-I Integration Guide 17
BACnet Data Points and Configuration Property Definitions
BACnet Data Points and Configuration Property
Definitions
The BCI device allows an IntelliPak control system to communicate with BACnet systems and
devices using BACnet MS/TP. This section includes information about:
BACnet protocol implementation conformance statement (PICS)
Object types: descriptions and configuration (refer to Table 2, p. 19)
BACnet protocol: data link layers, device address binding, networking options, and character
sets
Object data points and configurations
BACnet Protocol Implementation Conformance Statement (PICS)
Standardized Device Profile (Annex L)
Interoperability Building Blocks (Annex K)
Profile Description Supported Profile
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
9
BACnet Building Controller (B-BC)
BACnet Operator Workstation (B-OWS)
BACnet Smart Actuator (B-SA)
BACnet Smart Sensor (B-SS)
Data Sharing Description Supported BIBB
Data Sharing-COV-B (DS-COV-B)
Data Sharing-ReadProperty-A (DS-RP-A)
9
Data Sharing-ReadProperty-B (DS-RP-B)
9
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
9
Data Sharing-WriteProperty-A (DS-WP-A)
9
Data Sharing-WriteProperty-B (DS-WP-B)
9
Data Sharing-WritePropertyMultiple-B (DS-WPM-B)
9
Alarm and Event Management Description Supported BIBB
Alarm and Event-ACKI-B (AE-ACK-B)
9
Alarm and Event-Alarm Summary-B (AE-ASUM-B)
9
Alarm and Event-Enrollment Summary-B (AE-ESUM-B)
9
Alarm and Event-Information-B (AE-INFO-B)
9
Alarm and Event-Notification Internal-B (AE-N-I-B)
9
18 ACC-SVP01B-EN • BCI-I Integration Guide
BACnet Data Points and Configuration Property Definitions
Segmentation Capability
Trending Description Supported BIBB
Trending-Automated Trend Retrieval-B (T-ATR-B)
9
Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)
9
Device Management Description Supported BIBB
Device Management-Backup and Restore-B (DM-BR-B)
9
Device Management-Device Communication Control-B (DM-DCC-B)
9
Device Management-Dynamic Device Binding-A (DM-DDB-A)
9
Device Management-Dynamic Device Binding-B (DM-DDB-B)
9
Device Management-Dynamic Object Binding-B (DM-DOB-B)
9
Device Management-List Manipulation-B (DM-LM-B)
9
Device Management-Object Creation and Deletion-B (DM-OCD-B)
9
Device Management-Private Transfer-A (DM-PT-A)
9
Device Management-Private Transfer-B (DM-PT-B)
9
Device Management-Reinitialize Device-B (DM-RD-B)
9
Device Management-TimeSynchronization-B (DM-TS-B)
9
Segmentation Description Supported Segment
Segmented Requests/ Window Size: 1 9
Segmented Responses/ Window Size: 1
9
ACC-SVP01B-EN • BCI-I Integration Guide 19
BACnet Data Points and Configuration Property Definitions
Object Types
Table 2. Descriptions and configurations
Object
Type
Required Properties Read Properties Written
(a)
Optional Properties Read
Ability
to
Create
Ability to
Delete
Analog
Input
Object_Identifier
•Object_Name
•Object_Type
Present_Value
•Status_Flags
•Event_State
•Out_Of_Service
•Units
•Object_Name
•Description
•Out_Of_Service
Present_Value
Reliability
•Min_Pres_Value
•Max_Pres_Value
COV_Increment
•Time_Delay
Notification_Class
•High_Limit
•Low_Limit
•Deadband
•Limit_Enable
Event_Enable
•Notify_Type
•Description
Reliability
Min_Pres_Value
•Max_Pres_Value
•COV_Increment
•Time_Delay
Notification _Class
•High_Limit
•Low_Limit
•Deadband
•Limit_Enable
Event_Enable
Acked_Transitions
•Notify_Type
Event_Time_Stamps
Yes Yes, only
user created
objects
Analog
Output
Object_Identifier
•Object_Name
•Object_Type
Present_Value
•Status_Flags
•Event_State
•Out_Of_Service
•Units
•Priority_Array
Relinquish_Default
•Object_Name
•Description
•Out_Of_Service
Present_Value
Reliability
•Min_Pres_Value
•Max_Pres_Value
Relinquish_Default
COV_Increment
•Time_Delay
Notification_Class
•High_Limit
•Low_Limit
•Deadband
•Limit_Enable
Event_Enable
•Notify_Type
•Description
Reliability
•Min_Pres-Value
•Max_Pres_Value
•COV_Increment
•Time_Delay
Notification _Class
•High_Limit
•Low_Limit
•Deadband
•Limit_Enable
Event_Enable
Acked_Transitions
•Notify_Type
Event_Time_Stamps
Yes Yes, only
user created
objects
Analog
Value
Object_Identifier
•Object_Name
•Object_Type
Present_Value
•Status_Flags
•Event_State
•Out_Of_Service
•Units
•Object_Name
•Description
•Out_Of_Service
Present_Value
Reliability
Relinquish_Default
COV_Increment
•Time_Delay
Notification_Class
•High_Limit
•Low_Limit
•Deadband
•Limit_Enable
Event_Enable
•Notify_Type
•Description
Reliability
•Priority_Array
Relinquish_Default
•COV_Increment
•Time_Delay
Notification_Class
•High_Limit
•Low_Limit
•Deadband
•Limit_Enable
Event_Enable
Acked_Transitions
•Notify_Type
Event_Time_Stamps
Yes Yes, only
user created
objects
Binary
Input
Object_Identifier
•Object_Name
•Object_Type
Present_Value
•Status_Flags
•Event_State
•Out_Of_Service
•Polarity
•Object_Name
•Description
•Out_Of_Service
•Inactive_Text
•Active_Text
Present_Value
Reliability
Change_Of_State_Count
Elapsed_Active_Time
•Time_Delay
Notification_Class
•Alarm_Value
Event_Enable
Acked_Transitions
•Notify_Type
•Description
•Inactive_Text
•Active_Text
•Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
•Time_Delay
Notification_Class
•Alarm_Value
Event_Enable
Acked_Transitions
•Notify_Type
Event_Time_Stamps
Reliability
Yes Yes, only
user created
objects
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Trane BCI-I Integration Manual

Type
Integration Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI