Danfoss EVR 2 - 20 for Hydrocarbons Normally Closed (NC), EVR 6 - 20 Normally Open (NO) Installation guide

Type
Installation guide
Installation guide
Solenoid valves
Type EVR 3 - 20 for hydrocarbons, Normally Closed (NC)
© Danfoss A/S (AC-MCI sw) 2013-04 DKRCC.PI.BY0.A5.02 / 520H7596 1
032R9546
032R9546
Refrigerant:
R290, R600, R600a
Medium temperature:
T
min
: -20 °C (-4 °F)
T
max
: 105 °C (221 °F)
Max. working pressure:
PS/MWP:
EVR 2-10: 35 bar (508 psi)
EVR 15-20: 32 bar (464 psi)
Max. opening di. pressure:
(MOPD) 21 bar (305 psi)
EVR 3 (NC) EVR 6, 10 (NC) EVR 10-20 (NC)
Earth
Only use coils for zone II ( EEx nA II T3). Always install with fuse ahead of coil.
Clip-on
1
Never switch on power to the coil when the coil is
dismounted from the valve. Otherwise the coil may
be damaged and there is risk of injuries and burns.
11 W a.c
13 W a.c
14 W a.c ~
20 W d.c --
4
3
2
Danfoss
32F902.10
Danfoss
32F901.10
Danfoss
32F900.10
EVR 3 (NC) EVR 6 (NC) EVR 10 - 20 (NC)
2 DKRCC.PI.BY0.A5.02 / 520H7596 © Danfoss A/S (AC-MCI sw) 2013-04
EVR 6 - 20
Type Nm kpm ft-lbs Torx size
EVR 3 1.4 0.15 1 T 15
EVR 4
EVR 6,
EVR 8
2.0 0.2 1.8 T 20
Type Nm kpm ft-lbs Torx size
EVR 10
EVR 15
EVR 18
2.8 0.3 2 T 25
EVR 20 12 1.2 9 T 40
Service
  • Page 1 1
  • Page 2 2

Danfoss EVR 2 - 20 for Hydrocarbons Normally Closed (NC), EVR 6 - 20 Normally Open (NO) Installation guide

Type
Installation guide