Seasonpak PWA-041A

McQuay Seasonpak PWA-041A Installation And Maintenance Data

  • Hello! I am an AI chatbot trained to assist you with the McQuay Seasonpak PWA-041A Installation And Maintenance Data. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
BULLETIN NO. IM 126
AUGUST 1969
INSTALLATION AND
MAINTENANCE DATA
PACKAGED WATER CHILLER
TYPE WHR
7%
THRU 120 TONS
“McQUAY”
and
“SEASON PAK” are registered trademarks of
McQuay,
Inc., Minneapolis, Minnesota.
@ 1969
McQuay,
Inc.
TABLE OF CONTENTS
CONTROLS-CHECKING
..................................
24
CROSSREFERENCE
-
NEW TO OLD MO
.............
2
ELECTRICAL
.......................................
22-23
CONTROL CENTER SERVICE
...........................
26-27
ELECTRICALDATA
..................................
22-23
WIRING
...........................................
10-13
WIRING DIAGRAMS
...................................
14-21
MAINTENANCE......................................
26-29
MOVING
&
PLACING THE UNIT
..........................
2
NOMENCLATURE
.....................................
2
OPERATION
......................................... 24
PIPING
REFRIGERANT
....................................... 8-9
WATER............................................
6-7
PRE-INSTALLATION
.....................................
2
REPLACEMENT PARTS
...................................
30
SERVICE & MAINTENANCE
..............................
26-29
START-UP PROCEDURE
..................................
24
TROUBLE SHOOTING CHART.
............................
27-29
VIBRATION ISOLATORS
.................................
3-5
NOMENCLATURE
Nominal Capacity (Tons)
WH
R_OsOA-
l+Basic
unit with water cooled condenser(s).
-2kBasic
unit with mounted receiver(s) in lieu of condenser(s).
-3&Basic
unit less condenser(s) or receiver(s).
CROSS REFERENCE
-
NEW TO OLD MODEL NUMBERS
New model numbers represent a
change
in model number designation
only, NOT a change in unit design or performance.
PRE-INSTALLATION
INSPECTION
with a full refrigerantcharge.A holding charge is sup-
When the equipment is received, all items should be
plied in condenserless models (Arrangements 2 & 3).
carefully checked to make sure that all crates and
For shipment, the charge is contained in the
conden-
cartons have been received. All units should be
care-
ser and is isolated by the manual condenser liquid
fully inspected for damage when received. All damage
valve and the compressor discharge service valve.
should be reported immediately to the carrier and a
Should the unit be damaged, allowing the refrigerant
claim filed for damage.
to escape, there may be danger of suffocation in the
equipment area since the refrigerant will displace the
HANDLING
air. Care
should
be taken to avoid rough handling or
shock due to dropping the unit. NEVER LIFT, PUSH
Every model WHR SEASONPAK water chiller with
OR PULL UNIT FROM ANYTHING OTHER THAN
water cooled condensers (Arrangement 1) is supplied
THE BASE.
MOVING AND PLACING THE UNIT
MOVING THE UNIT
The
McQUAY
SEASONPAK water chiller is mounted
on heavy wooden skids to protect the unit from ac-
cidental damage and to permit easy handling and mov-
ing.
It is recommended that
all
moving and handling be
performed with the skids under the unit when possible
and that the skids not be removed until the unit is in
the final location.
When moving the unit, dollies or simple rollers can
be used under the skids, or dollies alone can be used
under ends of the frame. Do not use pipe rollers under
the unit if the skids have been removed.
The 4
channel base is arranged on the skid so
that the fork of a standard fork lift truck can be slid
easily under (See Figure 1). The forks of the fork lift
truck must be across both the front and rear channels
before
lifting.Never
put the weight of the unit against
the condensers.
In moving, always apply pressure to the base on
skids only and not to the piping or shells. A long bar
helps move the unit easily. Avoid dropping the unit at
the end of the roll.
If the unit must be hoisted, it is necessary to lift
from the skid or from the base as indicated in Figure
2, Page 3. A spreader bar must be used to protect the
control cabinet and other
areas
of the chiller.
Do not attach slings to piping or equipment. Move
unit in the upright horizontal position at all times.
Let unit down gently when iowering from the trucks or
rollers.
Page 2
FIGURE NO. 1
MOVING UNIT WITH FORK LIFT
NOTE:
ALWAYS LIFT ON SIDE OPPOSITE THE
CONTROL PANEL TO AVOID DAMAGING
THE CONTROLS.
LOCATION
Unit is designed for indoor application and must be
located in an area where the surrounding ambient tem-
peratures are 40F or above. A good rule of thumb is
to place units where ambients are at least 5 degrees
above the leaving water temperature.
Because of the electric control devices, the units
should not be exposed to the weather. A plastic cover
over the control box is supplied as temporary protec-
tion during transfer.
A reasonably level and sufficiently strong floor is
all that is required for the SEASONPAK water chiller.
If necessary, additional structural members should be
provided to transfer the weight of the unit to the near-
est beams. Refer to Page 4 for foundation information.
SPACE REQUIREMENTS FOR CONNECTIONS
AND SERVICING
The c h i I led water piping for all units enters and
leaves the cooler from the rear. A clearance of 3 to 4
feet should be provided for this piping and for replac-
ing the fi Iter-driers, for servicing the solenoid valves,
or for changing the compressors, should it ever be-
come necessary.
The condenser water piping enters and leaves the
shell from the ends. Work space must be provided in
case water regulating valves are being used and for
general servicing.
Clearance should be provided for removing cooler
tubes on one end of the unit as specified in Table 1.
Condenser tubes cannot be replaced. It is also desir-
able to leave a small walk area on the end opposite
that used for replacement of a cooler tube.
MINIMUM CLEARANCE FOR COOLER TUBE RE-
MOVAL MEASURED FROM CENTER LINE OF
CHILLED WATER CONNECTION ON EITHER END
TABLE NO. 1
MINIMUM CLEARANCE
UNIT SIZE
I
MINIMUM CLEARANCE
007A THRU 015A 72”
020A THRU 041A
96”
050A THRU 070A
108”
080A
120”
FIGURE NO. 2
SUGGESTED RIGGING
OTE:ALWAYS USE SPREADER
BARS TO PROTECT UNIT
FROM DAMAGE.
PLACING THE UNIT
The small amount of vibration normally encountered
with the SEASONPAK water chiller makes this unit
particularly desirable for basement or ground floor in-
stallations where the unit can be bolted directly to
the floor. The floor construction should be such that
the unit wi II not affect the bui
lding
structure, or trans-
mit noise and vibration into the structure. See VI-
BRATION ISOLATORS section for additional mount-
ing information. Hold down bolt locations are indicated
in Figures 3 and 4, Page 4.
VIBRATION ISOLATORS
Rubber-in-shear or spring isolators can be furnished
and field placed under each corner of the package. It
is recommended that a rubber-in-shear pad be used as
the minimum isolation on all upper level installations
or areas in which vibration transmission is a consid-
eration.
Transfer the unit as indicated under MOVING THE
UNIT, or use the methods as indicated in Figures 1
and 2. In all cases, set the unit in place and level
with a spirit level. When spring type isolators are re-
quired, install springs running under the main side
channels. Foundation hold down bolt locations for vi-
bration isolators are given in Figures 3 & 4. A
rubber-
anti -skid pad should be standard under isolators if
hold down bolts are not used.
Vibration eliminators in all water piping connected
to the SEASONPAK water chiller are recommended to
avoid straining the piping and transmitting vibration
and noise.
I
090A THRU
1OOA
i
1 OX”
I
I
110A
THRU
120A
I
132"
I
Page 3
WATER PIPING
GENERAL
Piping practices vary considerably. In most cases,
codes,
local ordinances and established practices
govern the selection and installation of piping. Local
building and safety codes and ordinances should be
studied and complied with.
Shut-off valves should be provided at the unit so
that normal servicing can be accomplished without
draining the system.
It is recommended that temperature and pressure in-
dicators be installed at the inlet and outlet of the
shells to aid in the normal checking and servicing of
the unit. Also, the installation of wire mesh strainers
at the pump suction will protect the pump and shells
from foreign matter.
be
A preliminary leak check of the water piping should
made before filling the system.
Vibration eliminators are recommended in all lines
connected to the SEASONPAK water chiller.
CHILLED WATER PIPING
The water flow entering the cooler must always be on
the end nearest the expansion valves and cooler re-
frigerant connections to assure proper expansion valve
operation and unit capacity.
Design the piping so that is has a minimum number
of changes in elevation. Include manual or automatic
vent valves at the high points of the chilled water
piping, so that air can be vented from the water cir-
cuit. System pressures can be maintained by using an
expansion tank or a combination pressure relief and
reducing valve.
All chilled water piping should be insulated to pre-
vent the nuisance of water dripping from the lines. If
insulation is not of the self-contained vapor barrier
type, it should be covered with a moisture seal. Do not
insulate piping until it has been tested for leaks and
drain connections have been extended beyond the pro-
FIGURE NO. 7
TO COOI.ER
4
posed insulation thickness to make them accessible.
CHILLED WATER THERMOSTAT
WHR-008A
thru 060A
-
The chilled water thermostat
is mounted inside the control console and the control
bulb, capillary tubing and control bulb immersion well
are attached to the unit with spring clips, The control
bulb well
must be
field inserted in the first tee install-
ed in the return water line as shown in Figure 7. The
bulb well is supplied with a
1/2"
NPT male thread.
Carefully unsnap the well from the holding clips, re-
d?
move the retaining bushing and
slowly remove the bulb
from the well. Install into piping as indicated in Fig-
ure 7. When installing the bulb, carefully remove it
from the well so as to not wipe off the heat
conduct-
ing compound supplied in the well. After installing
the well, carefully insert the bulb and seal in with
the excess compound. Insert the retaining gasket
and
sealing bushing and clip or tape the cap tube to the
water line. Care should be taken not to break or kink
the charged capillary tubing. Sufficient cap tube length
is provided for bulb insertion up to 10 feet from the
unit; however, it is recommended that the bulb well
be placed as close to the cooler inlet as possible.
Insulate over thermostat well.
WHR-070A thru 120A
-
The chilled water thermostat
is mounted inside the control console. The control
bulb is mounted in a well, located in the return water
connection to the unit. Care should be taken not to
kink or break the charged capillary tubing when work-
ing around the unit. It is also advisable to check the
cap tube before running the unit to be sure that it is
firmly anchored and not rubbing on the frame or any
other component.
CAUTION: The thermostat bulb should not be exposed
to water temperatures above 140F since this will
damage the control.
THERMOSTAT WELL INSTALLATION
RETURN WATER
‘h’
N.P.T.
Page 6
CONDENSER
-
WATER PIPING
General
_.-
For the best performance, the condenser water inlet
is established as the bottom connection of the con-
denser.
Water cooled condensers may be piped for well
water applications, or for use in conjunction with a
cooling tower. Cooling tower applications should in-
clude a small amount of waste circulating water to
prevent building up of solids in the tower basin.
Head Pressure Control
Some means of controlling operating head pressure
must be
provided.
A three way pressure actuated water
regulating valve is recommended for cooling tower ap-
plication, as indicated in Figure 8. This arrange-
ment wi II maintain a constant condensing pressure, re-
gardless of temperature conditions and assures enough
head pressure for proper thermal expansion valve op-
eration. Full water flow is assured to the tower with
this arrangement.
Well Water
Where well water is used for condensing refrigerant, a
direct acting water regulating valve is
recommended-
See Figure 9. The valve is n
orma
I ly installed at
the outlet of the condenser. On shut down, the valve
will close and, in this way, prevents water siphoning
out of the condenser. Siphoning causes drying of the
water side of the condenser and rapid buildup of foul-
ing. When no valve is used, a loop at the outlet end
is recommended
-
See Figure 9.
WATER REGULATING VALVES (EACH CONDENSER)
FIGURE NO. 8
3 WAY WATER
REGULATING VALVES
COi:lNG
TOWER
/
PURGE
4
MAIN
CONDENSER
WATER SUPPLY
FROM PUMP
BY
PASS
BA
LANCING
VALVES OR COCKS
FIGURE NO. 9
LOOP REQUIRED WHEN NO
REGULATING VALVE
IS
USED
,
l
TO DRAIN
\
FROM MAIN
CONDENSER
PUMP
DIRECT ACTING WATER
REGULATING VALVE
COOLING TOWER SYSTEM
WELL WATER COOLING SYSTEM
WATER FLOW SAFETY SWITCH (OPTIONAL)
A water flow safety switch is available as optional
equipment for all Type WHR chillers. The flow switch
must
be field installed and wired into the SEASONPAK
water chiller control center as indicated on the draw-
ings.
The flow switch should be installed in a horizontal
run in either the supply or return chilled water piping
as follows:
1. Apply pipe sealing compound to only the threads of
the switch and screw unit into D’ x D’ x
1”
reducing
tee(See Figure 10). The flow arrow must be pointed
FIGURE NO. 10
r
FLOW SWITCH
--._,
PADDLE
Ud
FLOW SWITCH
in the correct direction.
2. Piping should provide for a straight length before
and after the flow switch of at least 5 times the
pipe diameter.
CAUTION: Make sure the arrow on the side of the
switch is pointed in the proper direction of flow.
The flow switch is designed to handle the control
voltage and shouldonly be connected according to the
wiring diagram (See Wiring Diagram inside control
box door).
PIPE SECTION
4
FLOW DIRECTION
TEE
D’
x
D*
x
I*
VIEW FROM END OF COOLER
Page 7
REFRIGERANT PIPING
REMOTE AIR COOLED CONDENSERS
For remote condenser application, such as an air
cooled condenser, the chillers, with and without
mounted receivers, are shipped containing a Refriger-
ant-22 holding charge. It is important that the unit be
kept tightly closed until the remote condenser is in-
stalled, piped to the unit and the high side evacuated.
Refrigerant piping,to and from the remote unit,
should be sized and installed according to the latest
ASHRAE
Guide. It is important that the piping be
properly supported with sound and vibration insulation
between tubing and hangerand that the discharge lines
be looped at the condenser and trapped at the com-
pressor to prevent refrigerant liquid from draining into
the compressor discharge manifold. Looping the dis-
charge line also provides greater line flexibility.
The discharge gas valve, liquid line
solenoid,filter-
drier and moisture indicators are all provided as stan-
dard equipment with the SEASONPAK water chiller,
whether installed with remote or factory mounted re-
ceivers.
After the equipment is properly installed, the unit
may be charged with Refrigerant-22, then run at de-
sign load conditions, adding charge until the liquid
line sight-glass is clear, with no bubbles flowing to
expansion valve. Total operating charge will depend
on the air cooled condenser used and the length of
external piping, but generally will be equal to the
water cooled charge shown in Table 9, Page 26. With
SEASONTROL low ambient control on air cooled
units, additional charge must then be added, as re-
quired (but not to exceed receiver pumpdown capacity)
UNIT LESS CONDENSER
SEASONPAK water chillers without condensers or
with mounted receivers require field piping to a re-
mote condenser of some type. As mentioned under the
REMOTE CONDENSER section above, refrigerant
piping should be sized and installed according to the
latest ASHRAE Guide. The design of refrigerant pip-
ing when using air cooled condensers involves a num-
ber of considerations not commonly associated with
other types of condensing equipment. The following
discussion is intended for use as a general guide to
sound, economical and trouble-free piping of air cool-
ed condensers.
On remote condenser applications, discharge line
mufflers are recommended. The mufflers should be in-
stalled as close to the compressor discharge as pos-
sible, If oil separators are used, they will usually
perform the same function as a muffler and will elim-
inate the need for one. A muffler wi II reduce discharge
line pulsations; particularly those which occur during
unloaded compressor operation
Discharge lines must be designed to handle oil
properly and to protect the compressor from damage
that may result from condensing liquid refrigerant in
the line during shutdown. Total friction loss for dis-
charge lines of
3 psi is considered good design. Care-
ful consideration must be given for sizing vertical
risers to insure that gas velocities are sufficient at
all operat,ing conditions to carry oil. If the velocity
in a vertical discharge riser is too low, considerable
oil may collect in the riser and the horizontal header,
causing the compressor to lose its oil and resultant
damage due to lack of lubrication.
Another danger is when the compressor load is in-
creased, the oil that had collected during reduced
loads may be carried as a slug through the system
and back to the evaporator, where a sudden increase
of oil concentration may cause
slopover
and damage
to the compressor.
Any horizontal run of discharge piping should be
pitched away from the compressor approximately
1/4"
per foot or more. This is necessary to move by gravity
any oil lying in the header. Oil pockets must be
avoided as oil needed in the compressor would
col-
lect
at such points and the compressor crankcase may
become starved.
It is recommended that any discharge lines coming
into a horizontal discharge header rise above the
center line of the discharge header. This is necessary
to prevent any oil or condensed liquid from draining
to the top heads when the compressor is not running.
In designing liquid line, it is important that the
liquid reach the expansion valve with a minimum of
flash gas since this gas will reduce the capacity of
the valve. Because “flashing” can be caused by a
pressure drop in the liquid lines, the pressure losses
due to friction and changes in static head should be
kept to a minimum.
The liquid line from the condenser to the receiver
MUST be sized for sewer flow operation (100
fpm/ve-
locity
or less) and MUST be sloped to the receiver
with no traps in the line.
Any shut off valve in this
line must have an orifice area equal to the inside area
of the line. Free drainage in this line is essential to
permit gas from the receiver to vent back to the con-
denser. Failure to adequately size and slope this line
wi II force liquid to back up into the condenser causing
high head pressure and bubbling sight glass.
A check valve should be installed in the liquid line
on installations that require operation at outside am-
bients below 60F. This prevents liquid migration to
the condenser and helps maintain a supply of refriger-
ant in the receiver for initial start up.
Typical Arrangements
Figure No. 11,
Page 9 illustrates a typical piping
arrangement involving a remote air cooled condenser
located at a higher elevation than the compressor and
receiver. This arrangement is commonly encountered
when the air cooled condenser is on a roof and the
compressor and receiver are on grade level or in a
basement equipment room.
In this case,
the design of the discharge line is
very critical. If properly sized for full load condition,
the gas velocity might be too low at reduced loads to
carry oil up through the discharge line and condenser
coil. Reducing the discharge line size would increase
the gasvelocity sufficiently at reduced load condi-
tions; however,
when operating at
full
load, the line
might be greatly undersized and thereby create an ex-
cessive refrigerant pressure drop. This condition can
be overcome in one of the two following ways:
1. The discharge line may be properly sized for the
desired pressure drop at full load condition and an
oil separator installed at the bottom of the trap on
the discharge line from the compressor.
Page 8
2. A double riser discharge line may be used as shown
in Figure 12, Page 9. Line “A” should be sized
to carry the
oil
at minimum load condition and line
‘(
B
should be sized so that at the full load con-
dition both lines would carry oil.
The above two points are particularly important in
applications where the refrigerant receiver is directly
beneath the air cooled condensers. If two unlike air
cooled condensers or unequal piping is used, the re-
sultant unequal refrigerant pressure drop may cause
liquid to build up in one of the condenser coils, there-
by reducing its effective capacity.
Notice in all illustrations, the hot gas line is loop-
ed at the bottom and top of the vertical run. This is
done to prevent oil and condensed refrigerant from
flowing back into the compressor and causing damage
The highest point in the discharge line should always
be above the highest point in the condenser coi I; and
it is advisable to include a purging vent at this point
to release noncondensibles from the system.
Figure No. 13, below, i I I us t ra te s another very
common application where the air cooled condenser is
located on essentially the same level as the compress-
FIGURE NO. 11
PURGE
VALVE
DISCHARGE LINE
HECK VALVE
LIQUID LINE
FIGURE NO. 13
DISCHARGE LINE
I
TO EVAPORATOR
/
RECEIVER
LrQuro
LINE
(EVAPORATORS
or and receiver. The discharge line piping in this
case is not too critical. The principal problem en-
countered with this arrangement is that there is fre-
quently insufficient vertical distance to allow free
drainage of liquid refrigerant from the condenser coil
to the receiver.
To guard against gas binding in the receiver and
liquid buildup in the condenser coil, which are com-
mon to this arrangement, be certain that the receiver
is located as far below the condenser outlet as pos-
sible. The liquid line should be free of any traps or
loops and, if there are any horizontal runs, they
should be pitched down toward the receiver.
Figure No. 14, below, illustrates a third very
common application where two or more separate air
cooled condensers are piped together on a single
compressor.
First of all, it is very important that the two air
cooled condensers have the same capacity so that the
refrigerant pressure drop through each unit is equal.
Secondly, the piping should be arranged so that the
lengths of run to and from each air cooled condenser
are equal.
FIGURE NO. 12
PURGE
VALVE
LIQUID LINE
RECEIVER-
TiAp
(EVAPORATORS
FIGURE NO. 14
PURGE
VALVE
f
I
I I
I_
I
I I
I
I
1
CONDENSER
CONDENSER
\
I
(
x
EVAPORATOR
CHECKVALVE
\
Y
Page 9
ELECTRICAL
MODELS WHR-008A THRU 060A
FIGURE NO. 15
1.
FREEZESTAT (MANUAL RESET) 8. COMPRESSOR STARTING CONTACTORS
2. OIL FAILURE SWITCH (MANUAL RESET)
9. CONTROL CIRCUIT FUSE
3. LEAD LAG SWITCH 10. CIRCUIT BREAKERS
4. CONTROL RELAYS (BEHIND PANEL)
11. POWER CONNECTION TERMINAL BLOCK
5. WATER CONTROL THERMOSTAT 12. INDICATOR LIGHTS
6. HIGH (MANUAL RESET) AND LOW PRESSURE CUTOUTS
7. CONTROL SYSTEM ON -OFF SWITCH
FIGURE NO. 16
MODELS WHR-070A THRU 120A
1. FREEZESTAT (MANUAL RESET) 7. CONTROL SYSTEM ON
-OFF
SWITCH
2. OIL FAILURE SWITCH (MANUAL RESET)
8. COMPRESSOR STARTING CONTACTORS
3.
LEAD LAG SWITCH 9. CONTROL CIRCUIT FUSE
4.
CONTROL RELAYS (BEHIND PANEL) 10. CIRCUIT BREAKERS
5.
WATER CONTROL THERMOSTAT
11. POWER CONNECTION TERMINAL BLOCK
6.
HIGH (MANUAL RESET) AND LOW PRESSURE CUTOUTS 12. INDICATOR LIGHTS
Page 10
c
4
ELECTRICAL
MODELS WHR-008A THRU 060A
FIELD WIRING
Only three main power leads need be hooked up to the
chiller on Models WHR-008A thru 060A. Models WHR-
070A thru 120A have a dual control panel, each sec-
tion handling one circuit of the unit and require separ-
ate service connections to each panel. Table 8, Page
22 gives the recommended lead wire size when only
three conductors are used in a raceway. Refer to the
National Electrical Code for othertype wire or special
instructions.
Although there is no specific requirement,
inter-
locking of a flow switch and the condenser pump start-
er (or air cooled condenser fan) is suggested for the
most dependable and economical system operation.
The cooler pump should operate continuously,
when the unit is not operating.
even
The condenser pump should be field interlocked by
connecting the pump starter coil to terminal 7 and
terminal 12 as shown on Schematic Wiring Diagrams 1
and 2 and terminals 8 & 14 and 12
&
14 on Schematic
Wiring Diagrams 3 and 4, Pages 14 thru 17. This
cycles the condenser pump (or air cooled condenser
fan) with the compressor.
Referring to Diagrams 1 thru 4, the flow switch is
interlocked by removing jumpers between terminals 13
and 14 for single units and 25 and 26 for dual units,
and wiring the switch contacts into the system as is
shown on the Schematic Wiring Diagrams. When so
wired, the chilled water pump must be operating be-
fore power can be applied to start this system.
Note
that the crankcase heaters will be energized regard-
less of water flow. The flow switch is recommended
and does not have the shortcomings of interlocking the
the cooler pump starter.
A flow switch must be used
for leaving water temperature of 42 F and lower.
STARTING SEQUENCE
(Refer to Diagrams 1 thru 4)
Variations or options
in the control system will
change the basic wiring diagrams slightly, however,
the sequence of events will be similar.
The following starting sequence is for dual com-
pressor units. The sequence for single compressor
units is identical except for the obvious reference to
the second unit. Once the system ON-OFF switch is
pushed on the ON position, the unit will operate com-
pletely automatically.
1. Check or throw to “auto” position switches S3
and S4 (pumpdown switches). Switch is in “auto”
position during normal operation.
2. With main power on,
power to the control circuit
from L1 and L2 is fed through fuse
F1
to terminal
COMPRESSOR LOCATION
WHR-020A THRU 060A
FIGURE NO. 17
TOP VIEW OF UNIT
Models
WHR-OO8A thru 015A are
single compressor units.
3.
4.
5.
6.
7.
8.
9.
10.
25. The power from 25 is fed thru NC contacts to
relay R3 and R4 to energizethe compressor crank-
case heaters, when the compressors are not
oper-
ating. The indicator lights should show the heaters
on. Power is also supplied to the main system On-
Off switch,
S1.
Closing switch
S1
energizes System No. 1 and
System No. 2.
Referring to System No. 1, power at terminal 2 in-
dicates power to the system by lighting the red
“Power on” liaht.
Provided
operating
safety controls are closed
(FS1,
OP1,
HP1 and
MP1
or
OL1
when external
overloads are used), power at terminal 3 will ener-
gize safety light, indicating the system is ready
to run.
Referring to the standard non-recycle, pumpdown
operation of the Schematic Wiring Diagram, relay
R1
and R3 are normally open and power cannot
reach compressor starter. Power can reach starter
only by energizing
R1
which is controlled by ther-
mostat
TC1
through the compressor lead-lag switch
(dual units only) and the pumpdown switch S3.
When cooling is required, power is supplied to
terminal 4 through water thermostat
TC1
energiz-
ing relay
R1,
indicator light LT5.
When
R1
relay is energized, contact
R1
will close
and open the liquid line solenoid valve
LLS1.
If low pressure control
LP1
is open, the opening
of
LLS1
will allow refrigerant to flow into the low
side building up pressure which will close
LP1
and the compressor will start.
Meanwhile, time delay TD3 is timing the second
compressor. After the time delay closes, power is
fed to control system No. 2 and the same sequence
of starting for the second compressor is repeated.
OFF CYCLE
Referring to the Schematic Wiring Diagrams
when
thermostat
TC1
is satisfied, the electrical
circuit
to
terminal No. 4 (or No. 10 for second system), will be
broken opening relay
R1
de-energizing the liquid line
solenoid and indicator light LT5. The compressor wi II
continue to operate through the contacts of R3 relay.
Note that R3 relay is now energized through its own
contacts and the compressor is on the pumpdown
cycle. When the compressor has pumped most of the
liquid refrigerant from the cooler, the low pressure
cut out,
LP1
will open and de-energize R3 relay. This
locks the compressor off the line until the thermostat
TC1
calls for cooling again, energizing
LLS1
and
R1
and closing LPI.
COMPRESSOR HORSEPOWER
TABLE NO. 6
MODEL
NUMBER
COMPRESS
CI
OR NOMINAL HP
-3MP.
1
COMP.
2
WHR-008A
7%
WHR.OlOA
10
WHR-015A
15
-
WHC
. . ...1-020A
G
10
WUS-025A
II.
II.
15
15
WIJ’C
,J-030A
20
20
Whn-vr,
w
JD
nr,
*
I
_r
13
I
^.
23
WHR-050A
2.5
?5
1
WHR-060A
3J
I
1_
35
Paoe
11
ELECTRICAL
MODELS WHR-070A THRU 120A
FIELD WIRING
3. Close all circuit breakers in both
panels.
4.
Power leads must be run into each panel and be con-
nected to the power terminal block. Table 8, Page 22
gives the recommended lead wire size for each circuit
which is based on the use of 3 conductors in a race-
way. Refer to the National Electric Code for other
type wire or special instructions. All Field wiring
must comply with Local, State and National Electric
Codes.
Close control circuit system switch
S1
located on
the outside face of the Left Hand panel.
From the power connection block to the contactors,
overloads and compressor motors, the wiring is fac-
tory installed, ready for operation.
Red power lights
LT1
and LT2 will be energized.
Circuit
#1
(odd numbered components) will be
energized thru safety controls (Freeze & High
Pressure Controls) and safety light LT3 wi II
light as controls are closed (Normal position).
All compressor motor overload protector relays
MP1
& MP3 will be energized closing contacts
in safety circuit.
5.
6.
Although there is no specific requirement, inter-
locking of a flow switch and the condenser pump
starter (or air cooled condenser fan) is suggested for
the mostdependable and economical system operation.
The cooler pump should operate continuously, even
when the unit is not operating.
Close pump down switch S3 (Auto Position).
Switch
#1
on thermostat
TC1
closes (due to in-
crease in entering water temperature to cooler) and
followina sequence occurs.
The condenser pump or air cooled condenser fan
should be Field interlocked by connecting toterminals
8, 12, 36, 40 and 14 & 42 in the following manner, and
as indicated in Diagrams 5 and 6.
a.
b.
C.
d.
If the tower or air cooled condenser has only one
pump or fan, jumper terminals 8, 12, 36 and 40 and
connect the motor starter
coil
to any one of these
terminals, and also to terminal 14
or
42. Power at
these terminals is 220V; therefore, the pump or fan
motor starter coil must be 220 volts.
e.
If two towers or air cooled condensers are used (one
for each circuit), connect one pump or fan starter to
terminals (8 and 12) and 14 and the other pump or fan
to terminals (36 and 40) and 42.
f.
g.
Connecting the unit as indicated above will provide
tower pump or condenser fan operation when any com-
pressor is operating.
Referring to Diagrams 5 and 6, the flow switch is
interlocked by removing jumper between terminals 25
and 26 and wiring the switch contacts into the system
as is shown on the Schematic Wiring Diagrams. When
so wired, the chilled water pump must be operating
before power can be applied to start this system. Note
that the crankcase heaters will be energized regard-
less of water flow. The flow switch is recommended
and does not have the shortcomings of interlocking
the cooler pump starter. A flow switch must be used
for leaving water temperoture of 42 F and lower.
h.
Energizes
10 second time delay relay
TD1
to
provide a delay on starting circuit #2.
Energizes light LT5, indicating stage 1 cooling
is required.
Energizes TD3 10 second delay relay to provide
delayed start of compressor
1B.
Energizes run relay
R1
closing contacts to open
liquid line solenoid
LLS1,
allowing liquid re-
frigerant to flow into cooler.
Low side pressure will increase closing Low
pressure switch
LP1
energizing compressor con-
tactors
Ml and M3 and starting compressor motor
1A (Left Hand).
Non-recycle relay R3 is energized closing con-
tacts R3.
If oil pressure does not build up T2 contact in
oi I pressure,
safety control
OP1
will close,
energizing a heater in the control. If pressure
does not build up in 120 seconds, the heater wi II
cause the contacts
OP1
to open and shut down
the compressor.
If suction pressure does not build up to 56 psi,
the T2 contact in freeze control will close and
open contacts
FS1
after 60 seconds.
7.With a further increase in inlet water temperature,
thermostat switch
#2
will close. If 10 seconds has
elapsed since switch #1 closed, contacts TD3 in
time delay relay will be closed.
a. Light LT7 will be energized, indicating that
STARTING SEQUENCE
8.
(Refer to Diagrams 5
&
6)
cooling on stage 2 is required.
b. Relay R5 is energized, closing contacts R5
energizing contactors
M5
& M7 starting com-
pressor motor 1B (Left Center).
A further increase in water temperature will close
thermostats 3 and 4, starting compressors 2A and
2B in a similar manner.
Variations or options in the control systems will
change the basic wiring diagrams slightly; however,
the sequence of events will be similar.
The following starting sequence covers one circuit
of a two circuit, four compressor model. The second
circuit operates in a similar manner.
1. Close the main disconnect switches to both cir-
cuits 1 and 2.
9.When compressor contactors Ml, M3,
M5
and M7
are eneraized.
relays
R3 and R7 are eneraized.
a.
b.
2. Power for the control circuit is taken from circuit
#1
power terminal block; therefore, circuit
#1
dis-
connect must be closed to run the unit.
The
normally
closed contacts on R3
will
open
whenever compressor is operating, thus turning
off the compressor crankcase heaters.
The normally open contacts R3 and R7 will
close whenever the compressor is operating,
which will run the cooling tower pump or air
cooled condenser fan when connected as in-
structed in Field Wiring section.
Page 12
MODELS WHR-070A THRU 120A (Continued)
OFF CYCLE
(Refer to Diagrams 5 & 6)
On a decrease in entering water temperature thermo-
stat
(TC1),
stage
#2
will be satisfied and the con-
tacts will open.
1. LT7 cooling light will turn off.
2. R5 relay will be de-energized, contacts R5 will
open and de-energize
contactors
M5
& M7.
3. Compressor 1B will turn off immediately.
A further decrease in entering water temperature
wi II open thermostat contacts
#1.
1.
R1
relay will be de-energized, opening contacts
R1
which allows the liquid line solenoid to close.
2. Refrigerant flow to the evaporator will be shut off
and the unit will begin to pump down.
3. The compressor will continue to operate thru
pump-
down relay R3 since
R1
is open.
4. The suction pressure will drop until low pressure
switch
LP1
opens.
Contactors
Ml & M3 and relay
R3 will open and compressor 1A will turn off and
stay off until relay
R1
is again energized thru the
thermostat.
In the event compressor 1A is off on oil pressure
safety
(OP1)
or motor overload protection MP1, then
compressor 1B will serve as the pumpdown compress-
or.
1.
2.
3.
4.
Again thermostat
#2
will open and de-energize re-
lay R5 and open contacts R5.
The compressor 1B will continue to operate thru
pumpdown relay R7. R7 will be in the circuit in
this case since the auxiliary contact on
Ml
con-
tactor
is closed.
#1
thermostat will open on further decrease in
water temperature, closing the liquid line solenoid
(LLS1)
thru
R1
relay.
Compressor 1B will continue to run until the cir-
cuit is opened by low pressure control
LP1.
FIGURE 18
COMPRESSOR LOCATION
(REFERENCE TO ELECTRICAL DIAGRAMS 1 & 2)
COMP.
1A
COMP.
1B
COMP. 20
-
COMP. 2A
-
I
CONTROL
PANEL NO. 1
CONTROL
PANEL NO. 2
1
TOP VIEW OF UNIT
TABLE 7 COMPRESSOR HORSE POWER
Page 13
/