Legrand HPCP3BC (HPCU3BC and HPSA) Basic Outdoor Controller - Installation guide

Type
Installation guide
Installation Instructions
Santa Clara, CA 95050 © 2001 The Watt Stopper,
®
Inc.
HPCP3BC (HPCU3BC and HPSA)
Basic Outdoor Controller
Installation and Setup
The HPCU3BC Basic Outdoor Controller is an
intelligent component for simple control of
exterior lighting. It must be used in conjunction
with the HPSA Photocell Sensor. HPCP3BC is a
package combining both the controller and the
sensor.
The HPCU3BC accepts two inputs: the HPSA sensor,
which provides exterior daylight levels, and an
additional dry contact input which indicates normal
building occupancy. The controller also provides three
intelligent outputs, each dedicated to one type of
outdoor lighting: Security, Parking and Signage. Each
output can drive up to three relays in parallel.
The HPCU3BC provides built-in intelligent scenarios
for each type of outdoor lighting. Each output has its
own adjustable set point to indicate what level of
daylight (or darkness) should trip the lighting on.
The HPCU3BC is designed for use with Reliant Relay
H2R series or GE RR series relays installed in a
Horton Controls lighting control panel or an accessory
cabinet as detailed on the following page.
Features
Built-in intelligent scenarios for outdoor lighting
Three intelligent outputs for three types of outdoor
lighting
User-selectable ranges for three independent light
levels
Built in “deadband” to avoid nuisance switching
Optional egress delay for parking lot lighting
“Occupied” contact to indicate normal working
hours
Before proceeding, read the enclosed installation
instructions. If you have any questions, call our
Service Team at: 888-852-2778.
Shown above: HCPU3BC Control Unit and HPSA Photocell Sensor
2
HPCP3BC Basic Outdoor Controller Installation and Setup
CAUTION: Make sure all power to the
lighting control panel is off before
wiring. Do not energize wiring until
the units are fully assembled. Conform
to all applicable codes.
Basic Installation Steps
Detailed installation instructions follow.
1 Install the photocell sensor on the roof
2 Mount the control unit in the lighting
control panel or accessory cabinet
3 Wire the sensor to the photocell input
4 Wire 24 VAC power to power input
5 Wire intelligent outputs to relays to be
controlled
6 Connect a timeclock, switch or other
input to occupied contact
7 Select light levels and parking lot
egress delay
8 Test operation
Install the Sensor
(You may wish to install the photocell
sensor last, but wire it to the panel in the
electrical closet for testing as described
on page 4).
Mount the HPSA Photocell Sensor on
the outside of a weathertight junction
box on the building roof, facing toward
the northern sky as illustrated in Figure
1. Make sure the sensor lens is not
subject to shadows or directly aimed at
parking lot lights. In areas subject to
snow, the sensor must be mounted 12
inches above the snow line.
Mount the Control Unit
There are two recommended ways to
install the HPCU3BC controller:
1 In a Lighting Control Panel. A com-
plete panel assembly includes the
following components:
Tub (HTUB12/24/48)
Cover (HCVR12xx/24xx/48xx)
Interior* (HIN series)
Power Supply (HPSM115/277)
Relays (Reliant Relay H2R7P/9P or
GE RR7P/9P )
2 In an Accessory Cabinet next to the
lighting control panel. Order HSMC2
*
12- and 24-relay interiors each hold one or two
controllers on the accessory bracket. A 48-relay
interior holds 1 to 4 controllers.
Note: Be certain to observe proper
polarity, or the controller will not
operate properly.
Wire the Intelligent
Outputs
The HPCU3BC Controller has three
Intelligent Outputs labeled Security,
Parking and Signage. Each intelligent
output may be wired to drive either:
1 A single relay in the lighting control
panel
2 A group of relays hardwired in parallel
in the panel
Figure 2 – HPSA Dimensions
** The HPCU3BC controller is simplest to install
when used with a Horton Controls Smartwired
Contactor or Smartwired
Switching System
interior, due to their intelligent channel inputs for
grouping relays.
surface-mount accessory cabinet with
cover, which holds up to four (4)
HPCU3BC control inits.
Details for assembling a complete
Lighting Control Panel are outlined
separately in installation instructions for
Watt Stopper interiors (INHINBC,
INHINSC, INHINSS and INHINCC).
Once the panel is assembled and relays
are connected to the motherboard, the
HPCU3BC may be mounted in the low
voltage section of the panel on the
accessory bracket or in the separate
accessory cabinet, and wired as detailed
below.
Wire the Sensor to the
Control Unit
Run 3-conductor 20 AWG wire from the
HPSA photocell sensor back to the
panel and terminate on the HPCU3BC
controller as illustrated in Figure 3.
Wire 24 VAC Power
Using 2-conductor 20 AWG wire,
connect the 24VAC and WHITE power
input terminals on the HPCU3BC to the
24VAC and WHITE accessory power
terminals on the lighting control panel
motherboard.
Figure 1 – HPSA Photocell Sensor Wiring
3-CONDUCTOR
20 AWG
1000 FT. MAX.
WEATHERTIGHT
JUNCTION BOX
0.5 INCH
THREADED
INLET
12 INCHES
ABOVE
SNOW LINE
HPSA
1.30 (33)
1.86
(47)
inches (millimeters)
0.5" THREAD
3
HPCP3BC Basic Outdoor Controller Installation and Setup
working hours (closed contact) or after
hours (open contact). It may be wired to
a wall switch, a timeclock or other
building automation system as shown in
Figure 3.
Select Light Levels
Each output has an associated dial to
set the desired light level at which the
lighting group should be switched on or
off. (There is a deadband of approxi-
mately 5 seconds to avoid nuisance
switching).
As the label on the unit indicates, the
light levels for Security and Parking may
be set on the dial from 1 (2 fc) to 10 (20
fc) in 2 footcandle increments. Signage
3 An intelligent input in a lighting control
panel, such as a Channel in an SC or
SS System panel.**
See INHINSC or INHINSS installation
instructions.
Determine which relays or intelligent
inputs are to be controlled by each
output. Wire from the output RED,
BLACK and WHITE terminals to the
corresponding terminals in the lighting
control panel as shown in Figure 3.
Wire the ‘Occupied’
Contact
The occupied contact accepts a dry
contact input to indicate when the
building is operating under normal
levels may be set from 1 (20 fc) to 10
(200 fc) in 20 footcandle increments.
Recommended settings are:
Security 6 fc (Setting 3)
Parking 6 fc (Setting 3)
Signage 40 fc (Setting 2)
Select Egress Delay
The Parking output has an additional dial
to set the Parking Egress delay. This
time delay allows building occupants to
get to their cars in a lighted parking lot
after the building goes unoccupied. The
Parking Egress dial may be set from 0
(15 minutes) to 8 (2 hours) in 15-minute
increments. Setting 9 on the dial
provides a one-minute test.
24 VAC
YELLOWRED BLACK WHITE
1
“OCCUPIED” CONTACT
RELAY
TO HPSA ON ROOF
SECURITY
LIGHTING LEVEL
PARKING
LIGHTING LEVEL
PARKING EGRESS
DELAY
SIGNAGE
LIGHTING LEVEL
TEST/OPERATE
SWITCH*
A
OUTPUTS TO RELAYS
AND/OR SMART INPUTS SUCH AS
CHANNEL TERMINALS ON
SC OR SS PANEL
RED
RED
BLACK
WHITE
WHITE
WHITE
RED
BLACK
RED
BLACK
BLUE
*Must be in OPERATE position for normal operation.
2-CONDUCTOR 20 AWG 1000 FT. MAX.
Figure 3 – HCPU3BC Basic Outdoor Controller Wiring
Panel Division 888-852-2778 INHPCPBC 062801
HPCP3BC Basic Outdoor Controller Installation and Setup
Test Operation
When all wiring and settings are complete,
restore power to the lighting panel.
Test the expected sequence of operations
in the building to ensure that all controls
are operating as intended. An example
follows. This example assumes you are
testing during daylight hours. If testing at
night, provide a light to shine at the
photocell sensor.
1 Begin with the occupied contact in the
open position (the building is unoccu-
pied). Set the PARKING EGRESS dial
to 9 for a one-minute test.
2 Test the photocell sensors responsive-
ness by sliding the PHOTOCELL
switch on the HCPU3BC unit to TEST.
Cover the sensor to simulate dark-
ness. Security lighting should turn on.
3 Close the occupied contact (the
building is now occupied). If the
photocell sensor is still covered, both
parking and signage lighting should
turn on.
4 Open the occupied contact (the
building is now unoccupied). Signage
should turn off. Parking lot lighting
should stay on for one more minute.
5 Uncover the photocell sensor. All
exterior lighting groups controlled by
this unit should turn off.
6 Return to normal operation. Slide the
PHOTOCELL switch back to the
OPERATE position. Set the PARKING
EGRESS dial to the desired time
(minimum of 15 minutes at the 0
setting). If the photocell sensor is not
yet installed on the roof, install and
wire it as shown in Figure 1 on page 2.
If you have any questions, call the
Watt Stopper Service Team at:
888-852-2778.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Legrand HPCP3BC (HPCU3BC and HPSA) Basic Outdoor Controller - Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI