Legrand SWS Contactor Panel Installation guide

Type
Installation guide
Installation Instructions
Santa Clara, CA 95050 © 2001 The Watt Stopper,
®
Inc.
HINxxy12SC/24SC/48SC
Smartwired
Contactor Panel Interior
Installation and Setup
The HINxxy12SC/24SC/48SC is the interior for a
Smartwired
Contactor Lighting Control Panel.
The interior provides isolation between the line- and
low-voltage sections of the panel, as well as the
mounting frame for relays, the power supply and
optional control devices.
A complete panel assembly also includes one each of
the following:
1. Tub (HTUB series)
2.Cover (HCVR series)
3.Power Supply (HPSM115/277)
The Smartwired Contactor provides a simple way to
group lighting circuits by function for both manual and
automatic control. For example, in a store application,
several display, showcase and general-lighting circuits
could be grouped for control by three low-voltage
switches with pilot indication. A fourth switch could
provide master control for all of the lighting and also
tie into the building automation scheduling system.
The HINxxyxxSC has separate channels for grouping
any combination of the relays (lighting circuits) in the
panel. Channel switches within the panel provide
built-in override capability. Two independent inputs per
each allow both remote manual switches and automa-
tion contacts to control that group.
Automation system distributed control modules may
be mounted within the unit to simplify wiring (requires
a separate bracket, HBRK12SC or HBRKXXSC,
which is not provided with the interior).
Before starting, read the instructions that follow. If
you have any questions, call our Service Team at:
888-852-2778.
Retain these instructions and the completed
documentation cards in the plastic sleeve affixed
to the rear of the panel cover.
2
HINxxy12SC/24SC/48SC Smartwired
Contactor Panel Interior — Installation and Setup
ILLUSTRATION NOT TO SCALE
Install Interior
Attach the power supply to the frame
(bottom of 12-relay interior and left side
of 24- or 48-relay interiors) as shown to
the left, and plug the low-voltage
connector to the terminal marked
POWER.
Mount the interior in the tub and secure
it to the studs with the hardware sup-
plied. Make sure that all line- and low-
voltage wiring is confined to the appro-
priate areas.
Wire Line Voltage
Before making any connections to the
relays, make sure that none of the load
circuits are shorted. Wire from the circuit
breaker through each relay’s SPST output
terminals, and from there to the loads.
Confirm that each circuit is wired to the
relay specified in the drawings. Wire the
power supply as shown to the left.
Tub Dimensions (AxB)
12-Relay Capacity
16.0" (406mm) x 16.5" (419mm)
24-Relay Capacity
22.5" (572mm) x 24.0" (610mm)
48-Relay Capacity
36.0" (914mm) x 24.0" (610mm)
Interior Relay Capacities (C)
HINxxy12SC 12 H2R7P, H2R9P,
RR7P or RR9P relays
HINxxy24SC 24 H2R7P, H2R9P,
RR7P or RR9P relays
HINxxy48SC 48 H2R7P, H2R9P,
RR7P or RR9P relays
Optional Accessory Mount Bracket (D)
HINxxy12SC HBRK12SC
HINxxy24SC HBRKXXSC
HINxxy48SC HBRKXXSC
xx= number of relays installed (in multiples of 4)
y= type of relay installed
Figure 1 – Dimensions and Capacities
This interior is intended for field
installation within the enclosure of
another product.
Refer to installation instructions
INHTUB and INHCVR for installation
of The Watt Stopper
®
Tubs and Covers.
The following instructions assume
that a UL listed enclosure has been
properly installed.
CAUTION: Make sure all power is off
before wiring. Do not energize wiring
until the unit is fully assembled.
Conform to all applicable codes.
B
A
A
C
C
C
CLASS 2
LOW-VOLTAGE
WIRING SECTION
LINE-VOLTAGE WIRING SECTIONS
EACH 5" WIDE
B
LINE-VOLTAGE
WIRING SECTION 4" WIDE
D
4.5" D
4.5" D
CLASS 2
LOW-VOLTAGE
WIRING SECTION
D
24- and 48-Relay Configuration 12-Relay Configuration
3
Wire Low Voltage
Remote low-voltage switches and
isolated contacts (from a timeclock or
building automation system) are wired to
the channel inputs on the panel. Each
channel will accept two inputs, each of
which may be either a 2- or 3-wire
maintained or momentary device as
shown in Figure 2.
The HINxxy12SC interior has 4 channels,
the HINxxy24SC, 8 channels and the
HINxxy48SC, 16 channels. Pages 4 and
5 show common wiring configurations.
Power Up and Test Relays
Apply power to the power supply only.
Press the Relay Control Button next to
each relay’s yellow plug-in termination to
toggle it on/off as shown in Figure 3.
The relay should “click” and the LED
status indicator should change state.
Confirm the operation by measuring the
line-voltage terminations of each relay.
Apply power to the relays. Being careful
not to touch any line-voltage wiring,
toggle each relay on/off again and confirm
that each controls the appropriate load.
Relays may be smarwired to the channels
as shown in Figure 4.
Document Wiring
Record the circuit controlled by each
relay on the Smartwired Contactor
Relay Schedule included with these
installation instructions. Also indicate
which relays are controlled by each
channel. Place the Schedule in the
plastic envelope and attach it to the
inside of the panel cover.
1 Press and hold the Channel Push Button for several seconds. The channel LED
and the LEDs for relays currently controlled by that input will begin to flash.
2 Select the relays to be controlled. The LED for each relay “smartwired” to the
channel input selected will be flashing on/off. Press the associated Relay Control
Button to add/delete that relay to/from the group.
3 Press the Channel Push Button again. The LEDs will stop flashing and the input
switch will now control the relays selected.
Test. Press the Channel Push Button to toggle the group on/off/on. The input
LED will track the last action. Now, turn off each relay in the group using the individual
Relay Control Buttons. When the last relay is turned off, the channel LED should also
go off.
Figure 4 – Smartwiring a Relay Group to a Channel
Figure 3 – Power Up and
Test Relays
Figure 2 – Wire Low-Voltage
2-CONDUCTOR 20 AWG
1000 FT. MAXIMUM
RBYW
3-CONDUCTOR 20 AWG
1000 FT. MAXIMUM
RBYW
3-WIRE
SWITCH
2-WIRE
SWITCH
RELAY
CONTROL
BUTTON
TO RELAY
LED
3
PRESS
AND
HOLD
CHANNEL
PUSH
BUTTON
PRESS
RELAY
CONTROL
BUTTON
PRESS
CHANNEL
PUSH
BUTTON
AGAIN
1
FLASHING
LED
FLASHING
LED
2
HINxxy12SC/24SC/48SC Smartwired
Contactor Panel Interior — Installation and Setup
4
Typical Wiring Diagrams
Remote Manual Switch (3-wire)
Single or multiple remote low-voltage
momentary switches may be wired to a
channel input as shown in Figure 5. For
multiple switches, a separate black/red is
required for each switch, plus a single
white common.
Remote Pilot Light Switch (4-wire)
Each channel has an associated pilot
relay rated at 1 amp. One side of each
pilot relay is connected to a yellow
common, the other to the Y terminal on
the channel terminal strip (see Figure 10).
For typical 24 volt rectified pilot lights,
connect the YEL COM to the 24VR on
the ACC. POWER terminal as shown in
Figure 6.
Master Control of Channels in
Several Panels
Channel inputs in multiple panels may
be wired in parallel as shown in Figure 7,
provided all of the power supplies are
wired to the same phase
.
Master Control of Several Channels
within a Panel
While it is permissible to jumper several
switch inputs together to form a master,
the recommended approach is to define
another channel to include all of the
relays controlled by the individual
channel switches. When this “master” is
turned on or off, all of the individual
channel switches will track appropriately.
Figure 5 – Remote Manual Switch (3-wire)
Figure 6 – Remote Pilot Light Switch (4-wire)
Figure 7 – Master Control of Channels in Several Panels
3-CONDUCTOR 20 AWG
HSSW3(P) 1000 FT. MAXIMUM
RBYW
A through H
4-CONDUCTOR 20 AWG
HPSW4(P) 1000 FT. MAXIMUM
RBYWRBYW
RBY
25-CONDUCTOR 20 AWG
HMSW25(P) 1000 FT. MAXIMUM
WHITE
24VAC
24VR
YEL COM
JUMPER
ACC POWER
4-CONDUCTOR 20 AWG
HPSW4(P) 1000 FT. MAXIMUM*
3-CONDUCTOR
20 AWG HSSW3(P)*
RBYW RBYW
Connect to ONLY ONE
pilot contact.
Both panels must be
on the same phase.
AA
*Total combined length of
HPSW4(P) and HSSW3(P)
HINxxy12SC/24SC/48SC Smartwired
Contactor Panel Interior — Installation and Setup
5
Typical Wiring Diagrams
Automation or Timeclock Control
(Isolated Contacts Only!)
Single-pole, 2-Wire Configuration
Wire as shown in Figure 8.When the
control contacts open, the channel is
turned off; when closed, it is turned on.
You may wire the control contacts to
several channels within a panel. How-
ever, as with Master Switches on the
previous page, it is better to define a
separate channel to provide the master
function. If multiple panels are controlled,
the power supplies in each must be on
the same phase.
Note: If you are trying to provide multiple
OFF sweeps to catch overrides, you
should use the 3-wire configuration
shown below and wire the timeclock to
the OFF (black) input only, or use a
timeclock with pulse outputs.
3-Wire Configuration (C-form contacts)
When wired as shown in Figure 9, closing
the red contact will turn the connected
channels on; the black contact off.
For multiple OFF sweeps, connect to the
OFF contacts only. Automatic ON with
multiple OFF sweeps requires two
separate control outputs on the timeclock
or building automation system.
The timeclock or BAS control module
may be mounted to an optional accessory
bracket, HBRK12SC or HBRKXXSC
(must be ordered separately). 24 volt AC,
40VA accessory power is provided on the
motherboard.
Figure 8 – 2-Wire Automation Input with Pilot Switch Override
Figure 9 – 3-Wire Automation Input
Figure 10 – Channel Status Pilot Contacts
RBYW
AUTO ON AUTO OFF
(OVERRIDE CAUGHT AFTER 24 HOURS.)
4-CONDUCTOR 20 AWG
HPSW4(P) 1000 FT. MAXIMUM
2-CONDUCTOR 20 AWG
1000 FT. MAXIMUM
RBYW
AUTO ON AUTO OFF
3-CONDUCTOR 20 AWG
HSSW3(P) 1000 FT. MAXIMUM
RBYW
AUTO ON MULTIPLE OFF SWEEPS
(OVERRIDE CAUGHT WITH NEXT OFF SWEEP.)
EXAMPLE: ON AT 7:00 A.M.
OFF AT 6:00 P.M., 8:00 P.M., 10:00 P.M.
3-CONDUCTOR 20 AWG
HSSW3(P) 1000 FT. MAXIMUM
4-CONDUCTOR 20 AWG
HPSW4(P) 1000 FT. MAXIMUM
PILOT
CONTACTS
YELLOW COMMON
Connected to BAS Common
for pilot light operation
AB
RBYWRBYW
4-CONDUCTOR 20 AWG
HPSW4(P) 1000 FT. MAXIMUM
HINxxy12SC/24SC/48SC Smartwired
Contactor Panel Interior — Installation and Setup
Panel Division 888-852-2778 INHINSC 072301
Relay Output Ratings
Both General Electric* RR7P/RR9P and
Reliant Relay* H2R7P/H2R9P relays
may be installed in The Watt Stopper
®
interiors, including those listed herein.
The GE R7P/RR9P relay output power
contacts are rated as follows:
20A Tungsten, 125VAC
20A Ballast, 277VAC
20A Resistive, 277VAC
1
2HP @ 110-125VAC
1
1
2HP@ 220-277VAC
The Reliant Relay H2R7P/H2R9P relay
output contacts are rated as follows:
20A Tungsten
20A Ballast
20A General use
1HP @ 120VAC, 50-60Hz
Compatibility with GE Total Lighting
Control enclosures
All The Watt Stopper
®
interiors are fully
compatible with respective GE tubs,
covers and power supplies as defined in
the table below. All The Watt Stopper
®
warranties apply whether the interior is
used in one of our enclosures or a
General Electric enclosure.
TWS GE Tub/Cover GE Power
Cat.# Cat.# Supply Cat.#
HINxxy12SC RTUB12/RCOV12xx RPWRxxx
HINxxy24SC RTUB24/RCOV24xx RPWRxxx
HINxxy48SC RTUB48/RCOV48xx RPWRxxx
In The Watt Stopper
®
interiors, the xx stands for the number
of installed relays and the y indicates the type: G for General
Electric or R for Reliant Relay.
HINxxy12SC/24SC/48SC Smartwired
Contactor Panel Interior — Installation and Setup
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Legrand SWS Contactor Panel Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI