Installation guide
Solenoid valve
Types EVR 2 - EVR 22 (NC/NO)
032R9549
032R9549
© Danfoss | DCS (rja) |2016.02
DKRCC.PI.BB0.X1.22 | 1
Coil and O-ring
Danfoss
68F503.12
A
B
A: Be sure that the O-ring
is inplace
B: Sticker applies only
to UL products
Refrigerants:
R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
For other refrigerants, contactDanfoss.
EVR (NC are) EVR (NC solder) EVR (NC ange) EVR (NO solder)
Note:
tube construction
max. 212 °F
On
O
max. 1300 °F
EVR 2 – EVR 8 [psig] EVR 10 [psig] EVR 15 – EVR 22 [psig]
Max. working pressure PS/MWP 655 508 460
Max. operating diential pressure (MOPD) Coil dependent
Media temperature
Min. medium temperature t
min.
= -40 °F
Max. medium temperature t
max.
= 221 °F
Max. coil temperature
9 W AC (EVR 2) t
max.
= 105 °F
10/12 W AC t
max.
= 175 °F
20 W DC t
max.
= 120 °F
10 W AC t
max.
= 130 °F
Warning
Never switch on power
to the coil when the coil
is dismounted from the
valve. Otherwise the coil
may be damaged and
there is risk of injuries
and burns.
Mounting directions
Flare mounting
Mounting / dismounting coil
Soldering