2
HBMS8SS Building Management System Interface Module — Installation and Setup
Operation
In a Smartwired
™
Switching System,
relays and their associated lighting loads
may be “smartwired” — or grouped for
common control — to one of eight
channels in the relay panel, or to the
button of a dataline switch. When there
is no automation module (either a
Network Clock or BMS Interface Module)
in the network, relays may be controlled
manually by a wall switch, automatically
by a sensor, or by an interface to some
other system.
When the BMS Interface Module (or
Network Clock*) is added to the system,
the eight channels A-H have the capabil-
ity to become “global” — or system-wide
— automation groups. Relays grouped to
Channel A in Panel 01 and relays
grouped to Channel A in Panel 02 can
be controlled as a single global group.
With the BMS Interface Module, the user
may assign an automation “scenario” to
any channel. The type of scenario
chosen depends on how the building
space is to be used.
Questions the user should ask include:
• Is it an interior or exterior space?
• Should occupants turn lights on when
they arrive, or should lights turn on
automatically?
• Do occupants need to be warned
when lights are about to turn off?
• Should exterior lighting stay on all
night, or turn off after the building is
closed?
On the HBMS8SS, each channel has its
own connection to an external source —
whether that’s the building’s HVAC
system, security system, or some other
source of scheduling input — with both
input contacts and status feedback
contacts.
The input contacts are user-definable, and
through a simple contact closure provide
“Occupied” or “Unoccupied” status to the
BMS Interface module. With this informa-
tion, the HBMS8SS will control the lighting
based on the smart scenarios selected
by the user.
Since there are a total of eight global
channels, careful thought must be given
to which groups of relays share common
scheduling and automation scenarios.
Automation Scenarios
Each channel may be assigned any one
of four different automation scenarios as
follows:
Interior Lighting
Scenario 1: Scheduled ON/OFF
(Interior Lighting)
Relays smartwired to channels assigned
this scenario will turn on whenever the
channel’s input contact signals “Occupied”,
and off when it signals “Unoccupied.” As
an option, the lights will blink to alert
occupants five minutes before the lights
turn off. Any HDLS series dataline switch
button controlling affected relays will also
begin to flash. Pressing the switch button
will stop the flashing and start a timed
delay for that relay, overriding the off
command. An egress delay up to 4 hours
may also be set for the channel.
Data required by the BMS Interface Module:
A Override time delay (in 10-minute
increments, up to 4 hours)
B Blink Warn? Yes/No
C Egress Time (in 10-minute increments,
up to 4 hours)
D Define “Occupied” for Input Contact
(Occupied = Open or Closed contact)
E Define Status Contact (Closed contact
= Any ON, All ON, All OFF, Any OFF)
Scenario 2: Manual ON/Scheduled OFF
(Interior Lighting – Alternate)
Relays smartwired to channels assigned
this scenario will not turn on until turned
on by an occupant, even if the channel’s
input contact signals “Occupied.” During
Unoccupied periods, this scenario acts
the same as Scenario 1 and requires the
same data input.
Exterior Lighting
The following two scenarios for exterior
lighting appear automatically as menu
selections in the HBMS8SS when an
HPCU8SS Photocell Control Module is
connected to the system. Programming
scenarios for the channels is still done
through the HBMS8SS.
The Photocell Control Module receives
actual light level data from the HPSA
Photocell Sensor mounted on the
building’s roof and wired to the HPCU8SS.
(For testing, a simulated light level
function is available.)
For details on the Photocell Control
Module, refer to the installation instruc-
tions INHPCU8.
Scenario 3: Dark ON/OFF
(Exterior Lighting – Security)
Relays smartwired to channels assigned
this scenario will turn on when it is dark
outside and turn off when it is light. “Dark”
is defined by the user in footcandles.
Typical settings for Security lighting are
from 2 to 20 fc.
Data required by the BMS Interface Module:
A Define “Dark” from 2 to 200 fc
B Define Status Contact (Closed contact
= Any ON, All ON, All OFF, Any OFF)
Scenario 4: Dark ON/Scheduled OFF
(Exterior Lighting – Parking Lots, Signs)
Typical settings for Parking Lot lighting
are from 2 to 20 fc, and for Signage, 20
to 200 fc. Egress Time is the delay
between the Unoccupied signal and the
time the lights should actually turn off. It
is used to allow safe exit for the last
building occupants.
Data required by the BMS Interface Module:
A Egress Time (in 10-minute increments
up to 4 hours)
B Define “Dark” from 2 to 200 fc
C Define “Occupied” for Input Contact
(Occupied = Open or Closed contact)
D Define Status Contact (Closed contact
= Any ON, All ON, All OFF, Any OFF)
* Only one Network Clock or BMS Interface Module
can be used in a single Smartwired Switching
network to provide smart control scenarios. If the
HBMS8SS module is the primary controller, an
HCLK8SS Clock module should not be connected
to the dataline, but may be used in Programming
mode to program dataline switches.