  • Hello! I am an AI chatbot trained to assist you with the Danfoss EVR/EVRA 32-40 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
A
B
Installation Guide
© Danfoss A/S (AC-MCI / jmn), 2012-12 DKRCC.PI.BB0.E1.02 / 520H6988 1
032R9521
032R9521
Solenoid Valve
Types EVR 32, EVR 40, EVRA 32, EVRA 40
Refrigerants
EVR: R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
For other refrigerants, please contact Danfoss.
EVRA: R717, R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
For other refrigerants, please contact Danfoss.
Max. 150 °C (300 °F)
Max. 700 °C (1300 °F)
Max. 150 °C (300 °F)
EVRA 32, EVRA 40EVR 32, EVR 40
EVR / EVRA
[Nm] [kpm] [ft-lbs]
1.4 0.15 1
EVR 32, EVR 40 EVRA 32, EVRA 40
a.c. ~ a.c. ~
12 W a.c. ~
20 W d.c. –
a.c. ~
EVR 32, EVR 40 EVRA 32, EVRA 40
EVR 32, EVR 40, EVRA 32, EVRA 40
Min. medium temperature -40 °C (-40 °F) -40 °C (-40 °F)
Max. medium temperature 105 °C (220 °F) 105 °C (220 °F)
Max. working pressure PS = 28 bar/MWP = 405 psig PS = 28 bar/MWP = 405 psig
Max. opening di. pressure (MOPD)
[Nm] [kpm] [ft-lbs]
A 12 1.2 9
B 50 05.0 37
10 W a.c.
t
max.
80 °C
(175 °F)
10/12 W a.c.
t
max.
80 °C
(175 °F)
20 W d.c.
t
max.
50 °C
(120 °F)
2 DKRCC.PI.BB0.E1.02 / 520H6988 © Danfoss A/S (AC-MCI / jmn), 2012-12
EVRA 32, EVRA 40
EVRA 32, EVRA 40
EVR 32, EVR 40
EVR 32, EVR 40
Coil and O-ring
A
B
Warning
Never switch on power to
the coil when the coil is
dismounted from the valve.
Otherwise the coil may be
damaged and there is risk of
injuries and burns.
A: Be sure that the O-ring
is inplace
B: Sticker applies only
to UL products
/