Vallox TSK Multi 80 MC R User manual

  • Hello! I am an AI chatbot trained to assist you with the Vallox TSK Multi 80 MC R User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Manual
MANUAL
Low-energy ventilation unit with heat
recovery
Document
D2585
Valid from
15.1.2018
Updated
29.1.2018
Model
TSK Multi 50 MC
TSK Multi 80 MC
Types
3603
3602
2
MAIN PARTS
Supply air fan
Extract air fan
Post-heating radiator, electrical, 900W
(behind the supply air fan)
Vallox ProControl control panel
(ordered separately)
Vallox Capto PTC EC control hood,
Vallox X-Line PTXPMC control hood, or
Vallox X-Line PTXPAMC control hood (ordered
separately)
Bypass duct heater, electricity, 900 W (only TSK
Multi 80 MC, behind the heat recovery cell)
Heat recovery cell
Outdoor air filter F7
Outdoor air filter G4
Extract air filter G4
Automatic summer/winter damper
Safety switch
Adjusting the supply and extract air ratio
Adjusting the supply air temperature and
summer/winter function
Vallox Simple Control control panel
(ordered separately)
1
2
3
14
15
4
5
6
7
8
9
10
11
12
13
R model in the figure.
In the L model, the parts are mirrored
WARNING!
The unit is not intended for use by children under 8 or by persons with reduced sensory, physical or
mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the
unit. Such persons can use the unit under supervision, or by following the instructions of someone who
is responsible for their safety.
Vallox X-Line PTXP MC
Vallox X-Line PTXPA MC
(optional)
Vallox Capto PTCEC
(optional)
(optional) (optional)
6 9 8 5
11 12 12 4
7 2
13
15
14
1 3
3
© Vallox Oy - All rights reserved
USING THE UNIT
The fan speed of the Vallox ventilation unit is adjusted
using a four-step control (optional).
The available speed options of the control switch are 1, 2,
3, and 4:
1. Away mode. The ventilation eciency can be
temporarily reduced when the apartment is
unoccupied.
2-3. Standard mode. In standard mode, the air inside the
apartment is replaced once every two hours.
4. Boost mode. Cooking, sauna, bathing, drying of
clothes, guests, and other similar situations can
require that ventilation be increased from the
standard setting.
The fan speed can also be controlled through a separate
Vallox control hood (optional), the Vallox ProControl
control panel (optional), or directly through voltage
messages (0-11,4 V).
Vallox Simple Control control panel
Vallox ProControl control panel
The temperature of the air blown into the apartment can
be adjusted approximately between +1C and +30°C. The
unit has an automatic summer/winter function (a bypass
flap).
When the adjusted temperature is between +10°C
and +30°C, the heat recovery cell is not bypassed, i.e.
the unit is in winter mode.
In the OFF position, the unit is in the summer mode,
i.e. post-heating is turned o and the heat recovery
cell is bypassed when the outdoor temperature is
above +14°C. The heat recovery will be turned on
when the outdoor temperature falls below +1C.
In the AUTO position, the unit will operate as follows
around the year: The default post-heating setting
is +17°C. The unit will bypass the heat recovery cell
when the temperature of the outdoor air exceeds
+14°C. The heat recovery will be turned on when the
outdoor temperature falls below +12°C. During the
bypass, post-heating is turned o.
Adjusting supply air temperature
FAN SPEED ADJUSTMENT
The winter function of the ventilation
unit
The limit value has been set in the factory for freezing of
the heat recovery cell. When this limit value is exceeded,
the ventilation unit starts to defrost the heat recovery cell
by directing the outdoor air past the heat recovery cell.
The duration of the defrost cycle is 15-45 min depending
on the amount of ice accumulated in the heat recovery cell
and on the extract air flow. The factory settings ensure
optimal operation in standard living and detached house
conditions. Even though the winter operation parameters
can be adjusted for certain extreme conditions, such as
swimming pool facilities, it is always advisable to contact
Vallox maintenance services.
ADJUSTING THE SUPPLY AIR TEMPERATURE
AND SUMMER/WINTER FUNCTION
4
USING THE UNIT
FIREPLACE SWITCH
A switch with timer functions can be connected to the unit. The switch stops the
extract air fan when the fireplace is being used. NOTE! Starting up the extract
air fan can reduce the draw of the fireplace! In winter, this can disturb the winter
mode of the ventilation unit. The situation will return to normal soon after the
fireplace mode is turned o.
ADJUSTING THE SUPPLY AND EXTRACT AIR
RATIO
This function might be needed when the air flows are adjusted at the valves
during installation. The user does not need to adjust this function once
the valves have been adjusted, and indeed should not adjust it at all. A
potentiometer can be used to reduce the supply or extract air flow as required.
When the potentiometer is set roughly in the centre position, neither the supply
nor the extract air flow has been reduced. When the potentiometer is turned
anti-clockwise, the supply air flow is reduced, and when the potentiometer is
turned clockwise, the extract air flow is reduced.
The potentiometer for adjusting
the supply and extract air flows
Concealed installation
of the fireplace switch (optional)
MAINTENANCE REMINDER
If a signal light is connected to the connectors of the unit’s error relay, the unit will send a reminder of service need every
six months,. If connected, the signal light will flash every second. Sounds made by the relay can then be heard from
inside the unit. The maintenance reminder will be set o automatically when the door of the ventilation unit is opened or
the power is turned o.
The maintenance reminder can also be set o manually.
The Vallox Simple Control control panel,
and the Vallox X-Line PTXP MC and
PTXPA MC control hoods, VAK 0-11,4 VDC:
The low speed is turned on, then higher-lower-higher
- Low speed under 4 V
- High speed over 6 V
- The selected speed will always be turned on
for 1-5 seconds
Vallox Capto PTC EC control hood:
The damper is closed, then open-closed-open
Press at a 1-5 second interval.
The service reminder will only be set o if it has been activated. Refer to the maintenance instructions for the necessary
maintenance measures.
5
© Vallox Oy - All rights reserved
MAINTENANCE
TROUBLESHOOTING
Flashing
LED
Problem Correction
1 NTC sensor of the supply air from the cell
is faulty
Check the sensor and the wires, replace as required
2 NTC sensor of the extract air is faulty Check the sensor and the wires, replace as required
3 NTC sensor of the extract air is faulty Check the sensor and the wires, replace as required
4 NTC sensor of the exhaust air is faulty Check the sensor and the wires, replace as required
5 NTC sensor of the outdoor air is faulty Check the sensor and the wires, replace as required
6 The supply air fan has stopped. Check the wiring of the fan, replace the fan as required
7 The extract air fan has stopped. Check the wiring of the fan, replace the fan as required
8 EEPROM is faulty Replace the circuit board
BEFORE BEGINNING
MAINTENANCE WORK
The safety switch (S) automatically turns o the power
when the door of the Vallox TSK Multi 50/80 MC ventilation
unit is opened. Always disconnect the power plug before
starting the Vallox TSK Multi 50/80 MC ventilation unit
maintenance.
FILTERS
When the maintenance reminder becomes activated,
check the cleanliness of the filters and replace them if
required.The Vallox ventilation unit has three air filters:
Class G4 coarse filter (A) filters insects, heavy pollen
and other relatively large foreign objects out of the
outdoor air.
Class F7 fine filter (B) filters microscopic pollen and
dust particles out of the supply air.
Class G4 coarse filter (C) filters the extract air and
keeps the heat recovery cell clean.
Using original Vallox filters ensures the best operation
of the ventilation unit and the best filtering results. The
filter replacement interval depends on the ambient dust
concentration. It is recommended that the filters be
replaced every spring and autumn, or at the very least
once a year.
S
R model in the figures.
In the L model, the parts are mirrored
TROUBLESHOOTING TABLE
If the ventilation unit is aected by any of the errors listed in the table, the unit will report the error through the error
relay, signal light, and circuit board LEDS. The number of flashes indicates the nature of the error.
The error relay can be connected to remote monitoring.
NOTE! When remote monitoring is used, the signal light of the control panel cannot be turned on.
A
B
C
6
MAINTENANCE
E F
D
Location of the condensing
water outlet seen
from the side
Location of the
condensing water outlet
seen from the rear
CONDENSING WATER
In the heating season, the extract air humidity condenses
to water. In new buildings, condensation runo can form
rapidly. Condensed water must be able to freely leave the
unit. At some time before the heating season begins (e.g.
during autumn maintenance), check that the condensing
water outlets in the bottom pool are not clogged. To check
this, pour some water into the pool. Clean as required.
Water must at all times be kept out of the electrical system.
See the condensing water connections on page 15.
HEAT RECOVERY CELL
Check that the heat recovery cell (D) is clean roughly
once a year when the filters are being replaced. Clean by
washing as required.
Pull the coarse filters including the frames out of the
unit (A and C). Also remove the fine filter, if any (C).
Remove the sealing strip (E) above the heat recovery
cell in the direction of the arrow.
Once you have removed the sealing strip, pull the
heat recovery cell out of the unit.
IMPORTANT! Handle the cell carefully! For example, do
not lift the cells by the layers. The cell layers are very thin
and easily damaged.
If the heat recovery cell is dirty, clean it by immersing it in
water containing a small amount of a mild detergent. Rinse
the heat recovery cell clean with a water spray. When all
the water has drained from between the layers, push the
cell recovery cell back in place. Lastly, push the sealing
strip back in place.
7
© Vallox Oy - All rights reserved
MAINTENANCE
Fans
Check the cleanliness of the fans when servicing the filters
and the heat recovery cell. Clean the fans as required.
Fans can be removed from the unit for cleaning. The fan
blades can be cleaned with compressed air or by brushing
them gently. Do not remove or move the fan blade
balancing weights.
Removing the supply air fan, right-handed model
(The steps are mirrored for the left-handed unit)
The unit with the heat recovery cell and the filters removed
1. Remove the mounting screw of
the fan bed.
1. Remove the mounting
screwof the fan bed.
2. Remove the connector
package from the wall.
3. Separate the connectors
from each other.
2. Pull the bypass duct/
filter stand package
out of the unit and
turn to the right.
3. Disconnect the cable
of the bypass damper
motor.
4. Tilt the supply air fan to the right
and push the connectors out of
the way.
5,. Turn the fan 90° and
tilt it forward to pull it
out of the unit.
2
1
3
2
1
3
4
4
55
4.. Tilt the fan to the
left and turn 9.
5. Tilt the fan
forward to pull it
out of the unit.
Install the fan beds in a reverse order.
Removing the supply and extract air
fan
Before the supply and extract air fans are removed,
the filters and the heat recovery cell of the unit must
be removed as described above. Fan beds and the
bypass duct must be removed and reinstalled carefully
in accordance with the below instructions to prevent
damage. The small size of the unit restricts the space
available for servicing.
Removing the extract air fan, right-handed model
(The steps are mirrored for the left-handed unit)
8
VALLOX TSK MULTI 50 MC
TECHNICAL SPECIFICATIONS
Supply/extract air volumes
Volume flow rate (dm/s)
Pressure loss in ducts. Total pressure (Pa)
Combined input power of the fans (kW)
Airflow specified in the ventilation plan (m/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <2.0kW (m/s)
ED and SD are examples of pressure loss
in the supply and extract air ducts.
S = supply air
E = extract air
Air flow
measurement
points
Measurement points after
the outlet collar. The fan
curves indicate the total
pressure accounted for by
duct losses.
TECHNICAL SPECIFICATIONS
Product title
Vallox TSK Multi 50 MC R
Vallox TSK Multi 50 MC L
Product number
3462600
3462700
HVAC code
7912020
7912023
Air volumes Supply air
Extract air
49 dm3/s, 100 Pa
57 dm3/s, 100 Pa
Electrical connection 230V, 50Hz 4.5A power plug
Enclosure protection class IP34
Post-heating radiator Electric, 900W
Preheating radiator
Additional heating radiator
Fans Supply air
Extract air
0,043 kW 0,32 A EC
0,043 kW 0,32 A EC
Specific energy consumption (SEC)
in a cold climate
in a temperate climate
A+
B
Operating eciencies Annual
eciency
Supply air eciency
Specific Fan Power (SFP)
75% A+
85%
1.2 (25 dm3/s) B
Filters Supply air
Extract air
G4 + F7
G4
Heat recovery bypass Automatic
Dimensions (w x h x d) and weight 900 x 236 x 547, 45 kg
FAN INPUT POWER
Fan speeds
With the SC control
panel (V)
Extract air flow
(50 Pa) dm/s
Combined input power
of the fans (W)
3 - 11
4 ≈6 15
5 16 20
6 25 26
7 33 37
8 42 49
9 49 65
10 56 87
11.4 62 108
300
250
200
150
100
50
0
0 10 20 30 40 50 60 70 80
S 3,0 V
S 4,0 V
E 3,0 V
E 4,0 V
S 5,0 V
S 6,0 V
S 7,0 V
S 8,0 V
S 9,0 V
S 10,0 V
S 11,4 V
E 5,0 V
E 6,0 V
E 7,0 V
E 8,0 V
E 9,0 V
E 10,0 V
E 11,4 V
ED
SD
SFP, kW / (m3/s) 2,0
SFP, kW / (m3/s) 1,5
SFP, kW / (m3/s) 1,0
Supply air
View from above
2 1
2 4
3 1
3 4
Left side
Right side
Extract air
9
© Vallox Oy - All rights reserved
VALLOX TSK MULTI 50 MC
TECHNICAL SPECIFICATIONS
547
900
1
12
3
3
4
236
161
86
96
206
96
206
86
161
1
2
3
4
86
161
1
4
197
87
2
3
2
4
54
43
28
View from above
Right side
Left side
Seen from behind
View from
right
View from
left
Elbow
Space required
for installation:
47mm
Water seal
Space required
for installation:
70mm
1 Supply air fan
2 Extract air fan
3 Post-heating radiator,
electrical, 900W
(behind the supply air
fan)
4 Heat recovery cell
5 Supply air filter F7
6 Supply air filter G4
7 Extract air filter G4
8 Automatic
summer/winter damper
9 Safety switch
10 Adjusting the supply
and extract air ratio
11 Adjusting the supply
air temperature
and summer/winter
function
R model:
1. Outdoor air to the unit
2. Supply air to the apartment
3. Extract air from the apartment to the unit
4. Exhaust air out
L model:
1. Extract air from the apartment to the unit
2. Exhaust air out
3. Outdoor air to the unit
4. to the apartment
Main parts
Dimensions and duct outlets
1 8 7 6 2453
11 910
Total height with an elbow 264 mm
Total height with the Vallox Silent Klick
water seal is 279 mm
R model in the figure.
Dimensions are mirrored for the L-model
SOUND VALUES
Sound power level in the supply air duct
by octave band Lw, dB
Sound power level in the extract air duct
by octave band Lw, dB
Adjustment position V / Air flow dm3/s Adjustment position V / Air flow dm/s
Adjustment position
/ V
3 4 5 6 7 8 9 10 11.4 3 4 5 6 7 8 9 10 11.4
Air flow dm/s 8.1 13.8 18.8 25.1 31.3 38.7 43.9 50.4 54.6 13.7 19.1 26.2 32.1 37.9 45 50.3 56.9 62.8
Medium
frequency
of the
octave
band Hz
63 42.3 40.7 44.9 47.3 50.2 52.8 54.1 57.4 57.6 *30.3 *31.6 *34.0 *38.2 43.4 45.5 47.6 50 51
125 40.5 47.8 51.1 50 53.7 55.6 57.3 59.3 60.4 40.4 44.1 44.7 48 49.2 51.9 54.5 57 57.8
250 34.9 45.9 51.2 55.1 58.5 59.9 61 62.3 64 28.7 37.6 43.5 47.9 48.6 52.1 52.7 53.9 55.3
500 30.1 39.5 45.5 50 55.2 60.8 61.8 64.3 66.2 *17.6 *25.3 30.8 36.2 40.8 49.4 48.3 50.2 51
1000 *24.0 35.5 42.3 47.5 51 56.6 59.6 61.5 63.2 *16.8 *25.4 31.6 36.1 39.1 44.1 46.5 49.3 51.1
2000 *17.8 *23.9 34.4 41.9 47.4 51.3 54.3 56.9 58.8 *12.2 *13.9 *21.3 *27.7 29.9 35.3 36.8 38.4 40.1
4000 *18.6 *20.6 *23.1 *29.6 38 43.9 48.1 51.4 53.6 *17.5 *17.6 *17.6 *18.4 *19.9 *26.5 29.5 31.1 33
8000 *23.2 *23.1 *23.1 *23.3 *24.3 *26.5 *29.6 33.4 36.5 *22.9 *22.9 *22.9 *22.9 *22.9 *23.2 *23.1 *23.2 *23.5
LW, dB
LWA, dB(A)
45.2 50.9 55.4 58.1 62 65.2 66.8 68.9 70.6 *41.2 45.3 47.6 51.5 53 56.7 58.1 60.2 61.3
32.5 41.5 47.6 52.3 57 61.1 63.3 65.6 67.5 *28.9 *33.5 38 42.7 44.5 49.7 50.6 52.7 54.1
Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m2 sound absorption)
Adjustment position V / air flow dm3/s (supply/extract)
Adjustment position
/ V
3.0V 4.0V 5.0V 6.0V 7.0V 8.0V 9.0V 10.0V 11.4V
Air flow dm3/s 8.0/13.1 13.4/18.6 19.4/25.1 25.1/30.9 31.5/37.3 38.1/44.0 43.9/50.1 49.3/55.8 54.0/61.4
LpA, dB (A) *24.4 *27.0 32.1 35.6 39.3 42.9 45.6 47.7 49.2
10
TECHNICAL SPECIFICATIONS
Supply/extract air volumes
Volume flow rate (dm/s)
Pressure loss in ducts. Total pressure (Pa)
Air flow
measurement
points
Measurement points after
the outlet collar. The fan
curves indicate the total
pressure accounted for by
duct losses.
FAN INPUT POWER
Fan speeds
With the SC control
panel (V)
Extract air flow
(50 Pa) dm/s
Combined input power
of the fans (W)
3 - 12
4 9 17
5 27 25
6 38 34
7 52 47
8 67 68
9 78 95
10 90 125
11.3 99 165
TECHNICAL SPECIFICATIONS
Product title
Vallox TSK Multi 80 MC R
Vallox TSK Multi 80 MC L
Product number
3478000
3478100
HVAC code
7912024
7912025
Air volumes Supply air
Extract air
76dm/s, 100Pa
93dm/s, 100Pa
Electrical connection 230V, 50Hz 8.8A power plug
Enclosure protection class IP34
Post-heating radiator Electric, 900W
Preheating radiator
Additional heating radiator Electric, 900W
Fans Supply air
Extract air
0.071kW 0.5 A EC
0.071kW 0.5 A EC
Specific energy consumption (SEC)
in a cold climate
in a temperate climate
A+
B
Operating eciencies Annual
eciency
Supply air eciency
Specific Fan Power
(SFP)
75% A+
85%
0.9 (38dm/s) A
Filters Supply air
Extract air
G4 + F7
G4
Heat recovery bypass Automatic
Dimensions (w x h x d) and weight 1026 x 293 x 626, 58.5 kg
350
300
250
200
150
100
50
0
0 10 20 30 40 50 60 70 80 90 100 110
SFP, kW / (m/s) 2,0
SFP, kW / (m/s) 1,5
SFP, kW / (m/s) 1,0
S 3,0 V
S 4,0 V
E 3,0 V
E 4,0 V
S 5,0 V
S 6,0 V
S 7,0 V
S 8,0 V
S 9,0 V
S 10,0 V
S 11,3 V
E 5,0 V
E 6,0 V
E 7,0 V
E 8,0 V
E 9,0 V
E 10,0 V
E 11,3 V
ED
SD
VALLOX TSK MULTI 80 MC
Supply air
View from above
2 1
2 4
3 1
3 4
Left side
Right side
Extract air
Combined input power of the fans (kW)
Airflow specified in the ventilation plan (m/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <2.0kW (m/s)
ED and SD are examples of pressure loss
in the supply and extract air ducts.
S = supply air
E = extract air
11
© Vallox Oy - All rights reserved
TECHNICAL SPECIFICATIONS
VALLOX TSK MULTI 80 MC
1 Supply air fan
2 Extract air fan
3 Post-heating radiator,
electrical, 900W
(behind the supply air
fan)
4 Heat recovery cell
5 Supply air filter F7
6 Supply air filter G4
7 Extract air filter G4
8 Automatic
summer/winter damper
9 Safety switch
10 Adjusting the supply
and extract air ratio
11 Adjusting the supply
air temperature
and summer/winter
function
R model:
1. Outdoor air to the unit
2. Supply air to the apartment
3. Extract air from the apartment to the unit
4. Exhaust air out
L model:
1. Extract air from the apartment to the unit
2. Exhaust air out
3. Outdoor air to the unit
4. to the apartment
Main parts
Dimensions and duct outlets
1 8 7 6 2453
11 910
R model in the figure.
Dimensions are mirrored for the L-model
626
1026
View from above
Right side
Left side
1
12
3
3
4
293
200
96
96 96
231 231
96
200
Seen from behind
1
2
3
4
110
200
View from
right
1
4
254
110
View from
left
2
3
2
4
Elbow
Space required
for installation:
47mm
54
43
28
Water seal
Space required
for installation:
70mm
Total height with an elbow 321 mm
Total height with the Vallox Silent Klick
water seal is 336 mm
SOUND VALUES
Sound power level in the supply air duct
by octave band Lw, dB
Sound power level in the extract air duct
by octave band Lw, dB
Adjustment position V / Air flow dm3/s Adjustment position V / Air flow dm/s
Adjustment position
/ V
3 4 5 6 7 8 9 10 11.3 3 4 5 6 7 8 9 10 11.3
Air flow dm/s 15.6 23.1 31.6 39.6 47.9 57.7 65.7 75.2 83.8 22.3 33.1 43.3 50.3 59.3 71.2 81.3 92.2 101
Medium
frequency
of the
octave
band Hz
63 43.2 43.3 55.8 52.4 54.3 56 57.4 60.4 60.4 *38.9 39.8 48.4 47.3 48.5 54.5 57.7 55 55.6
125 39.1 46.1 52.4 54.6 56.9 58.5 60.4 61.9 64.5 33.9 41.6 48 48.3 50.9 53.7 56.8 58.3 60.1
250 38.3 46 50.9 56.6 60.3 68 69.5 72 71.9 30.3 36.7 42.9 46.9 50.3 55.3 56.9 58.2 59.1
500 33.1 40.9 47.4 51.8 56.3 59.9 63.2 66.8 73 *21.8 27.1 34.3 37.5 42.9 45.9 48.9 52.3 55.2
1000 *27.9 36.2 42.5 4 7.1 51.8 56.5 59.7 62.9 66 *19.8 *25.5 32.1 35.7 40 44.1 47.5 49.9 53.1
2000 *19.7 30.1 38.3 43.6 48.9 53 56.2 59.3 62 *13.9 *16.4 *22.3 25.8 29.7 33.6 37 39.8 42.3
4000 *17.9 *20.0 *25.8 31.5 37.2 42.2 46.1 49.6 52.5 *18.0 *17.7 *17.8 *18.0 *18.8 *20.7 *23.9 *26.7 29.4
8000 *22.9 *23.0 *23.0 *23.2 *24.4 *27.3 30.8 34.9 38.5 *23.0 *23.0 *23.0 *23.0 *23.0 *23.1 *23.1 *23.2 *23.5
LW, dB
LWA, dB(A)
45.9 50.8 58.8 60.6 64 69.6 71.5 74.2 76.6 *40.7 44.7 52 52.6 55.2 59.6 62.3 62.9 64.4
*35.0 42.6 48.8 53.4 57.9 63.2 66.1 69.1 72.2 *28.1 *32.7 38.9 41.6 45.7 49.8 52.7 54.8 57
Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m2 sound absorption)
Adjustment position V / air flow dm3/s (supply/extract)
Adjustment position
/ V
3 4 5 6 7 8 9 10 11.3
Air flow dm3/s 15.1/19.5 23.4/27.8 32.3/36.8 39.3/43.1 47.4/52.1 57.0/61.7 66.1/70.4 74.8/79.2 84.0/88.1
LpA, dB (A) *24.7 *28.9 34.4 37.4 42 45.9 49.5 51.2 53.5
12
ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTION
9. GND / -
8. Supply fan PWM
7. Supply fan tacho
6. GND/-
5. Extract fan PWM
4. Extract fan tacho
3. GND/-
2. 11.2VDC/+
1. Control signal S
Error relay
230V 50Hz
DIP
switch
1
2
3
4
5
6
7
8
9
1
2
3
4
5
LINE, BN
NEUTRAL, BU
SLI, BK
SNI, BK
SLO, BK
SNO, BK
SFL, BN
SFN, BU
EFL, BN
EFN, BU
FSO
FSI
AHL, BN
AHN, BU
PHL, BN
PHN, BU
BL1, 3
BL, 2
BN, 1
E/I
E/O 1 2 3 4
Freezing level adjustment Extract air NTC "1"
Outdoor air NTC "2"
Supply air to the apartment NTC "3"
Exhaust air NTC "4"
Supply air from the cell NTC "5"
Programming
connector
PWM level adjustment
Post-heating control
LED
90°C
1 = N
2 = L
3 =
M
130°C
951159
951154
SS
SE
DIP Switch Up Down
1. Post-heating Electric VKL
2. Additional heating Electric MLV
3. Unit type Bypass Supply fan stop
4. Winter function Normal Humid
90°C 130°C
R2
T1
T2
T1
T2
R1
5
123
S Supply air fan
E Extract air fan
SS Safety switch
R1 Additional heating radiator (80 MC in the bypass duct)
R2 Post-heating radiator
M Damper motor
FS Fireplace switch (optional)
OK Voltage distribution switch (in the cooker hood)
VA Light switch (in the cooker hood)
Cables:
BK black
BN brown
BU blue
GN green
GY grey
WT white
YE/GN yellow/green
RD red
951155
951123
951153/951159:
BU = 1
BN = 2
YEGN = 9
951150/951152
BN = 7
W T = 8
GN = 15
YE = 16
RD = 7
W T = 8
BU = 15
YE = 16
BK = 1
BN = 2
YE/GN = 9
4
Error relay
E/O E/I
4 x 951107
951129
3562000
951166
951150
951152
951153
230V
L=L
R=R
4
3
214
5
GN
YE
W T
GN
YE
W T
External control panel
or cooker hood
LED
- +
S
VAK
Remote
monitoring
The signal LED of the external
control panel or the cooker
hood will be left disconnected
if error data and maintenance
reminder are to be covered
by remote monitoring.
Also disconnect the short
circuit link between connectors
3 and 5 from the female side
of the control panel connector.
45321
5
LINE: Phase
NEUTRAL: Neutral
SLI: Safety switch phase feed
SNI: Safety switch neutral feed
SLO: Safety switch phase to the circuit board
SNO: Safety switch neutral to the circuit board
SFL: Phase to supply air fan
SFN: Neutral to supply air fan
EFL: Phase to extract air fan
EFN: Neutral to extract air fan
FSO: Fireplace switch feed
FSI: Fireplace switch output
AHL: Post-heating phase
AHN:Post-heating neutral
PHL: Additional heater phase
PHN: Additional heater neutral
BL: Damper motor phase A
BL1: Damper motor phase B
BN: Damper motor neutral
E/I: Error relay feed
E/O: Error relay output
13
© Vallox Oy - All rights reserved
ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTIONS
EXTERNAL ELECTRICAL CONNECTION
with Vallox Capto PTC EC control hood
EXTERNAL ELECTRICAL CONNECTION
with the Vallox Simple Control control panel / Vallox PTXP MC,
Vallox PTXPA MC cooker hood
S
+
-
LED
Simple Control
S
S
+
+
-
-
Control signal S
11.2 Vdc / +
GND / -
Error relay / LED
LED LED
Internal connection
of the ventilation unit
S
+
-
LED
PTXP MC, PTXPA MC
ALARM
TACHO
GND
0-11V
PIEZO
+ -
DAMP
IN OUT
MODE
IN OUT
F ALARM
RS 485
A B GND
N
L
DAMPER
1 2 3
LIGHT
N L
FAN
N L
EC roof fan
Tacho
-
S
MC
VENTILATION UNIT
Five terminal
connector**
GND
S
GND
S
MC
VENTILATION UNIT
Four terminal
connector
MV
VENTILATIONUNIT
GND
AN/I
RM/I
RM/O
E/I
LED / E/O
PROGRAMMING
CONNECTORS OF
THE MOTHERBOARD
CONTACT DATA:
GUARD FUNCTION:
NORMAL SITUATION = OPEN
ACTIVATED = CLOSED
HOUSE AUTOMATION:
NORMAL SITUATION = OPEN
ERROR SITUATION
(HOOD OR VENTILATION UNIT) = CLOSED
ACTIVATED GUARD FUNCTION = FLASHING
POSITION OF THE DAMPER:
DAMPER CLOSED = CONTACT OPEN
DAMPER OPEN = CONTACT CLOSED
* External error data is connected in the place
of the short circuit link of the mother board
** Disconnect the short circuit link between connectors
3 and 5 from the MC unit’s control panel connector
IN OUT
PE
EXTRA
DAMPER POSITION
CONTACT DATA
GUARD FUNCTION
CONTACT DATA
HOUSE AUTOMATION
CONTACT DATA
3 POTENTIAL FREE CONTACT
DATA 24VDC/5A
*HUOM!
14
ELECTRICAL CONNECTIONS
EXTERNAL ELECTRICAL CONNECTION
with Vallox ProControl control panel
EXTERNAL ELECTRICAL CONNECTION
with an external control panel
Wiring between the control panel and the ventilation unit, NOMAK 2x2x0.5+0.5
Ventilation unit cable Control panel connector
S Y1
+ leave disconnected
- G0
LED S/DI2
CONTROL PANEL
G 24 VAC feed S/DI2 Error relay
G0 0 VAC G0 0 VAC
Y1 10V, control voltage
of the ventilation unit
Y2
DI1 Boost at the cooker hood
A1 24VAC 1A, intermediate
relay control
Y3
A2
Y4
U1 0...10V, humidity boost
A+ RS-485
B- RS-485
C RS-485 Common
RH%
optional
946147
Nomak
2x2x0,5+0,5
0...10V
LED
G
G0
Y1
Y2
DI1
A1
Y3
A2
Y4
U1
A+
B-
C
S/DI2
G0
Vallox Procontrol
949034
S
LED
S
+
+
-
-
B term
CONFIG
Control signal S Cooker hood
or boost switch
11.2 VDC / +
GND / -
DISTRIBUTION
BOARD
L N
24V
Error relay / LED
Nomak 2x2x0,5+0,5 Modbus
RS-485
Nomak
2x2x0,5+0,5
Cable types specified in the drawing are indicative
2x0.5
2x0.5
Internal connection
of the ventilation unit
The phase of 24VAC feed is connected
to the control panel connector G and
the neutral to the connector G0
Control signal S
GND / -
An external 0-10 VDC
voltage can be
connected to the S
and GND connectors
for fan control.
External control panel
S
S
+
+
-
-
GND / -
LED LED
Internal connection
of the ventilation unit
Control signal S
11.2 VDC / +
Error relay / LED
15
© Vallox Oy - All rights reserved
INSTALLATION
Mounting
The Vallox TSK Multi 50/80 MC is normally installed on the
ceiling using the four mounting hooks delivered with the unit.
The weight of the unit (45 kg) must be taken into account when
mounting the unit.
Wall structure
The wall structure must be observed in the mounting.
Avoid mounting the unit on hollow, echoing intermediate
walls and on bedroom walls, or take measures to prevent
conduction of noise.
INSTALLATION SITE
Vallox TSK Multi 50/80 MC must be installed in a location
where the temperature remains above +10 °C. When the
unit is installed without a protective enclosure, the location
must be chosen so that its noise does not cause any
disturbance. Such locations include storage premises and
technical spaces.
Important! The whole length of the outdoor air duct to the unit
and exhaust air duct from the unit must be insulated using
closed cell insulation.
CONDENSING WATER
The delivery includes a water seal and an elbow for connecting the pipe that leads the water condensed from the extract air to the
floor drain (not directly into the sewer). The pipe must not rise after the water seal. See the accessory bag for further instructions
on the installation of the water seal and the elbow.
DIMENSION TSK Multi 50
mm
TSK Multi 80
mm
A 431 519
B 91 91
C 16 16
D 548 626
E 530 600
F 236 293
G 935 1060
H 900 1026
F
Water seal
Water outlet
(alternative)
54
Plug cord and cord
for SC speed switch
Space required
for mounting
H
ALITOTLOUH
G
E
D
BA
C
61
43
27
47
SPACE FOR
MAINTENANCE
SPACE FOR
MAINTENANCE
© Vallox - All rights reserved
D2585 | 29.1.2018|PDF
EXPLODED VIEW
EXPLODED VIEW AND PARTS LIST
R model in the figure.
In the L model, the parts are
mirrored
13
12B
10
11
12
14
15
16
17
18
19
20 21
22
23
24
25
1
2
3
4
5
6
7
8
9
NO. Part Product number
1 Frame (Vallox TSK Multi 50 MC/80 MC)
2 Door (Vallox TSK Multi 50 MC) ................................................................... 3473500
2 Door (Vallox TSK Multi 80 MC) ...................................................................3483000
3 Finger screw for the door .............................................................................. 990698
4 Heat recovery cell (Vallox TSK Multi 50 MC)..............................................933120
4 Heat recovery cell (Vallox TSK Multi 80 MC) ..............................................933130
5 Supply/extract air fan assembly, ................................................................ 3473400
R and L model (Vallox TSK Multi 50 MC)
5 Supply/extract air fan assembly, ............................................................... 3482900
R and L model (Vallox TSK Multi 80 MC)
6 Fan (Vallox TSK Multi 50 MC) ........................................................................ 935385
6 Fan (Vallox TSK Multi 80 MC) ........................................................................ 935375
7 Bypass duct assembly, R model (Vallox TSK Multi 50 MC) ................ 3432700
7 Bypass duct assembly, L model (Vallox TSK Multi 50 MC) ..................3551300
7 Bypass duct assembly, R model (Vallox TSK Multi 80 MC) ................ 3479500
7 Bypass duct assembly, L model (Vallox TSK Multi 80 MC) ..................3551400
8 Damper actuator, L model ............................................................................. 930620
8 Damper actuator, R model ..............................................................................930621
9 Safety switch ......................................................................................................948370
10 Motherboard ......................................................................................................949032
11 NTC sensor kit ................................................................................................. 3494100
12 Post-heating radiator, R model ......................................................................942210
12 Post-heating radiator, L model ........................................................................ 942211
12B Additional heating radiator, R model (Vallox TSK Multi 80 MC) ............942210
12B Additional heating radiator, L model (Vallox TSK Multi 80 MC) ..............942211
13 Side sealing strip of the heat recovery cell ............................................ 3356300
(Vallox TSK Multi 50 MC)
13 Side sealing strip of the heat recovery cell ........................................... 3352600
(Vallox TSK Multi 80 MC)
NO. Part Product number
14 Upper sealing strip of the heat recovery cell ......................................... 3463400
(Vallox TSK Multi 50 MC)
14 Upper sealing strip of the heat recovery cell ......................................... 3488700
(Vallox TSK Multi 80 MC)
15 Filter stand (G4, supply) 500mm (Vallox TSK Multi 50 MC) .............. 3356400
15 Filter stand (G4, supply) 580mm (Vallox TSK Multi 80 MC) ................ 3352700
16 Filter stand (G4, extract) 400mm (Vallox TSK Multi 50 MC) ............... 3382800
16 Filter stand (G4, extract) 450mm (Vallox TSK Multi 80 MC) ............... 3368500
17 Filter (G4, supply) (Vallox TSK Multi 50 MC) .............................................978036
17 Filter (G4, supply) (Vallox TSK Multi 80 MC) .......................................... 3326700
18 Filter (G4, extract) (Vallox TSK Multi 50 MC) .............................................. 978035
18 Filter (G4, extract) (Vallox TSK Multi 80 MC) ............................................3379700
19 Filter (F7, supply) (Vallox TSK Multi 50 MC) ................................................ 978136
19 Filter (F7, supply) (Vallox TSK Multi 80 MC)................................................. 978135
20 Plug (Vallox TSK Multi 50 MC) ...................................................................... 990630
20 Plug (Vallox TSK Multi 80 MC) ...................................................................... 990640
21 Cover panel 100mm (Vallox TSK Multi 50 MC) ...................................... 3363500
21 Cover panel 125mm (Vallox TSK Multi 80 MC) ...................................... 3363600
22 Water seal Vallox Silent Klick ..................................................................... 3494700
23 Connection box assembly ........................................................................... 3526700
24 MyVallox humidity sensor (optional) .............................................................946149
25 MyVallox carbon dioxide sensor (optional) ...................................................949111
Vallox TSK Multi 50 MC
Vallox filter package no. 25. ....................................................................... 3570200
Vallox TSK Multi 80 MC
Vallox filter package no. 26. ....................................................................... 3356800
www.vallox.com
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND
Customer Service +358 10 7732 200 | Aftersales +358 10 7732 270
/