1. BREAK STUD BRACKETS OFF METAL TREE AND
INSTALL ONTO WALL BOX.
INSTALL WALL BOX ONTO STUDS AND SECURE WITH
HARDWARE (BY OTHERS) AS REQUIRED.
2.
PWB-FR-450 INSTALLATION INSTRUCTIONS
APPLY FIRE-RATED SEALANT THROUGH FLANGE OPENINGS AND ALSO
BETWEEN BOX FLANGE AND DRYWALL. ENSURE SEALANT OCCUPIES ALL OF
THE GAP BETWEEN THE BOX FLANGE AND THE DRYWALL MINIMUM 1/8"
THICKNESS (REFER TO SECTIONAL VIEW). WIPE ANY EXCESS SEALANT FROM
BOX FLANGE AFTER APPLICATION. USE 3M FIRE BARRIER SEALANT CP 25WB+.
6.
WALL BOX
(2) STUD BRACKET
(2) STUD BRACKET
(8) #8-32 x 1/4" LONG
PAN HEAD SCREW
USE APPROPRIATE HOLES
ON STUD BRACKET TO SECURE
WALL BOX TO WOOD STUDS WITH
#6 x 1" OR LARGER SCREWS
(BY OTHERS) AS REQUIRED
(MINIMUM 3 SCREWS PER BRACKET)
RIM
(4) #8-32 x 1/2" LONG
PAN HEAD SCREW
COVER
(4) #6-32 x 3/8" LONG
PAN HEAD SCREW
DRYWALL
DRYWALL
BOX FLANGE
DRYWALL FIRE-RATED SEALANT DRYWALL
7. COVER HAS TO BE REMOVED FROM RIM BEFORE
RIM CAN BE INSTALLED TO WALL BOX.
11-7/16" CUTOUT
9-5/8"
CUTOUT
FLANGE OPENING
WOOD STUD MOUNTING METAL STUD MOUNTING
WOOD STUD METAL STUD USE APPROPRIATE HOLES
ON STUD BRACKET TO SECURE
WALL BOX TO METAL STUDS WITH
#6 x 1/2" OR LARGER SHEET METAL
SCREWS (BY OTHERS) AS REQUIRED
(MINIMUM 3 SCREWS PER BRACKET)
MINIMUM TWO STUDS REQUIRED 16" ON CENTER.
ADDITIONAL STUDS MAY BE ADDED AS NEEDED.