GE RPS12 is a powerful and versatile lighting control solution that offers a wide range of features and capabilities. With its ability to control up to 12 individual relay outputs, each of which can drive up to three relays in parallel, the RPS12 provides flexible and scalable lighting control for a variety of applications. The device's 12 individual switch inputs, which can accept any 2- or 3-wire switch, allow for easy integration with existing lighting systems and provide precise control over individual lights or groups of lights.

GE RPS12 is a powerful and versatile lighting control solution that offers a wide range of features and capabilities. With its ability to control up to 12 individual relay outputs, each of which can drive up to three relays in parallel, the RPS12 provides flexible and scalable lighting control for a variety of applications. The device's 12 individual switch inputs, which can accept any 2- or 3-wire switch, allow for easy integration with existing lighting systems and provide precise control over individual lights or groups of lights.

Catalog Number: RSP12
Installation Instructions
IMRSP12
DESCRIPTION
FEATURES
Remote Control Smart Sweeper
Total Lighting Control
The Remote Control Smart Sweeper
is an intelligent
component for simple lighting control. It provides 12
individual switch inputs and one Master input for a group
of 12 relays. Each input will accept any 2- or 3-wire
switch. The RSP12 converts any switch input to a
momentary output to drive the corresponding relay(s).
Each output can drive up to three relays in parallel.
The RSP12 also provides several advanced functions for
basic lighting automation. Besides the Master ON/OFF
function, it allows options for Time Delay and Flick
Warning for individual overrides, as well as Automatic
ON for all lights.
The RSP12 should be installed in a lighting automation
panel or an accessory cabinet as detailed on the
following page.
12 individual relay outputs, with up to 3 relays wired
in parallel per output.
12 individual switch inputs (one per relay) and one
Master input.
Inputs accept any 2- or 3-wire switch (dry contact).
Master ON/OFF control for group of relays while
retaining individual switch override.
Additional control of subgroups by tying any
combination of inputs together.
“Occupied” contact to indicate normal working hours.
Option to turn lights on automatically at start of
normal working hours.
Time delay in 15-minute increments up to 2 hours.
Option to “flick warn” occupants 5 minutes before
lights go off.
Before starting, read the installation instructions inside.
If you have questions call GE Service at:
1-877-584-2685 (USA) or 1-800-661-6619 (Canada)
R
L
Y
1
RED
WHITE
BLACK
MASTER
RSP12
HORTON CONTROLS COPYRIGHT 1995
437D687 REV 0
RED
BLACK
BLUE
R
L
Y
2
RED
BLACK
BLUE
R
L
Y
3
RED
BLACK
BLUE
R
L
Y
4
RED
BLACK
BLUE
R
L
Y
5
RED
BLACK
BLUE
R
L
Y
6
RED
BLACK
BLUE
R
L
Y
7
RED
BLACK
BLUE
R
L
Y
8
RED
BLACK
BLUE
R
L
Y
9
RED
BLACK
BLUE
R
L
Y
1
0
RED
BLACK
BLUE
R
L
Y
1
1
RED
BLACK
BLUE
R
L
Y
1
2
ASM 437D688G
RED
BLACK
WARN
YES
NO
TIME DELAY
AUTO ON
YES
NO
BLUE
S
W
T
1
2
RED
BLACK
WHITE
S
W
T
1
1
RED
BLACK
WHITE
S
W
T
1
0
RED
BLACK
WHITE
S
W
T
9
RED
BLACK
WHITE
S
W
T
8
RED
BLACK
WHITE
S
W
T
7
RED
BLACK
WHITE
S
W
T
6
RED
BLACK
WHITE
S
W
T
5
RED
BLACK
WHITE
S
W
T
4
RED
BLACK
WHITE
S
W
T
3
RED
BLACK
WHITE
S
W
T
2
RED
BLACK
WHITE
S
W
T
1
RED
BLACK
WHITE
1
O
N
2
0
BLACK
POWER
24VAC
RED
BLACK
OCCUPIED
RED
WHITE
ACC.
24VRECT
BLUE
Catalog Number RSP12
Description
Remote Control Smart Sweeper
Converts 2- or 3-wire switch inputs to momentary outputs.
Each switch input drives corresponding relay output.
Master Switch controls all 12 outputs.
Installation
Wire 24VAC power to Power Input.
Connect up to 3 relays to each Relay Output.
Wire any 2- or 3- wire switch to Switch Inputs, including
Master Switch, if desired.
Occupied –
Close contact during normal working hours.
Opening contact turns OFF all relays and enables time delays.
• Time Delay – Set dial in 15-minute increments (1=15min.
to 8=2 hrs. 9=1 min. test). After "occupied" hours, any
relays manually switched ON will automatically turn OFF
after the set amount of time.
• Warn – Lights "flick" 5-minutes before turning OFF at 
end of day or time delay (YES or NO).
• Auto On – Lights turn ON automatically at start of normal
working hours (YES) or require manual switch ON (NO).
LISTED 533F
ENERGY MANAGEMENT
EQUIPMENT SUBASSEMBLY
Service: 1-800-884-4852
GE Wiring Devices
Warwick, RI
Made in U.S.A.
POWER INPUT
24VAC
ACCESSORY PWR
24V RECT
MASTER SWITCH
INPUT
GE Total Lighting Control
R
SWITCH INPUTS
1 12
Catalog Number: RSP12
FEATURE SUMMARY
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
RED
BLACK
BLUE
24VRECT ACC
BLUE WHITE
MASTER
RED BLACK WHITE
24VAC POWER
RED BLACK
WARN
YES
NO
AUTO ON
YES
NO
OCCUPIED
RED WHITE
0
*The 24 volt AC inputs can be used if connecting directly to a transformer.
24 Volt Power Inputs
The RSP12 can be
powered through the
24 volt rectified
terminals on the
Lighting Automation
Panel motherboard*
Master Switch Input
Master ON/OFF control
for all connected relays
12 Individual
Relay Outputs
Connect up to 3 relays
wired in parallel per
output
“Auto On” Function
Can turn on all lights
automatically at the start
of normal working
hours
“Time Delay” Function
After hours, any
individual switch over-
ride will automatically
be turned off if time
delay is set from 15
minutes to 2 hours
12 Individual
Switch Inputs
Accept any 2- or
3-wire momentary
or maintained
dry-contact
switch
“Occupied” Contact
Connected to a
timeclock or BAS,
indicates when a
building is operating
under normal working
hours (closed contact)
or after hours (open
contact). Connection
and scheduling
determine when other
functions will be
enabled
“Warn” Function
Five minutes before the
RSP12 is about to turn
relays OFF at the end of
normal working hours or
at the end of a time
delay, warns occupants
by blinking the lights
Catalog Number: RSP12
RSP12
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
RED
BLACK
WHITE
MAINTAINED
ISOLATED
CONTACT
2-WIRE
MOMENTARY
PUSH BUTTON
STANDARD
3-WIRE
MOMENTARY
STANDARD
3-WIRE
MAINTAINED
20/2 AWG 1000 FT. MAX.
20/2 AWG 1000 FT. MAX.
20/3 AWG 1000 FT. MAX.
20/3 AWG 1000 FT. MAX.
JUMP RED TO BLACK
JUMP BLACK TO WHITE
12-RELAY 
LIGHTING
AUTOMATION
PANEL
24-RELAY LIGHTING
AUTOMATION PANEL
48-RELAY LIGHTING
AUTOMATION PANEL
RSP12
RED
BLACK
BLUE
ON TLC PANEL
MOTHERBOARD
YELLOWRED BLACK WHITE
1
RRxP RELAY
LOAD
CIRCUIT
20/2 AWG
24VRECT ACC
BLUE WHITE
24V
RECT
BLUE
PILOT
COMMON
YELLOW
24VAC COM
2
4V
RECT
BLUE
ON TLC PANEL
MOTHERBOARD
18/2 AWG
RSP12
INSTALLATION
CAUTION: The power supply must be OFF when
inserting or removing components. These instructions
assume the panel has a standard cover which exposes
both line-voltage and low-voltage sections. The line-
voltage sections must be covered to avoid exposure to
live high-voltage wiring.
There are two recommended ways to install the RSP12
Remote Control Smart Sweeper — in a Lighting
Automation Panel (LAP) or in an Accessory Cabinet near
a Lighting Automation Panel
Installation in a Lighting Automation Panel
A complete LAP assembly includes the following TLC
components:
Tub RTUB12, -24 or -48
Cover RCOV12xx, -24xxx or -48xxx
Interior RINTER0012RC, -0024RC or -0048RC*
Power Supply RPWRxxx
Relays RR7P or RR9P
* RINTER0012RC and -0024RC accept one RSP12, RINTER0048RC accepts one or two
Details for assembling a complete Lighting Automation
Panel are outlined separately in the RINTER installation
instructions. Once the panel is assembled and relays are
connected to the motherboard, the RSP12 may be
installed.
Basic Installation Steps
1. Mount the RSP12(s) on the panel accessory bracket.
2. Wire 24V rectified power from the panel motherboard
to the blue and white power input tabs on the RSP12.
3. Wire red and black connections for each relay from
the panel motherboard to relay outputs on the RSP12.
4. Wire any 2- or 3-wire switch to the individual switch
inputs and/or the Master switch input on the RSP12
(not on the panel motherboard).
5. Select additional control functions.
Installation in an Accessory Cabinet near the LAP
Accessory cabinets with covers include:
RBS1 Accepts one (1) RSP12
RBS2 Accepts two (2) RSP12s
Mount the RSP12 in the accessory cabinet and wire the
same as above.
2.
WIRE
24 VOLT
RECTIFIED
POWER
4. WIRE ANY 2- OR 3-WIRE SWITCHES
1. MOUNT RSP12 IN PANEL
3.
WIRE
RELAYS
Catalog Number: RSP12
GE Lighting Controls, 41 Woodford Ave., Plainville, CT 06062
Made in U.S.A.
EMERGENCY SERVICE OR SUPPORT:
1-877-584-2685 (USA) or 1-800-661-6619 (Canada)
RSP12
0
WARN
YES
NO
AUTO ON
YES
NO
OCCUPIED
RED WHITE
WARN
YES
NO
O
N
1
RSP12
0
WARN
YES
NO
AUTO ON
YES
NO
OCCUPIED
RED WHITE
AUTO ON
YES
NO
2
RSP12
0
WARN
YES
NO
AUTO ON
YES
NO
OCCUPIED
RED WHITE
0 = NO TIME DELAY
1 = 15-MINUTE DELAY
2 = 30-MINUTE DELAY
3 = 45-MINUTE DELAY
…ETC. TO…
8 = 2-HOUR DELAY
9 = 1-MINUTE TEST
0
ADDITIONAL CONTROL FUNCTIONS
Four optional control functions are available at the
bottom of the RSP12 board: Occupied, Time Delay, Warn
and Auto Off. Set these functions for all relays connected
to the RSP12 as a group, based on the needs at the site.
Occupied
The Occupied contact is available for connection with a
timeclock or building automation system. It indicates
when the building is operating under normal working
hours (CLOSED contact) or after hours (OPEN contact).
Properly connecting and scheduling the Occupied
contact determines when other functions will be enabled.
Time Delay
If the Time Delay function is set, when an occupant turns
on a switch after hours (Occupied contact OPEN), the
RSP12 will turn off the lights again after a predetermined
amount of time. Each occupant override will have its own
time delay.
Set the Time Delay dial as follows:
0 No time delay (no automatic off; lights must be
manually turned off)
1-8 15-minute to 2-hour delay, in 15-minute
increments
9 1-minute test
Warn
When the RSP12 turns relays OFF (at the end of normal
working hours, or at the end of a time delay), it will
optionally warn the occupants by blinking the lights five
minutes before they go off.
Set the WARN switch to YES or NO as follows:
YES Gives a 5-minute warning before lights turn off
NO Turns lights off without giving the warning
Auto On
When the Occupied contact closes at the start of normal
working hours, the RSP12 can optionally turn all the
relays ON automatically.
Set the AUTO ON switch to YES or NO as follows:
YES Automatically turns all relays ON at start of
normal working hours
NO Manual switch required to turn relays ON
OCCUPIED CONTACT
TIME DELAY
WARN SWITCH
AUTO ON SWITCH
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

GE RPS12 User manual

Type
User manual

GE RPS12 is a powerful and versatile lighting control solution that offers a wide range of features and capabilities. With its ability to control up to 12 individual relay outputs, each of which can drive up to three relays in parallel, the RPS12 provides flexible and scalable lighting control for a variety of applications. The device's 12 individual switch inputs, which can accept any 2- or 3-wire switch, allow for easy integration with existing lighting systems and provide precise control over individual lights or groups of lights.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI