EVR 2 - 20 for Hydrocarbons Normally Closed (NC), EVR 6 - 20 Normally Open (NO)

Danfoss EVR 2 - 20 for Hydrocarbons Normally Closed (NC), EVR 6 - 20 Normally Open (NO) Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss EVR 2 - 20 for Hydrocarbons Normally Closed (NC), EVR 6 - 20 Normally Open (NO) Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Installation guide
Solenoid valves
Type EVR 3 - 20 for hydrocarbons, Normally Closed (NC)
© Danfoss A/S (AC-MCI sw) 2013-04 DKRCC.PI.BY0.A5.02 / 520H7596 1
032R9546
032R9546
Refrigerant:
R290, R600, R600a
Medium temperature:
T
min
: -20 °C (-4 °F)
T
max
: 105 °C (221 °F)
Max. working pressure:
PS/MWP:
EVR 2-10: 35 bar (508 psi)
EVR 15-20: 32 bar (464 psi)
Max. opening di. pressure:
(MOPD) 21 bar (305 psi)
EVR 3 (NC) EVR 6, 10 (NC) EVR 10-20 (NC)
Earth
Only use coils for zone II ( EEx nA II T3). Always install with fuse ahead of coil.
Clip-on
1
Never switch on power to the coil when the coil is
dismounted from the valve. Otherwise the coil may
be damaged and there is risk of injuries and burns.
11 W a.c
13 W a.c
14 W a.c ~
20 W d.c --
4
3
2
Danfoss
32F902.10
Danfoss
32F901.10
Danfoss
32F900.10
EVR 3 (NC) EVR 6 (NC) EVR 10 - 20 (NC)
2 DKRCC.PI.BY0.A5.02 / 520H7596 © Danfoss A/S (AC-MCI sw) 2013-04
EVR 6 - 20
Type Nm kpm ft-lbs Torx size
EVR 3 1.4 0.15 1 T 15
EVR 4
EVR 6,
EVR 8
2.0 0.2 1.8 T 20
Type Nm kpm ft-lbs Torx size
EVR 10
EVR 15
EVR 18
2.8 0.3 2 T 25
EVR 20 12 1.2 9 T 40
Service
/