Lithonia Lighting WST Installation guide

Type
Installation guide
Installation Instructions
Part Number: RJ5210180 Rev. E
Revision Date: 5/4/10
Lithonia Lighting Outdoor
One Lithonia Way, Conyers, GA 30012
Phone: 800-279-8041 Fax: 770-918-1209
www.lithonia.com
MRW - WSQ - WSR - WST
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
SAVE THESE INSTRUCTIONS
WARNING
To reduce the risk of death, injury or property damage from fire, electric shock, cuts,
abrasions, falling parts, and other hazards:
Service of the equipment must be performed by qualified service personnel.
Installation and maintenance must be performed by a person familiar with the construction and
operation of this product and any hazards involved. All applicable codes and ordinances must
be followed.
Read this document before installing, servicing, or maintaining this equipment or installing a
lamp. These instructions do not cover all installation, service, and maintenance situations. If
your situation is not covered, or if you do not understand these instructions or additional
information is required, contact Lithonia Lighting or your local Lithonia LIghting Distributor.
Read and follow all warnings and instructions provided by the lamp manufacturer.
WARNING
Before installing, servicing, or maintaining this equipment, follow these general precautions.
To reduce the risk of electrocution:
Make sure the equipment is properly grounded.
Always de-energize the circuit and/or equipment before connecting to, disconnecting
from, or servicing the equipment.
To reduce the risk of fire:
Keep material away that can burn from hot lamp.
Make sure lamps are correctly installed.
Use supply conductors with a minimum installation temperature rating as specified on
equipment.
To reduce the risk of personal injury from cuts, abrasions, or falling parts:
Wear gloves to prevent cuts or abrasions from sharp edges when removing from carton,
handling and maintaining this equipment.
Do not use abrasive materials, glass cleaners or other solvents on reflector or lens.
These substances may damage equipment and cause parts to eventually break and
fall.
Do not install a damaged fixture.
CAUTION: Observe lamp manufacturer’s recommendations and restrictions on lamp operation,
including but not limited to ballast type, burning position, replacement and cycling. Use only lamps that
comply with applicable ANSI standards.
NOTICE: If lamp is marked it contains mercury. Follow disposal laws. See www.lamprecycle.org
Lithonia Lighting, a division of Acuity Brands Lighting, Inc., assumes no responsibility for claims arising out of
improper or careless installation or handling of this product.
IMPORTANT SAFETY INSTRUCTIONS
DISCONTINUED
Installation Instructions
Part Number: RJ5210180 Rev. E
Revision Date: 5/4/10
Lithonia Lighting Outdoor
One Lithonia Way, Conyers, GA 30012
Phone: 800-279-8041 Fax: 770-918-1209
www.lithonia.com
MRW - WSQ - WSR - WST
DELIVERY: Upon receipt thoroughly inspect for any freight damage. All damage should be reported to the delivery carrier. Compare the catalog description
listed on the packing slip with the fixture label on the inside of the housing to be sure to correct merchandise was received.
Tools Required: #2 philips type and flathead screwdriver. 1/8" and 3/16" allen wrench.
1. These steps below are for mounting over a standard recessed junction box. Remove 1/4"-20 screws from mounting
plate top and discard. Position mounting plate over j-box. The mounting plate may be attached to the j-box for
alignment only, it should not be relied upon for structural support. Ensure integral support rod on mounting plate is in a
downward position and bubble level is at the top. Level mounting plate prior to tightening using integral bubble level.
Secure to wall using (4) 1/4" diameter fasteners (not provided). See figure 1.
2. Back out the (2) 1/4"-20 x 1/2" hex socket set screws on the bottom of the fixture
until flush with the finned backplate to keep from interferring with mounting the
fixture, or may be removed and discarded when mounting doorframe up.
For doorframe up only: Install 1/4"-20 x 3/4" hex socket cap screws (provided in
prepackaged hardware) into the top of the mounting plate (replacing 1/4"-20
screws from step 1), turning twice is sufficient. Note--These fixtures are listed
for DAMP location ONLY when installed in the lens up orientation unless the
WLU option has been ordered. Installation of the fixture in any position other
than what is indicated with the supplied instructions will void all warranties.
3. To attach fixture to the integral support rods, facing the wall, grip the fixture
on the sides with the front towards you, insert the support rod on one side of the
wall mounting plate into the corresponding slot in the fixture side mounting
bracket. Lift the other side of the fixture up (so it is slanted) in order to insert the
other support rod into the top of the corresponding slot in the fixture side
mounting bracket. (See figure 2).
4. Slide fixture down and align so that the fixture is straight and let fixture hang
off the integral support rods. (See figure 3). Protect the fixture surface from the
wall surface so as not to scratch or mar the fixture finish.
5. Do not make any connections with energized supply leads. Ensure the line voltage at the fixture is correct. Make all
necessary wiring connections ensuring that wires are not being pinched. Place wires inside junction box.
6. Lift fixture and place the bottom hook of the fixture mounting bracket onto the bottom center slot of the wall mounting
plate (see circles A in figure 4). Keep pressure on the bottom of the fixture against the wall, lift up slightly and insert the
top hooks of the fixture mounting bracket into the top slots of the wall mounting plate (see circles B in figure 4). Make
sure wires are inside the junction box and not pinched.
7. Slide the fixture into place by firmly applying pressure against the fixture onto the wall mounted plate and pushing
down. Verify the fixture is securely seated and parallel to the wall.
8. Doorframe down: Tighten the (2) hex socket set screws on the bottom of the housing with an 1/8" allen wrench evenly
(10-15 in. lbs maximum). Note--Product labels will be visible from the ground.
Doorframe up: Tighten the (2) hex socket cap screws (installed in step 2) into the housing with an 3/16" allen wrench
evenly (10-15 in. lbs maximum).
©2001 Acuity Brands Lighting, Inc. All
Rights Reserved. Rev. 04/10
D
C
B
A
D
A
C
B
D
A
C
B
CAUTION: APPLY A CONTINUOUS BEAD OF WEATHER - PROOF CAULKING BETWEEN MOUNTING PLATE AND WALL TO ENSURE WEATHER - TIGHT INTEGRITY OF ELECTRICAL COMPONENTS.
TB - Tapped Ballast: The tapped ballast will be wired for 277 volt at the factory. To wire a fixture that contains a tapped
ballast, first determine correct line voltage. Then select the corresponding fixture voltage lead, remove the crimped cap
and connect to the supply voltage lead. The fixture lead marked COM should be connected to the neutral supply lead for
120 or 277. For 208 or 240, connect the other incoming hot leg to the fixture lead marked "COM". Be sure to cap off all
unused fixture leads individually. For fixtures with ELDW or ELED option, consult the additional instructions and wire diagrams provided in the carton. For
fixtures with ELDWR or ELDWRPS, consult the instructions and wire diagrams provided with the remote battery pack (by others).
Lamp Installation: Open lens/doorframe. Check to make sure that all power is disconnected. Ensure that the lamp source and wattage corresponds with
the fixture label. To properly seat the lamp into the fixture, screw the lamp securely into the socket. Back the lamp out one to two turns, and then screw
the lamp back into the socket, making sure that it is secure. Compact Fluorescent: Verify correct wattage and source, push lamp into socket until the
socket retention clips snap secure (you will hear a click). Close lens/doorframe and tighten captive screws. Optional Tamper Resistant Torx® screws are
provided. Remove existing door closure screws and insert the optional screws (a Torx® T20 with center pin reject driver or bit to install and remove).
Troubleshooting - If this fixture fails to operate properly, check to make sure: • The correct lamp is properly installed •The fixture is wired correctly •The
lamp is not faulty • The fixture is grounded correctly •The line voltage at the fixture is correct.
Fixture mounting bracket
FIGURE 2
WSR
A
7-7/16”
B
3-15/16”
C
3-1/2”
D
9”
MRW
A
7-3/16”
B
3-15/16”
C
3-7/8”
D
9”
WSQ
9-13/16”
3-15/16”
5-7/8”
9”
WST
A
7-7/16”
B
3-15/16”
C
3-1/2”
D
9”
D
A
C
B
FIGURE 3
Wall mounting plate
Integral support rods
FIGURE 1
A
B
FIGURE 4
B
DISCONTINUED
  • Page 1 1
  • Page 2 2

Lithonia Lighting WST Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document