Trane R Series Installation, Operation and Maintenance Manual

Type
Installation, Operation and Maintenance Manual
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
Series R Air-Cooled
Helical Rotary Liquid Chillers
May 2012 RTAC-SVX01J-EN
Installation, Operation,
and Maintenance
© 2012Trane All rights reserved RTAC-SVX01J-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals
throughout this manual. Warnings are provide to alert
installing contractors to potential hazards that could result
in death or personal injury. Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughly before operating or servicing
this unit.
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earths naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read
these carefully:
WARNING
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTIONs
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
NOTICE:
Indicates a situation that could result in
equipment or property-damage only
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
Refrigerant under High Pressure!
System contains oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for refrigerant
type. Do not use non-approved refrigerants, refrigerant
substitutes, or refrigerant additives. Failure to recover
refrigerant to relieve pressure or the use of non-
approved refrigerants, refrigerant substitutes, or
refrigerant additives could result in an explosion which
could result in death or serious injury or equipment
damage.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
Warnings, Cautions and Notices
RTAC-SVX01J-EN 3
Introduction
Literature History
RTAC-SVX01J-EN (May 2012) - Added RTAC Extra
Efficiency (XE) units.
RTAC-SVX01H-EN (November 2011) - Revised manual to
add 120, 130T 50 Hz units. Updated for W0 design
sequence change.
RTAC-SVX01G-EN (January 2011) - Revised manual for 3
pass evaporator option. Updated for V0 design sequence
change.
RTAC-SVX01F-EN (January 2006) - Revised manual for
new control panel design.
RTAC-SVX01E-EN (July 2004) - Revised manual for new
evaporator design for 3 and 4 compressor units. Design
Sequence J0 and later.
RTAC-SVX01D-EN (July 2003) - Revised manual for new
evaporator design for 2 compressor units. Design
Sequence H0 and later.
RTAC-SVX01C-EN (February 2002) - Revised manual
includes additional RTAC units to size 500 tons, new
installation and maintenance material, and expanded
CH530 diagnostics
RTAC-SVX01B-EN (September 2001) - New manual
describes installation, operation, and maintenance of
RTAC units and the remote evaporator option.
RTAC-SVX01A-EN (December 2000) - New manual.
Trademarks
Trane and theTrane logo are trademarks ofTrane in the
United States and other countries. All trademarks
referenced in this document are the trademarks of their
respective owners.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians
MUST put on all Personal Protective Equipment (PPE)
recommended for the work being undertaken.
ALWAYS refer to appropriate MSDS sheets and OSHA
guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put
on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.
Failure to follow recommendations could result in death
or serious injury.
4 RTAC-SVX01J-EN
Table of Contents
Warnings, Cautions and Notices .......................................................... 2
Model Number Description ............................................................... 8
Outdoor Unit Nameplate ................................................................ 8
Compressor Nameplate ................................................................. 8
Unit Model Number .................................................................... 9
Compressor Model Number ............................................................ 10
Compressor Serial Number ............................................................ 10
General Data ........................................................................... 11
Unit Description ...................................................................... 11
Accessory/Option Information .......................................................... 11
Isolator Shipping Location ............................................................ 11
Pre-installation ......................................................................... 22
Unit Inspection ..................................................................... 22
Inspection Checklist ................................................................. 22
Storage ........................................................................... 22
Installation Responsibilities ........................................................... 22
General .............................................................................. 22
Dimensions and Weights ................................................................ 23
Clearances ........................................................................... 23
Dimensions .......................................................................... 26
Weights ............................................................................. 38
Installation - Mechanical ................................................................ 41
Location Requirements ................................................................ 41
Noise Considerations ................................................................ 41
Foundation ........................................................................ 41
Clearances ......................................................................... 41
Rigging .............................................................................. 41
Lifting Procedure .................................................................... 41
Isolation and Sound Emission .......................................................... 44
Unit Isolation and Leveling ........................................................... 44
Drainage ............................................................................. 48
Evaporator Water Piping ............................................................... 48
Evaporator Piping ................................................................... 48
Entering Chilled Water Piping ......................................................... 49
Leaving Chilled Water Piping .......................................................... 49
Evaporator Drain .................................................................... 49
Evaporator Flow Switch .............................................................. 49
Water Pressure Gauges ................................................................ 52
Water Pressure Relief Valves ........................................................... 52
Freeze Protection ..................................................................... 52
RTAC-SVX01J-EN 5
Low Evaporator Refrigerant Cutout, Glycol Recommendations .............................. 53
Procedure ......................................................................... 53
Specials ........................................................................... 53
Installation - Mechanical — Remote Evaporator Option .................................... 55
System Configuration and Interconnecting Refrigerant Piping .............................. 55
Line Sizing ........................................................................... 59
Liquid Line Sizing Steps .............................................................. 59
Suction Line Sizing Steps ............................................................. 60
Suction Accumulator Sizing ........................................................... 60
Piping Installation Procedures .......................................................... 61
Refrigerant Sensors ................................................................... 61
Refrigerant Pressure Relief Valve Venting ................................................ 61
Leak Test and Evacuation .............................................................. 62
Refrigerant and Additional Oil Charge ................................................... 63
Refrigerant Charge Determination ..................................................... 63
Oil Charge Determination ............................................................. 63
Installation - Electrical ................................................................... 64
General Recommendations ............................................................ 64
Installer-Supplied Components ......................................................... 85
Power Supply Wiring ................................................................ 85
Control Power Supply ................................................................. 86
Heater Power Supply and Convenience Outlet (Packaged Units Only) ........................ 86
Interconnecting Wiring ................................................................ 87
Chilled Water Pump Control .......................................................... 87
Alarm and Status Relay Outputs (Programmable Relays) ................................... 88
Relay Assignments Using TechView ..................................................... 88
Low Voltage Wiring ................................................................... 88
Emergency Stop .................................................................... 89
External Auto/Stop .................................................................. 89
External Circuit Lockout – Circuit #1 and #2 .............................................. 89
Ice Building Option .................................................................. 89
External Chilled Water Setpoint (ECWS) Option .......................................... 89
External Current Limit Setpoint (ECLS) Option ........................................... 90
Chilled Water Reset (CWR) ............................................................ 90
Communications Interface options ...................................................... 91
Optional Tracer Communications Interface .............................................. 91
LonTalk Communications Interface for Chillers (LCI-C) ..................................... 91
BACnet Communications Interface (BCI-C) ............................................... 92
Object and Diagnostic Data Points with Corresponding Chiller Models ....................... 98
BCI-C Alarming .................................................................... 105
Operating Principles ................................................................... 106
Refrigeration Cycle ................................................................... 106
Refrigerant R-134a ................................................................... 106
6 RTAC-SVX01J-EN
Compressor ......................................................................... 106
Condenser and Subcooler ............................................................. 107
Expansion Valve ..................................................................... 108
Evaporator .......................................................................... 108
Oil System .......................................................................... 108
Controls Interface ...................................................................... 109
Overview ........................................................................... 109
Controls Interface .................................................................... 109
DynaView Display .................................................................... 109
Key Functions ..................................................................... 109
Display Screens .................................................................... 110
Modes Screen ..................................................................... 111
Chiller Screen ..................................................................... 115
Compressor Screen ................................................................ 115
Refrigerant Screen ................................................................. 115
Setpoint Screen .................................................................... 116
Diagnostic Screen .................................................................. 117
Power-Up ......................................................................... 117
Display Formats ..................................................................... 117
Units ............................................................................. 117
Languages ........................................................................ 117
TechView ........................................................................... 117
Software Download ................................................................ 118
Unit View ......................................................................... 118
Compressor Service View ........................................................... 119
Status View ....................................................................... 119
Setpoint View ..................................................................... 119
Diagnostics View ................................................................... 120
Configuration View ................................................................. 120
Software View ..................................................................... 123
Binding View ...................................................................... 123
Replacing or Adding Devices ......................................................... 123
Pre-Start Checkout ..................................................................... 126
Installation Checklist ................................................................. 126
Receiving ........................................................................... 126
Unit Location and Mounting ........................................................... 126
Unit Piping .......................................................................... 126
Electrical Wiring ..................................................................... 126
General ............................................................................. 127
Unit Voltage Power Supply ............................................................ 128
Unit Voltage Imbalance ............................................................... 128
Unit Voltage Phasing ................................................................. 128
Water System Flow Rates ............................................................. 129
RTAC-SVX01J-EN 7
Water System Pressure Drop .......................................................... 129
CH530 Set-Up ....................................................................... 129
Unit Start-Up Procedures ............................................................... 130
Daily Unit Start-Up ................................................................... 130
General ............................................................................. 130
Seasonal Unit Start-Up Procedure ..................................................... 130
System Restart After Extended Shutdown ............................................... 131
Shutdown ............................................................................. 136
Temporary Shutdown And Restart ..................................................... 136
Extended Shutdown Procedure ........................................................ 136
Maintenance .......................................................................... 137
Weekly Maintenance ................................................................. 137
Monthly Maintenance ................................................................ 137
Annual Maintenance ................................................................. 137
Refrigerant and Oil Charge Management ................................................ 140
R-134a Field Charging Procedure ...................................................... 141
Factory Refrigerant Charging Procedure (Initial) ......................................... 141
Field Refrigerant Charging Procedure .................................................. 141
Adding Charge .................................................................... 141
Charge Isolation in the high or low side of system ....................................... 142
High side charge isolation procedure .................................................. 142
Low side charge isolation procedure .................................................. 142
Refrigerant Filter Replacement Procedure ............................................... 143
Lubrication System .................................................................. 143
Oil Charging Procedure ............................................................. 143
Factory (initial) Oil Charging Procedure ................................................ 145
Field Oil Charging Procedure ......................................................... 145
Evaporator tube replacement .......................................................... 146
Compressor Replacement ............................................................. 146
Condenser Maintenance .............................................................. 147
Condenser Coil Cleaning ............................................................ 147
Travel Restraint ...................................................................... 147
Diagnostics ........................................................................... 148
Legend to Diagnostics Table .......................................................... 148
Starter Diagnostics ................................................................... 148
Main Processor Diagnostics ........................................................... 154
Communication Diagnostics ........................................................... 162
Main Processor Boot Messages and Diagnostics ......................................... 167
Unit Wiring ........................................................................... 168
8 RTAC-SVX01J-EN
Model Number Description
Nameplates
The RTAC outdoor unit nameplates are applied to the
exterior of the Control Panel. A compressor nameplate is
located on each compressor. When the unit arrives,
compare all nameplate data with ordering, submittal, and
shipping information.
Outdoor Unit Nameplate
See Figure 1, p. 8 for a typical unit nameplate.The outdoor
unit nameplate provides the following information:
Unit model and size description.
Unit serial number.
Identifies unit electrical requirements.
Lists correct operating charges of R-134a and
refrigerant oil (Trane OIL00048).
Lists unit test pressures.
Identifies installation, operation and maintenance and
service data literature (Pueblo).
Lists drawing numbers for unit wiring diagrams
(Pueblo).
Model Number Coding System
The model numbers for the unit and the compressor are
composed of numbers and letters that represent features
of the equipment. Shown in the following table is a sample
of typical unit model number and the coding system for
each.
Each position, or group of positions, in the model number
is used to represent a feature. For example, in the first
table, position 08 of the unit model number, UnitVoltage,
contains the number “4”.A 4 in this position means that the
unit voltage is 460/60/3.
Unit Model Number. An example of a typical unit
model number (M/N) is:
RTAC 350A UA0N NAFN N1NX 1TEN NN0N N01N
Model number digits are selected and assigned in
accordance with the definitions as listed in “Unit Model
Number,” p. 9.
Compressor Nameplate
The compressor nameplate provides following
information:
Compressor model number. See “Compressor Model
Number,” p. 10.
Compressor serial number. See“Compressor Serial
Number,” p. 10.
Compressor electrical characteristics.
Utilization range.
Recommended refrigerant.
Figure 1. Typical unit nameplate
RTAC-SVX01J-EN 9
Model Number Descriptions
Unit Model Number
Digits 1, 2 Unit Model
RT = Rotary chiller
Digit 3 Unit Type
A = Air-cooled
Digit 4 Development
Sequence
C = Development Sequence
Digits 5-7 Nominal Capacity
120 = 120 Nominal tons
130 = 120 Nominal tons
140 = 120 Nominal tons
155 = 120 Nominal tons
170 = 120 Nominal tons
180 = 120 Nominal tons
200 = 120 Nominal tons
225 = 120 Nominal tons
250 = 120 Nominal tons
275 = 120 Nominal tons
300 = 120 Nominal tons
350 = 120 Nominal tons
375 = 120 Nominal tons
400 = 120 Nominal tons
450 = 120 Nominal tons
500 = 120 Nominal tons
Digit 8— Unit Voltage
A = 200/60/3
C = 230/60/3
J = 380/60/3
D = 400/50/3
4 = 460/60/3
5 = 575/60/3
Digit 9 Manufacturing
Location
U = Trane Commercial Systems,
Pueblo, CO USA
Digits 10, 11— Design Sequence
XX = Factory assigned
Digit 12 Unit Basic
Configuration
N = Standard efficiency/performance
configuration
H = High efficiency/performance
configuration
A = Extra efficiency/performance
configuration
Digit 13 Agency Listing
N = No agency listing
U = UL/CUL listing
Digit 14 Pressure Vessel Code
A = ASME pressure vessel code
C = Canadian code
D = Australian code
L = Chinese code
Digit 15 Evaporator
Application
F = Standard (40-60°F) leaving temp
R = Low (<40°F) leaving temp
G = Remote (40-60°F) leaving temp
Digit 16 Evaporator
Configuration
N = 2 pass, 0.75” insulation
P = 3 pass, 0.75” insulation
Q = 2 pass, 1.25” insulation
R = 3 pass, 1.25” insulation
Digit 17 Condenser
Application
N = Standard ambient (25-115°F)
H = High ambient (25-125°F)
L = Low ambient (0-115°F)
W = Wide ambient (0-125°F)
Digit 18 Condenser Fin
Material
1 = Standard aluminum slit fins
2 = Copper fins
4 = CompleteCoat epoxy coated fins
Digit 19 Condenser Fan/Motor
Configuration
T = Std fans with TEAO motors
W = Low noise fans
Digit 20 Compressor Motor
Starter Type
X = Across-the-line starter
Y = Wye-delta closed transition
starter
Digit 21 Incoming Power Line
Connection
1 = Single point power connection
2 = Dual point power connection
Digit 22 Power Line
Connection Type
T = Terminal block connection
D = Non-fused disconnect switch(es)
C = Circuit breaker(s)
Digit 23 Unit Operator
Interface
D = DynaView operator interface
Digit 24 Remote Operator
Interface
N = No remote interface
C = Tracer Comm3 interface
B = BACnet interface
L = LonTalk compatible (LCI-C)
interface
Digit 25 Control Input
Accessories/Options
N = No remote inputs
R = External evaporator leaving
water setpoint
C = External current limit setpoint
B = External leaving water and
current limit setpoint
Digit 26 Control Output
Accessories/Options
N = No output options
A = Alarm relay options
C = Ice making I/O
D = Alarm relay outputs and ice
making I/O
Digit 27 Electrical Protection
Options
0 = No short circuit rating
5 = Default short circuit rating
6 = High amp short circuit rating
Digit 28 Flow Switch
T = Factory installed flow switch -
water
U = Factory installed flow switch -
glycol
Digit 29 Control Panel
Accessories
N = No convenience outlet
A = 15A 115V convenience outlet
(60Hz)
Digit 30 Service Valves
1 = With suction service valves
Digit 31 Compressor Sound
Attenuation Option
0 = No compressor sound
attenuation
1 = Factory installed compressor
sound attenuation
Digit 32 Appearance Options
N = No appearance options
A = Architectural louvered panels
C = Half louvers
Digit 33 Installation
Accessories
N = No installation accessories
R = Neoprene in shear unit isolators
F = Flange kit for water connections
G = Neoprene isolators and flange kit
Digit 34 Factory Testing
Options
0 = Standard functional test
C = Customer-witnessed
performance test with report
E = Non-witnessed performance test
with report
Model Number Descriptions
10 RTAC-SVX01J-EN
Compressor Model
Number
Digits 1-3 Compressor Family
CHH= Positive displacement,
refrigerant, helical rotary, hermetic
compressor
Digit 4— Compressor Type
T = GP2+
Digit 5
0= All compressors
Digit 6 Frame Size
K = K Frame
L = L Frame
M = M Frame
N = N Frame
Digit 7 Compressor Capacity
3 = GP2+ Smaller capacity (minor)
4 = GP2+ Larger capacity (major)
Compressor Serial
Number
Digits 1-2 Year
YY = Last two digits of year of
manufacture
Digits 3-4 Week
WW= Week of build, from 00 to 52
Digit 5 Day
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = sunday
Digits 6-8 Coded Time Stamp
TTT = Used to ensure uniqueness of
serial number
Digit 9 Assembly Line
L = Varies with facility
Digit 10— Build Location
A = Monterrey
RTAC-SVX01J-EN 11
General Data
Unit Description
The 140 - 500 ton Model RTAC units are helical-rotary type,
air-cooled liquid chillers designed for installation
outdoors.The compressor circuits are completely
assembled, hermetic packages that are factory-piped,
wired, leak-tested, dehydrated, and tested for proper
control operation before shipment.
Chilled water inlet and outlet openings are covered for
shipment. Each compressor has a separate compressor
motor starter.The RTAC series featuresTranes exclusive
Adaptive Control ™ logic, which monitors the control
variables that govern the operation of the chiller unit.
Adaptive Control logic can adjust capacity variables to
avoid chiller shutdown when necessary, and keep
producing chilled water.The units feature two
independent refrigerant circuits. Compressor unloaders
are solenoid actuated and oil pressure operated. Each
refrigerant circuit is provided with filter, sight glass,
electronic expansion valve, and charging valves.The
shell-and-tube type evaporator is manufactured in
accordance with ASME standards or other international
codes. Each evaporator is fully insulated and is equipped
with water drain and vent connections. Packaged units
have heat tape protection to - 20°F (-28.9°C) as standard.
As an option, a convenience outlet can be supplied.
Note: Packaged units are factory charged with refrigerant
and oil.
Accessory/Option Information
Check all the accessories and loose parts which are
shipped with the unit against the shipping list. Included in
these items will be water vessel drain plugs, rigging and
electrical diagrams, and service literature, which are
placed inside the control panel and/or starter panel for
shipment.
Isolator Shipping Location
If optional neoprene isolators (model number digit 33) are
ordered with unit, they are shipped mounted on the unit.
See Figure 3 and Figure 4.
Figure 2. Typical RTAC packaged unit and components
Figure 3. Isolator shipping locations 140-250T units
Figure 4. Isolator shipping locations 140-250T units
Neoprene Isolator Shipping Location
Neoprene Isolator Shipping Location
Size 140 155 170 185 200 225 250 275 300 350 400 450 500
Screw
Quantity #2222222333444
Nominal size
@60Hz
(tons) 70/70 85/70 85/85
100/
85
100/
100
120/
100
120/
120
85-85/
100
100-100/
100
120-120/
100
100-100/
100-100
120-120/
100-100
120-120/
120-120
Flooded
Water storage (gal)29323436403943626772838691
2 pass arrangement
Min flow (gpm) 193 214 202 217 241 217 241 309 339 375 404 422 461
Max flow (gpm) 709 785 741 796 883 796 883 1134 1243 1374 1483 1548 1690
Water conn(NPS-in)4466666888888
3 pass arrangement
Min flow (gpm) 129 143 135 145 161 145 161 206 226 250 270 282 307
Max flow (gpm) 473 523 494 531 589 531 589 756 829
916 989 1032 1127
Water conn(NPS-in)3.53.544444666888
Fin and tube
Qty of coils#4444444888888
Coil length (in)
156/
156
180/
156
180/
180
216/
180
216/
216
252/
216
252/
252
180/
108
216/108 252/108 216/216 252/216 252/252
Coil height (in) 42 42 42 42 42 42 42 42 42 42 42 42 42
(mm) 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067
# of rows#3333333333333
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192
Direct drive propeller
Quantity # 4/4 5/4 5/5 6/5 6/6 7/6 7/7 10/6 12/6 14/6 12/12 14/12 14/14
Diameter (in) 30.0 30.0 30.0 30.0 30.0 30.0 30.0
30.0 30.0 30.0 30.0 30.0 30.0
Air flow per fan (cfm) 9625 9394 9209 9209 9209 9210 9210 9209 9209 9208 9209 9210 9214
Power/motor (hp) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Fan speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140
Tip speed (Ft/min) 8954 8954 8954 8954 8954 8954 8954 8954 8954 8954 8954 8954 8954
HFC-134a
# Refrig ckts#2222222222222
% min load%15151515151515151515151515
Refrigerant charge (lb)
165/
165
175/
165
175/
175
215/
210
215/
215
225/
215
225/
225
365/
200
415/200 460/200 415/415 460/415 460/460
Oil charge (gal)
1.3/
1.3
1.3/
1.3
1.3/
1.3
1.9/
1.3
1.9/
1.9
1.9/
1.9
1.9/
1.9
4.2/1.9 4.6/2.9 4.6/1.9 4.6/4.6 4.6/4.6 4.6/4.6
Min ambient-std (°F) 25 25 25 25 25
25 25 25 25 25 25 25 25
Min ambient-low(°F)0000000000000
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
General Data
12 RTAC-SVX01J-EN
Table 1. General Data - 60 hz units - standard efficiency - IP
Compressor
Evaporator
Condenser
Fan
General Unit
General Data
RTAC-SVX01J-EN 13
Table 2. General Data - 60 hz units - high efficiency - IP
Size 140 155 170 185 200 225 250 275 300 350 400
Compressor
Screw
Quantity #22222223344
Nominal size
@60Hz
(tons) 70/70 85/70 85/85 100/85 100/100 120/100 120/120
85-85/
100
100-100/
100
85-85/
85/85
100-100/
100-100
Evaporator
Flooded
Water storage(gal)34364039434343727283 91
2 pass arrangement
Min flow (gpm) 202 217 241 217 241 241 241 375 375 404 461
Max flow (gpm) 741 796 883 796 883 883 883 1374 1374 1483 1690
Water conn(NPS-in)66666668888
3 pass arrangement
Min flow (gpm) 135 145 161 145 161 161 161 250 250 270 307
Max flow (gpm) 494 531 589 531 589 589 589 916 916 989 1127
Water conn(NPS-in)44444446688
Condenser
Fin and tube
Qty of coils#44444888888
Coil length (in) 180/180 216/180 216/216 252/216 252/252 144/144 144/144 216/144 252/144 216/216 252/252
Coil height (in) 42 42 42 42 42 42 42 42 42 42 42
Number of rows # 192 192 192 192 192 192 192 192 192 192 192
Fins per foot(fpf)33333333333
Fan
Direct drive propeller
Quantity # 5/5 6/5 6/6 7/6 7/7 8/6 8/8 12/6 14/6 12/12 14/14
Diameter(in)30303030303030 303030 30
Air flow/fan (cfm) 9199 9199 9199 9200 9201 9783 9203 9652 9605 9199 9201
Power/motor (hp) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Fan speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140
Tip speed (Ft/Min) 8954 8954 8954 8954 8954 8954 8954 8954 8954 8954 8954
General unit
HFC-134a
# Refrig ckts#22222222222
% min load%15151515151515151515 15
Refrigerant charge (lb) 175/175 215/205 215/215 225/215 225/225 235/235 235/235 415/200 460/200 415/415 460/460
Oil charge (gal) 1.3/1.3 1.3/1.3 1.3/1.3 1.9/1.3 1.9/1.9 1.9/1.9 1.9/1.9
2.1-2.1/
1.9
2.3-2.3/
1.9
2.1-2.1/
2.1-2.1
2.3-2.3/
2.3-2.3
Min ambient-std (°F) 25 25 25 25 25 25 25 25 25 25 25
Min ambient-low(°F)00000000000
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
General Data
14 RTAC-SVX01J-EN
Table 3. General Data - 60 hz units - extra efficiency - IP
Size 140 155 170 185 200 250 275 300 350
Compressor
Screw
Quantity #222223 3 4 4
Nominal size
@60Hz
(tons) 70/70 85/70 85/85 100/85 100/100 70-70/85 85-85/85
70-70/
70-70
85-85/
85-85
Evaporator
Flooded
Water storage (gal) 40 39 43 43 43 72 72 83 91
2 pass arrangement
Min flow (gpm) 241 217 241 241 241 375 375 404 461
Max flow (gpm) 883 796 883 883 883 1374 1374 1483 1690
Water conn (NPS-in) 6 6 6 6 6 8 8 8 8
3 pass arrangement
Min flow (gpm) 161 145 161 161 161 250 250 270 307
Max flow (gpm) 589 531 589 589 589 916 916 989 1127
Water conn (NPS-in) 4 4 4 4 4 6 6 8 8
Condenser
Fin and tube
Qty of coils # 4 4 4 8 8 8 8 8 8
Coil length (in) 216/216 252/216 252/252 144/144 180/180 216/144 252/144 216/216 252/252
Coil height (in) 42 42 42 42 42 42 42 42 42
Number of rows # 192 192 192 192 192 192 192 192 192
Fins per foot (fpf) 3 3 3 3 3 3 3 3 3
Fan
Direct drive propeller
Quantity # 6/6 7/6 7/7 8/6 8/8 12/6 14/6 12/12 14/14
Diameter(in)3030303030303030 30
Air flow/fan (cfm) 9199 9200 9201 9783 9203 9652 9605 9199 9201
Power/motor (hp) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Fan speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140
Tip speed (Ft/Min) 8954 8954 8954 8954 8954 8954 8954 8954 8954
General unit
HFC-134a
# Refrig ckts # 2 2 2 2 2 2 2 2 2
% min load%15151515151515 1515
Refrigerant charge (lb) 215/215 225/215 225/225 235/235 235/235 415/200 460/200 415/415 460/460
Oil charge (gal) 1.3/1.3 1.9/1.3 1.9/1.9 1.9/1.9 1.9/1.9 2.1-2.1/1.9 2.1-2.1/1.9
2.1-2.1/
2.1-2.1
2.1-2.1/
2.1-2.1
Min ambient-std (°F) 25 25 25 25 25 25 25 25 25
Min ambient-low (°F) 0 0 0 0 0 0 0 0 0
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
General Data
RTAC-SVX01J-EN 15
Table 4. General Data - 60 hz units - standard efficiency - SI
Size 140 155 170 185 200 225 250 275 300 350 400 450 500
Compressor
Screw
Quantity # 2222222 3 3 3 4 4 4
Nominal size
(tons) @60Hz
70/70 85/70 85/85 100/85
100/
100
120/
100
120/
120
85-85/
100
100-100/
100
120-120/
100
100-100/
100-100
120-120/
100-100
120-120/
120-120
Evaporator
Flooded
Water storage (L) 110.0 121 129 136 151 148 163 235 254 273 314 326 344
2 pass arrangement
Min flow (L/s) 12 14 13 14 15 14 15 19 21 24 25 27 29
Max flow (L/s) 45 50 47 50 56 50 56 72 78 87 94 98 107
Water conn (NPS-in) 4 4 6 6 6 6 6 8 8 8 8 8 8
3 pass arrangement
Min flow (L/s) 8 9 9 9 10 9 10 13 14 16 17 18 19
Max flow (L/s) 30 33 31 34 37 34 37 48 52 58 62 65 71
Water conn (NPS-in) 3.5 3.5 4 4 4 4 4 6 6 6 8 8 8
Condenser
Fin and tube
Qty of coils # 4 4 4 4 4 4 4 8 8 8 8 8 8
Coil length (mm)
3962/
3962
4572/
3962
4572/
4572
5486/
4572
5486/
5486
6400/
5486
6400/
6400
4572/
2743
5486/
2743
6400/
2743
5486/
5486
6400/
5486
6400/
6400
Coil height (mm) 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067
# of rows # 3 3 3 3 3 3 3 3 3 3 3 3 3
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192
Fan
Direct drive propeller
Quantity # 4/4 5/4 5/5 6/5 6/6 7/6 7/7 10/6 12/6 14/6 12/12 14/12 14/14
Diameter (mm) 726.0 726.0 726.0 726.0 726.0 726.0 726.0 726.0 726.0 726.0 726.0 726.0 726.0
Air flow per fan (m³/hr) 16351 15958 15644 15644 15644 15646 15647 15644 15645 15642 15645 15646 15653
Power/motor (kW) 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12
Fan speed (rps) 19 19 19 19 19 19 19 19 19 19 19 19 19
Tip speed M/S 45 45 45 45 45 45 45 45 45 45 45 45 45
General Unit
HFC-134a
# Refrig ckts # 2 2 2 2 2 2 2 2 2 2 2 2 2
% min load % 15 15 15 15 15 15 15 15 15 15 15 15 15
Refrigerant
charge
(kg) 75/75 79/75 79/79 98/95 98/98 102/98
102/
102
166/91 188/91 209/91 188/188 209/188 209/209
Oil charge (L) 5/5 5/5 5/5 7/5 7/7 7/7 7/7 8-8/7 9-9/11 9-9/11 9-9/9-9 9-9/9-9 9-9/9-9
Min ambient-std (°C) -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9
Min ambient-low (°C) -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
General Data
16 RTAC-SVX01J-EN
Table 5. General Data - 60 hz units - high efficiency - SI
Size 140 155 170 185 200 225 250 275 300 350 400
Compressor
Screw
Quantity#2222233444 4
Nominal size
@60Hz
(tons) 70/70 85/70 85/85 100/85 100/100 70-70/85 85-85/85
70-70/
70-70
85-85/
85-85
85-85/
85/85
100-100/
100-100
Evaporator
Flooded
Water storage (L) 129 136 151 148 163 163 163 273 273 314 344
2 Pass arrangement
Min flow(L/s)13141514151515242425 29
Max flow(L/s)47505650565656878794107
Water conn(NPS-in)6666666888 8
3 Pass arrangement
Min flow (L/s) 9 9 10 9 10 10 10 16 16 17 19
Max flow(L/s)31343734373737585862 71
Water conn(NPS-in)4444444668 8
Condenser
Fin and tube
Qty of coils#4444488888 8
Coil length (mm)
4572/
4572
5486/
4572
5486/
5486
6400/
5486
6400/
6400
3657/
3657
3657/
3657
5486/
3657
6400/
3657
5486/
5486
6400/
6400
Coil height (mm) 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067
Number of rows # 192 192 192 192 192 192 192 192 192 192 192
Fins per foot(fpf)3333333333 3
Fan
Direct drive propeller
Quantity # 5/5 6/5 6/6 7/6 7/7 8/6 8/8 12/6 14/6 12/12 14/14
Diameter (mm) 762 762 762 762 762 762 762 762 762 762 762
Air per fan (m³/hr) 15628 15628 15628 15629 15631 16619 15634 16397 16317 15628 15631
Power/motor (kW) 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12
Fan speed (rps) 19 19 19 19 19 19 19 19 19 19 19
Tip speedM/S45454545454545454545 45
General unit
HFC-134a
# refrig ckts#2222222222 2
% min load%15151515151515151515 15
Refrig charge (kg) 79/79 98/93 98/98 102/98 102/102 107/107 107/107 188/91 209/91 188/188 209/209
Oil charge (L) 5/5 5/5 5/5 7/5 7/7 7/7 7/7 8-8/7 9-9/7 8-8/8-8 9-9/9-9
Min ambient-std (°C) -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9
Min ambient-low (°C) -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
General Data
RTAC-SVX01J-EN 17
Table 6. General Data - 60 hz units - extra efficiency - SI
Size 140 155 170 185 200 250 275 300 350
Compressor
Quantity#22222334 4
Nominal size
@60Hz
(tons) 85/85 100/85 100/100 120/100 120/120 85-85/100
100-100/
100
85-85/85/
85
100-100/
100-100
Evaporator
Flooded
Water storage (L) 151 148 163 163 163 273 273 314 344
2 Pass arrangement
Min flow(L/s)1514151515242425 29
Max flow(L/s)5650565656878794107
Water conn(NPS-in)66666888 8
3 Pass arrangement
Min flow (L/s) 10 9 10 10 10 16 16 17 19
Max flow(L/s)3734373737585862 71
Water conn(NPS-in)44444668 8
Condenser
Fin and tube
Qty of coils#44488888 8
Coil length (mm) 5486/5486 6400/5486 6400/6400 3657/3657 4572/2743 5486/3657 6400/3657 5486/5486 6400/6400
Coil height (mm) 1067 1067 1067 1067 1067 1067 1067 1067 1067
Number of rows # 192 192 192 192 192 192 192 192 192
Fins per foot(fpf)33333333 3
Fan
Direct drive propeller
Quantity # 6/6 7/6 7/7 8/6 8/8 12/6 14/6 12/12 14/14
Diameter (mm) 762 762 762 762 762 762 762 762 762
Air per fan (m³/hr) 15628 15629 15631 16619 15634 16397 16317 15628 15631
Power/motor (kW) 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12
Fan speed (rps) 19 19 19 19 19 19 19 19 19
Tip speedM/S4545454545454545 45
General unit
HFC-134a
# refrig ckts#22222222 2
% min load%1515151515151515 15
Refrig charge (kg) 98/98 102/98 102/102 107/107 107/107 188/91 209/91 188/188 209/209
Oil charge (L) 5/5 7/5 7/7 7/7 7/7 8-8/7 8-8/7 8-8/8-8 8-8/8-8
Min ambient-std (°C) -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9
Min ambient-low (°C) -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
General Data
18 RTAC-SVX01J-EN
Table 7. General Data - 50 hz units - standard efficiency - IP
Size 140 155 170 185 200 250 275 300 350 375 400
Compressor
Screw
Quantity #2222233344 4
Nominal
size@50Hz
(tons) 70/70 85/70 85/85 100/85 100/100
70-70 /
100
85-85 /
100
100-100/
100
85-85/
85-85
100-100/
85-85
100-100/
100-100
Evaporator
Flooded
Water storage (gal) 29 32 34 36 40 56 62 67 75 79 83
2 pass arrangement
Min flow (gpm) 193 214 202 217 241 265 309 339 351 381 404
Max flow (gpm) 709 785 741 796 883 970 1134 1243 1287 1396 1483
Water conn (NPS-in) 4 4 6 6 6 8 8 8 8 8 8
3 pass arrangement
Min flow (gpm) 129 143 135 145 161 176 206 226 234 254 270
Max flow (gpm) 473 523 494 531 589 647 756 829 858 930 989
Water conn (NPS-in) 3.5 3.5 4 4 4 6 6 6 8 8 8
Condenser
Fin and tube
Qty of coils # 4 4 4 4 4 8 8 8 8 8 8
Coil length (in) 156/156 180/156 180/180 216/180 216/216 156/108 180/108 216/108 180/180 216/180 216/216
Coil height (in) 42 42 42 42 42 42 42 42 42 42 42
Number of rows # 3 3 3 3 3 3 3 3 3 3 3
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192
Fan
Direct drive propeller
Quantity # 4/4 5/4 5/5 6/5 6/5 8/6 10/6 12/6 10/10 12/10 12/12
Diameter(in)30303030303030303030 30
Air flow per fan (cfm) 7918 7723 7567 7567 7567 7764 7566 7567 7567 7567 7567
Power per motor (hp) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Fan speed (rpm) 950 950 950 950 950 950 950 950 950 950 950
Tip speed (Ft/min) 7461 7461 7461 7461 7461 7461 7461 7461 7461 7461 7461
General unit
HFC-134a
# refrig ckts # 2 2 2 2 2 2 2 2 2 2 2
% min load%15151515151515151515 15
Refrig charge (lb) 175/175 215/205 215/215 225/215 225/225 235/235 235/235 415/200 460/200 415/415 460/460
Oil charge (gal) 1.3/1.3 1.3/1.3 1.3/1.3 1.9/1.3 1.9/1.9
2.1-2.1/
1.9
2.1-2.1/
1.9
2.3-2.3/
1.9
2.1-2.1/
2.1-2.1
2.3-2.3/
2.1-2.1
2.3-2.3/
2.3-2.3
Min ambient-std (°F) 25 25 25 25 25 25 25 25 25 25 25
Min ambient-low (°F) 0 0 0 0 0 0 0 0 0 0 0
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
General Data
RTAC-SVX01J-EN 19
Table 8. General Data - 50 hz units - high efficiency - IP
Size 120 130 140 155 170 185 200 250 275 300 350 375 400
Compressor
Screw
Quantity # 22222223 3 3 4 4 4
Nominal
size@50Hz
(tons) 60/60 70/60 70/70 85/70 85/85 100/85
100/
100
70-70 /
100
85-85 /
100
100-100/
100
85-85 /
85-85
100-100/
85-85
100-100/
100-100
Evaporator
Flooded
Water storage(gal)2932343640394367 72 72 83 86 91
2 pass arrangement
Min flow (gpm) 193 214 202 217 241 217 241 339 375 375 404 422 461
Max flow (gpm) 709 785 741 796 883 796 883 1243 1374 1374 1483 1548 1690
Water conn (NPS-in) 4 4 6 6 6 6 6 8 8 8 8 8 8
3 pass arrangement
Min flow (gpm) 129 143 135 145 161 145 161 226 250 250 270 282 307
Max flow (gpm) 473 523 494 531 589 531 589 829 916 916 989 1032 1127
Water conn (NPS-in) 3.5 3.5 4 4 4 4 4 6 6 6 8 8 8
Condenser
Fin and tube
Qty of coils# 4444444 8 8 8 8 8 8
Coil length (in)
156/
156
180/
156
180/
180
216/
180
216/
216
252/
216
252/
252
180/108 216/144 252/144 216/216 252/216 252/252
Coil height (in) 42 42 42 42 42 42 42 42 42 42 42 42 42
Number of rows# 3333333 3 3 3 3 3 3
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192 192 192
Fan
Direct drive propeller
Quantity # 4/4 5/4 5/5 6/5 6/6 7/6 7/7 10/6 12/6 14/6 12/12 14/12 14/14
Diameter(in)30303030303030 30 30 30 30 30 30
Air flow per fan (cfm) 62484 68819 7558 7557 7557 7558 7559 7561 7943 7906 7557 7490 7559
Power/motor (hp) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Fan speed (rpm) 950 950 950 950 950 950 950 950 950 950 950 950 950
Tip speed (Ft/min) 7461 7461 7461 7461 7461 7461 7461 7461 7461 7461 7461 7461 7461
General unit
HFC-134a
# refrig ckts# 2222222 2 2 2 2 2 2
% min load% 15151515151515 15 15 15 15 15 15
Refrig charge (lb)
165/
165
175/
165
175/
175
215/
205
215/
215
225/
215
225/
225
365/200
415/
200
460/
200
415/
415
460/
415
460/
460
Oil charge (gal) 1.3/1.3 1.3/1.3 1.3/1.3 1.3/1.3 1.3/1.3 1.9/1.3 1.9/1.9
2.1-2.1/
1.9
2.1-2.1/
1.9
2.3-2.3/
1.9
2.1-2.1/
2.1-2.1
2.3-2.3/
2.3-2.3
2.3-2.3/
2.3-2.3
Min ambient-std (°F) 25 25 25 25 25 25 25 25 25 25 25 25 25
Min ambient-low (°F) 0 0 0 0 0 0 0 0 0 0 0 0 0
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
General Data
20 RTAC-SVX01J-EN
Table 9. General Data - 50 hz units - standard efficiency - SI
Size 140 155 170 185 200 250 275 300 350 375 400
Compressor
Screw
Quantity #222223334 4 4
Nominal
size@50Hz
(tons) 70/70 85/70 85/85 100/85 100/100
70-70 /
100
85-85 /
100
100-100/
100
85-85/
85-85
100-100/
85-85
100-100/
100-100
Evaporator
Flooded
Water storage (L) 110 121 129 136 151 212 235 254 284 299 314
2 pass arrangement
Min flow(L/s)121413141517192122 24 25
Max flow(L/s)455047505661727881 88 94
Water conn(NPS-in)446668888 8 8
3 pass arrangement
Min flow(L/s)899910111314151617
Max flow(L/s)303331343741485254 59 62
Water conn(NPS-in)3.53.54446668 8 8
Condenser
Fin and tube
Qty of coils#444448888 8 8
Coil length (mm)
3962/
3962
4572/
3962
4572/
4572
5486/
4572
5486/
5486
3962/
2743
4572/
2743
5486/
2743
4572/
4572
5486/
4572
5486/
5486
Coil height (mm) 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067 1067
Number of rows#333333333 3 3
Fins per foot (fpf) 192 192 192 192 192 192 192 192 192 192 192
Fan
Direct drive propeller
Quantity # 4/4 5/4 5/5 6/5 6/6 8/6 10/6 12/6 10/10 12/10 12/12
Diameter (mm) 762 762 762 762 762 762 762 762 762 762 762
Air flow per fan (m³/hr) 13452 13120 12855 12855 12855 13190 12853 12856 12854 12855 12855
Power per motor (kW) .74 .74 .74 .74 .74 .74 .74 .74 .74 .74 .74
Fan speed (rps) 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8 15.8
Tip speedM/S383838383838383838 38 38
General unit
HFC-134a
# refrig ckts#222222222 2 2
% min load%151515151515151515 15 15
Refrig charge (kg) 79/79 98/93 98/98 102/98 102/102 107/107 107/107 188/91 209/91 188/188 209/209
Oil charge (L) 5/5 5/5 5/5 7/5 7/7 8-8/7 8-8/7 8-8/7 8-8/8-8 9-9/8-8 9-9/9-9
Min ambient-std (°C) -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9 -3.9
Min ambient-low (°C) -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8 -17.8
1. Data containing information on two circuits is shown as follows: ckt 1/ ckt 2.
2. Minimum start-up/operating ambient is based on a 5 mph wind across the condenser.
3. RTAC units must only operate with refrigerant R-134a and Trane Oil 00048.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170

Trane R Series Installation, Operation and Maintenance Manual

Type
Installation, Operation and Maintenance Manual