Application sheet
SpeedUp
Laminate
Strongboard tile and laminate
1
2
3
4
5
1 Laminate ≥ 8 mm
2 Strongboard tile and laminate 5 mm
3 SpeedUp heat panel + FH composite pipe 30 mm
4 Support batten (30mm)
5 Additional insulation EPS 035 DEO 20 mm
6 SpeedUp perimeter insulation
7 If necessary construction sealing
Floor nish ≥ 8 mm Laminate; strength without subsonic noise lamination
Construction height ≥ 63 mm Height including oor nish
Weight ~ 16 kg / m² Weight including oor nish
Thermal resistance R 1,43 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,63 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 2,0 kN Sum point load ≤ design load; please notice special heavy ob-
jects (aquaria etc.)
Impact subsonic noise reduction NA dB
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3. Oce spaces, hallways in oce
buildings, medical oces, stations and spaces with human occupancy, and commercial
spaces with oor areas up to 50 m² in residential or oce buildings. Corresponds to
categories B1, D1 and D2 of DIN 1055-3.
Requirements & special features
A level, smooth and structurally sound surface is necessary for full surface contact with
the heating elements (elevated requirements according to DIN 18202 Table 3, row 4).
Supply / return panels and cut panels (insulation panels or SpeedUp panels) must be
glued to the substrate and to each other. The R value must be increased if the ground-
water level is less than or equal to 5 m. A U value not exceeding 0.5 W/m²K must be
maintained in existing buildings and additions with areas up to 50 m². Strongboard
is used under the laminate as a structural and subsonic noise reduction layer. Protect
laminate against moisture penetration from below if necessary (vapour barrier). Observe
all installation instructions and manufacturer’s instructions.
Additional insulation
20 mm EPS 035 DEO 200 kPa; existing buildings: 40 mm XPS 035 500 kPa
Construction
According to EnEV, EN 1264, DIN 1055, 18195 and 18202
Construction number 79
Technical Data Floors/ceilings facing unheated rooms or the ground
6
7
© Danfoss 11/2008
VA.CR.M1.02