Installation Guide
Solenoid Valve
Types EVR 25, EVRA 25
© Danfoss A/S (AC-MCI sw) 2013 - 04 DKRCC.PI.BB0.G5.02 / 520H7542 1
032R9520
032R9520
Refrigerants
EVR: R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
EVRA: R717, R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
For other refrigerants, please contact Danfoss.
Max. 150 °C (300 °F)
Max. 700 °C (1300 °F)
Max. 150 °C (300 °F)
Clip-on coil
EVR 25 EVRA 25
a.c. ~ a.c. ~
12 W a.c. ~
20 W d.c. –
a.c. ~
EVR 25
EVRA 25
EVR 25
EVRA 25
Nm kpm ft-lbs
1.4 0.15 1
10 W a.c. t
max.
80 °C (175 °F)
10 / 12 W a.c. t
max.
80 °C (175 °F)
20 W d.c. t
max.
50 °C (120 °F)
Warning
Never switch on power
to the coil when the coil
is dismounted from the
valve. Otherwise the
coil may be damaged
and there is risk of
injuries and burns.
Medium temperature:
EVR 25 / EVRA 25 Min. -40 °C (-40 °F) Max. 105 °C (221 °F)
Max. working pressure:
EVR 25 PS / MWP = 28 bar (405 psig)
EVRA 25 PS / MWP = 42 bar (600 psig)
Max. opening di. pressure (MOPD)